I. Safety precautions
Before use, read through the operating instructions to ensure proper using. Please keep it well so that the professional technician can refer to it anytime. 1. Installation safety considerations Access to the unit must be reserved to authorized personnel, qualified and trained in monitoring and…
-
If any maintenance operations are carried out on the unit, lock the power supply circuit in the open position ahead of the machine. If the work is interrupted, always ensure that all circuits are still deenergized before resuming the work. ATTENTION: Even if the unit has been switched off, the power…
-
The refrigerant pipelines can break under the weight and release refrigerant, causing personal injury. Do not climb on a machine. Use a platform, or staging to work at higher levels. Use mechanical lifting equipment (crane, hoist, winch, etc.) to lift or move heavy components. For lighter…
-
II. Product
-
3). External appearance
-
2. Feature
Environmental care R134a refrigerant Refrigerant of the HFC group with zero ozone depletion potential. It is environmentally safe and does not have a phase-out date. Economical operation cost Extremely high full load and partial load energy efficiency. New twin-rotor screw compressor equipped…
-
efficiency and minimum noise and vibration. A heavy-gauge vinyl-coated fan guard protects each fan
Outstanding reliability Full factory testing of all the units ensures a trouble free start-up. Extensive test makes certain that each safety and operating control is properly adjusted, and operates correctly. The unit has passed full factory test before being delivered to ensure the reliable…
-
3. Specification
Single compressor: LSBLGWXXX/C(T3) Cooling capacity Power input kW kW COP kW/kW 3.03 3.12 3.17 3.07 Semi-hermetic screw compressor Circuit A Circuit B Quantity Quantity Oil recharge Circuit A Circuit B Refrigerant Circuit A Circuit B Control Type Evaporator Water content Water flow Pressure drop…
-
Dual compressors
LSBLGWXXX/C(T3) Cooling capacity Power input kW kW 1000 996 318 1200 1203 381 COP kW/kW 3.16 3.13 3.157 Semi-hermetic screw compressor Circuit A Quantity Circuit B Quantity Oil recharge Circuit A Circuit B Refrigerant Circuit A Circuit B Control Type Evaporator Water content Water flow Pressure drop…
-
4. Outline dimension
-
(2) LSBLGW500/C(T3)
-
(3) LSBLGW600/C(T3)
-
(4) LSBLGW760/C(T3)
-
(5) LSBLGW900/C(T3)
-
(6) LSBLGW1000/C(T3)
-
(7) LSBLGW1200/C(T3)
-
5. Refrigeration system
1). Refrigeration system diagram 380/500/600kW 18
-
760/900/1000/1200kW
-
6. Key parts list
No Name Picture Model Brand CSH series Bitzer Germany Fan RZLC-9.0P3 0S6BGE-C RAINBOW China 5 Drier filter SRA Series LIANGJIANG China 7 Electric expansion valve ETS250 Danfoss Denmark 8 Solenoid valve FDF8MJ-10 STF China 12 Safety valve SFV25 T325(2416+ 187) Danfoss Denmark 1 Compressor 4 20
-
7. Application
1).Operating Range Content Running range Ambient Temp. 15℃~52℃(T3) Leaving water Temp. 5℃~15℃ Water flow volume Rating flow volume±20% Max inlet/outlet water Temp. difference 8℃ Fouling factor (m2.℃/kW) 0.086 Voltage tolerance Rating Voltage±10% Phase tolerance ±2% Power supply frequency Rating…
-
таблицы и схемы — в просмотре
-
3).Minimum volume in pipeline system
How to calculate minimum volume in pipeline system: W=QgT/CP▽t W — Minimum water volume(kg); Qg — Total cooling/heating capacity of the terminal(kW); T — Thermal stability time requirement,Take(8~10)×60s; CP — Water specific heat at constant pressure,4.187kj/(kg·℃); ▽t — Water temperature…
-
8. Capacity table
Model 380 500 Leaving Water Temp (℃) Ambient Temperature/℃ Cooling Capacit y (kW) Power Input (kW) Cooling Capacit y (kW) Power Input (kW) Cooling Capacit y (kW) Power Input (kW) Cooling Capacit y (kW) Power Input (kW) Cooling Capacit y (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW)…
-
Ambient Temperature/℃
Model 600 760 Leaving Water Temp (℃) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power…
-
Ambient Temperature/℃
Model 900 1000 Leaving Water Temp (℃) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power…
-
Ambient Temperature/℃
Model 1200 Leaving Water Temp(℃) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) Cooling Capacity (kW) Power Input (kW) 5 1277.2 273.6 1250.4 295.2…
-
9. Accessories
Standard accessories NO. Name Quantity 1 Qualified certification 1 2 User manual 1 3 Water flow switch connectors 1 4 Packing list 1 Optional accessories No. Name Model Introduction Picture Installed on evaporator outlet pipe to prevent heat exchange pipe from frost 1 Water flow switch WFS-1001-H…
-
III. Controls
1. Control flow chart 2 Compressors Double-Head 380VAC 3P+N+PE M ~ M ~ Moulded Case Circuit Breaker Moulded Case Circuit Breaker Phase Sequence Protector Miniature Circuit Breaker Compressor Thermorelay Compressor Thermorelay Compressor Contactor Compressor Star-Delta Start Contactor Star-Delta…
-
Energy adjustment
The unit can adjust capacity by chilled water, please see above picture. Energy adjustment is districted when starting high pressure is too high. High pressure unloading 17Bar 15Bar 3. Normal adjusting Start/stop process 30
-
1).Cooling start
Power-on YES Clear failure Detect fault NO Start on Pump on Water flow switch protection YES Stop. Clear failure NO Water temp is ok.Oil heating time is enough. Stop time is enough. NO Stand by. YES Fan motor on Compressor 25% SV on Compressor Y-△ start Compressor 50% SV on 25% SV off Compressor 75%…
-
2).Cooling stop
MCAC-CTSM-2014-03 stop NO Running is enough. time Stand by YES Unload to 50% step Unload to 25% step Compressor off Fan motor off Compressor 25%SV off Chilled pump off 32
-
MCAC-CTSM-2014-03 Sensors 1). Temperature sensors The temp. sensors use NTC thermistors, they including chilled leaving water temp., chilled entering water temp., ambient temp., condenser fin temp., discharge temp., EXV suction temp.. NO. Name Type Remark 1 Chilled entering water temp. NTC,10k@25℃…
-
2). Fan Control
The number of operating fan as required is according to the discharge pressure. For example, for LSBLGW500/C, there are 8 fans, divided into 5 groups. Opening condition as follow: 3). Solenoid valve control a. Compressor suction injection solenoid valve control Compressor suction injection solenoid…
-
b. Low pressure control
low pressure on 1.5Bar 1Bar stop 5). EXV controller control a. EXV controller wiring principle 24V DC Alarm output to controller CAREL EXV controller EVD Start/stop relay From controller Suction pressure transmitter EXV Suction temp. thermistor EXV controller is started by main base controller.it…
-
Remove cover
Change display Display 1 Display suction superheat 2 Display EXV opening 3 Relay output status 4 Alarm 5 Start of the protection 6 Control state Button Function Prg Open the display screen, enter the password to enter the programming mode • In the alarm state, the display alerts the queue; • When…
-
Running status
MCAC-CTSM-2014-03 Display all status Press Press Esc button b. Controller parameter checking and changing. Checking or changing repair parameters step: ①Press one or more Esc to switch to the standard display interface; ②Press Prg: display interface input password; ③Press ENTER input repair level…
-
The following shows the detailed settings: 13 pages
Drive hardware configuration 1/13 Drive hardware configuration Refrigerant type R134a Valve type Danfoss ETS 250 2/13 Drive hardware configuration Type of probe S1 User-defined Unit type Fin coil evaporator air-conditioner 3/13 Drive hardware configuration Type of probe S1 NTC Carel Auxiliary…
-
Checking or changing manufacturer parameters step
①Press one or more Esc to switch to the standard display interface; ②Press Prg: display interface input password; ③Press ENTER input manufacturer password, starting from the right most digit, each input a digital, confirm with ENTER ; ④ If the password is correct, it will display the following…
-
Relay settings
Alarm relay DI2 settings Invalid Variable 1 on the display Overheat degree Variable 2 on the display Valve opened Sensor S1 alarm management Valve at a fixed position Sensor S2 alarm management Valve at a fixed position S1: calibration offset 0 S1: calibration gain, 4–20 mA 1 Pressure sensor S1…
-
1) Home page Power indicator (yellow), which is on when display is powered on; it is off when powered off. 2) Status indicator (green), which flashes at low frequency when display is normally operative, otherwise it is off. 3) Communication indicator (red), which flashes at high frequency when…
-
MCAC-CTSM-2014-03 Mode setting page Password input page Mode setting page Control mode and working mode are to be set in this page: 1. Control mode and running mode which have been selected currently for units are displayed here, and this position will correspondingly vary according to the choices…
-
1. Main page System Status: Current system status of units is displayed here. The status of system possibly displayed is as follows: 1) Standby status: in normal condition, displaying “Standby status” after the unit is powered on. 2) Running status: indicating that starting of unit compressors has…
-
the following dialog box will be popped up at this moment: click on “CANCEL” if you don’t expect to
execute the start. Ensure unit start-up 8. The sign “Failure to start, please check the status” will appear when the conditions of compressor stating can’t be required. 9. There is a rotate button with a key beside the touch screen. When the units need to be maintained by the user or after sale…
-
If the current temperature return to the rage, click to the“OK”and the unit will start to run normally. Shutting down operation Click on button , and the “Confirm Shutdown” dialog will be popped up. Click on “Confirm” if you ensure execution of Shutdown action, the system status indicates “Shutting…
-
Password error page
“Password Error Page” will be popped up when the password is wrong, click on button to return “Password Input Interface”, input the password again to enter the next page. Note: ① “Max” in the upper left indicates the upper limit of the setting parameter; “Min” in the upper right indicates the lower…
-
Manual
input is allowed Clock setting Click on the numerical box, the numeric keyboard will appear, input the time, click “ENT” to save and take effect. Click “ESC” to cancel the input value. Note: Please pay special attention in setting of time and date to the fact that setting of non-existent date or…
-
Manual Input
Is allowed Inching switch Automatic On/Off setting Any time every day in a week can be selected, and the units will be started or stopped at the time points. When a period of continuous running time (for example from 10:00 Tuesday to 16:00 Thursday) is necessary, you can set the time 10:00 in…
-
Click on
MCAC-CTSM-2014-03 to read serial port information when the unit need to be multiple controlled. Status Click on in main page to check the current unit status information. Status information The upper left in the page display the refrigerant type; the upper right display the station number address…
-
Current data display
Input Input status “ON” as displayed indicates the input point is closed; “OFF” as displayed indicates the input point is open. Note: ① “Remote Start/Stop” is available only under REMOTE mode. ② “Water Switch”: indicating that current water flow status of chilled water system. “OFF” displayed in no…
-
Output
“ON” as displayed indicates the output point is energized; “OFF” as displayed indicates the output point is de-energized. Alarm Alarm information page Click on button in Main Page to enter the alarm information page. If there is any alarm, the unit will execute alarm procedure action. The unit…
-
shown in Picture 8.2. Max.5 warning messages can be recorded meanwhile. The messages will be updated
automatically if there are more messages. History alarm information query Note: 1. The history alarm information record the unit operating parameters when there happen unit alarms during the compressor running. NO. Interface in English 1 Water flow fault 2 Anti-freeze Protection 3 1# High-pressure…
-
MCAC-CTSM-2014-03 29 Mode water temp. protection 30 1# EXV module failure 31 2# High pressure protection 32 2# Low pressure protection 33 2# Compressor motor protection 34 2# Oil level protection 35 2# Contactor protection 36 2# Oil differential pressure protection 37 2# Compressor overload 38 2#…
-
Click on
MCAC-CTSM-2014-03 to enter the next page. Note: ① Max.8 units can achieve combination control, the unconnected unit can access the combination control system at any time as long as the unit is powered on and connected with the system by communication cable. ② The “Status” displays “Run” until the…
-
MCAC-CTSM-2014-03 Control screen menu structure Touch screen tree diagram Homepage Mode Setting Main Page Setting (Password Input) Multi-Status Alarm User Parameter Setting Multi Units Status Alarm Information Module Choose Clock Setting Adjust Screen Automatic On/Off Status Information 1 Comm.…
-
MCAC-CTSM-2014-03 Safety protection Name Code Brand Setting Range Low-pressure Switch YK-0.03/0.10O-R-7000 JUNLE 0.03~0.10MPa High-pressure Switch 1 YK-2.1/1.7-CR-7000 JUNLE 1.7~2.1MPa High-pressure Switch 2 YK-2.2/1.8-CR-7000 JUNLE 1.8~2.2MPa Low-pressure Sensor(For main control board) AKS33…
-
IV. Electrical control
1. Electrical data LSBLGWXXX/C(T3) Standard voltage Voltage range Max. running current Max. power consumption Rated current Compressor A Locked rotor Amps. Max. allowed current Rated current Rated power Compressor B Locked rotor Amps. Max. allowed current Rated current Rated power Fan Full load…
-
provides overload and short circuit protection
2) Power protector This module is used to detect power supply and provide protection in case of phase loss, phase sequence, and under voltage of incoming line power, so as to prevent damage to the compressor or other components caused by power failure. Some models also provide protection for…
-
Electrical components parameter setting
1)Moulded case circuit breaker TEST key: to press to test whether the breaker is normal in stop condition Unit Type 1000 1200 Remarks:/ Compressor Startup Current 586+586 586 805 805+805 805+805 Tripping value Maximum Running Current of the Entire Unit 287+287 287 368 368+368 412+412 Value Ir…
-
3) Time Relay
Time’s up LED Up display green Power LED On display red T: 6S Time relay use Omron H3Y type. 4) Compressor and fan thermal overload relay Thermal overload relay takes advantage of heating effect to protect the compressor and fans. TEST key: to press to test whether the overload relay is normal in…
-
calculated value is 4.17; in practice, set the value to 4.15
Unit Type 1000 1200 Maximum running current of compressor 287+287 287+368 368+368 412+412 Transformation ratio of current transformer 300/5 500/5 500/5 400/5 300/5$500/5 500/5 500/5 Thermal relay value of compressor 4.8 3.7 4.2 3.6/3.6 4.8/3.7 3.7/3.7 4.2/4.2 Fan motor thermal relay value: Unit type…
-
L3
Alarm Water Pump Heating Lamp (Heat pump) Cooling Lamp (Heat pump) Aux. Heater Multi-units communication interface (Only Heat Pump) C/H Mode Switch Remote Stop Remote Start 4. Water Flow Switch Air-cooled screw chiller technical manual MCAC-CTSM-2014-03 Field wiring 1) Wiring diagram…
-
[900&1000&1200&1420kW]
2# Alarm 1# Alarm Water Pump Heating Lamp (Heat pump) Cooling Lamp Aux. Heater (Heat pump) Multi-units communication interface 2A (Only Heat Pump) 2A C/H Mode Switch 4A Remote Stop Remote Start Water Flow Switch 6A 2) Recommended cable and mould case circuit breaker Model Recommended cable…
-
Cable introduction
BVR:Copper core PVC insulated soft wire Domestic model Conductor material BVR70 Cu BVR95 Insulator material Nominal section area (MM ²) UL model PVC 70 2/0 Cu PVC 95 4/0 BVR120 Cu PVC 120 250 BVR150 Cu PVC 150 300 BVR185 Cu PVC 185 400 BVR240 Cu PVC 240 500 BVR300 Cu PVC 300 600 BVR400 Cu PVC 400…
-
Water flow normal
Connect the CDM NC of the water flow switch to customer terminals 5 and 6. Water flow switch Alert status MCAC-CTSM-2014-03 6) Combination wiring Combination connection method 1# Unit 8# Unit 2# Unit Customer terminals or the last unit Customer terminals Customer terminals ○1 . Terminal 9 is A+…
-
The wiring ports for remote start/stop, flow switch, water pump linked control, alarm indication, etc. are reserved in the electrical cabinet of the unit, with the numbers shown in the diagram below. Only double head Customer wiring terminal Inside electric control cabinet Inside electric control…
-
V
Installation 1. Unit installation MCAC-CTSM-2014-03 1).Lifting ○1 Hoist the unit according to the following chart strictly. The steel rope shall wind the lifting hook one circle to prevent steel rope slipping and causing danger when the weight is unbalanced. ○2 Must use enlargement pole prevent…
-
3) Dimensions& Vibration Isolators
Vibration isolators are recommended for all roof mounted installations or wherever vibration transmission is a consideration. Neoprene Isolation is optional, it is recommended for normal installations and provides good performance in most applications for the least cost. Spring isolators are level…
-
4).Spaces
Reserve the spaces required for unit installation, operation and maintenance. The installation place of the unit shall be free from the effects of fire, inflammables, corrosive gas or waste gas as much as possible; the ventilation space shall be reserved there; proper measures shall be taken to…
-
2. Water pipeline system installation
1) Water treatment Use of untreated water or incorrect water makes unit operation low efficiency and could lead to heat exchanger damage. If the resulting from equipment scaling, corrosion, rust, produce the algae or siltation etc, must ask qualified water treatment engineering company or personnel…
-
Propylene Glycol
Modification coefficient Quality of glycol (%) Cooling capacity modification Power modification Water resistance Water flow modification 1.000 0.99 0.979 0.964 0.95 0.925 1.000 0.992 0.983 0.975 0.967 0.96 1.000 1.029 1.167 1.364 1.648 2.056 1.000 1.013 1.035 1.063 1.098 1.145 0 10% 20% 30% 40% 50%…
-
Error
Error Recommendation MCAC-CTSM-2014-03 Recommendation Recommendation Error 4) Water pipeline installation Fig.4-4 Due to the variety of piping practices, it is advisable to follow the recommendations of local authorities. The installation and insulation of the water pipelines of the air conditioning…
-
(1) The flow switch shall be installed on the pipe vertically
(2) The straight pipe section at each side of the flow switch shall have a length that is at least 5 times the pipe diameter; do not install it near the elbow, orifice plate or valve. (3) The direction of the arrow on the flow switch must be consistent with the direction of water flow. (4) In order…
-
flexible connections can reduce vibration transfer
14) The chilled water pipeline and expansion tank shall be subjected to insulation treatment, and the maintenance and operation part shall be reserved on the valve connections. 15) After the air-tightness test is carried out, and the insulation layer is applied on the pipeline, so as to avoid heat…
-
Wiring installation
WARNING: In order to prevent any accident of injury and death during the site wiring, the power supply shall be cut off before the line is connected to the unit. Wiring must comply with all applicable codes and ordinances. Warranty is voided if wiring is not in accordance with specifications. An…
-
CAUTION: An independent power supply box needs to be equipped with the power supply of the
water pump. (12) The wiring ports for remote start/stop, flow switch, cool/warm switch, water pump linked control, alarm indication, etc. are reserved in the electrical cabinet of the unit, with the numbers shown in the diagram below. (13) Passive inching button is used for remote start and stop…
-
VI. Commissioning
1. Pre start-up (1) Electrical system inspection Inspect whether power distribution capacity is compliant with the power of the unit before the first start-up, and whether the diameter of the selected cable can bear the maximum working current of the master compressor. The max economical conveying…
-
in operating
(2) Refrigeration System Inspection 1) The discharge line valve and suction line valve of the compressor must be fully open (turn anticlockwise to open) and the cores shall be tightly locked to prevent leakage of refrigerant. 2) Inspect whether moisture content of the system exceeds the limit…
-
the start-up, inspect whether the liquid/air sampling stop valve is open
7) After the unit is installed and before connected, it is required to tighten the connections in the electrical cabinet of the unit one by one. 8) Inspect the bolts of the unit for looseness. After the unit is transported and installed, it is required to inspect whether the fixing bolts of the unit…
-
transfer. Thermostatic insulation and enclosing measures shall be taken for the temperature
sensing device. Inspect whether there is temperature deviation for the entering and leaving water temperature sensor caused by insufficient heat transfer oil in the thermostatic pipe. 2. Start-up 1) High/low voltage value of the system. In the case of the unit shut-down and waterless in a long time…
-
Compressor oil
heater is working when the unit is electrified. 3) Inspect whether there is alarm for trouble of the display screen. if there is, the trouble must be corrected. 4) Inspect the electronic expansion valve control module for alarm trouble. 5) Inspect whether various temperature points displayed on the…
-
Working Condition
Optimal range Limit Range Discharge temp. ℃ 60~80 <110 Suction temp. ℃ 3~12 Condensation temp. ℃ 46~51 <65 Evaporation temp. ℃ -1~4 <15 Suction super-heating degree ℃ 4~8 ~ Discharge pressure MPa 1.2~1.4 <1.8 Suction pressure MPa Discharge super-heating degree ℃ 0.28~0.38 10~30 <0.38 Super-cooling…
-
VII
MCAC-CTSM-2014-03 Maintenance In order to ensure the long term safe operation, to extend the service life of unit, reduce the failure and repair, should be regularly maintained and checked on the unit 1. Daily maintenance 1). Switch machine daily by local and remote two modes, the local switch unit…
-
Maintenance
frequency Qualify standards (Settlement) Note Drainage Anytime Drain all the water if it is not used for a long time Drain water in the distribution pipe Action Once/Month Check according to ‘Protection Devices Action Value’ Whether the match point is good Finger Once/ Half of a year Action…
-
If only to clean the dry filter, but not to replace it, before removal of the filter, ensure that the refrigerant in the dry filter is completely discharged and the dry filter has remained not in use for a time (to ensure the temperature of the dry filter core is close to the ambient temperature) so…
-
VIII. Troubleshooting
1. List of failures Failure display Flow switch failure Name of failure Flow switch failure Source of failure Flow switch Freeze protection Freeze alarm Antifreez e Switch High-press ure alarm High-press ure alarm High-pres sure switch Low-press ure alarm Low-press ure alarm Low-pres sure switch…
-
failure is confirmed manually on touch screen as required after switch
resetting. Report compressor overload protection when the current value of unit compressor is greater than the setting value and energy accumulated to result in thermo relay trip. Stop the module immediately in the failure stop procedure, and save the content of failure. Do not switch on the units…
-
Differential
pressure alarm Differential pressure alarm Differenti al pressure switch To be detected in running. Currently, there are two modes, one is direct use of differential pressure switch, namely that when the difference between high pressure and low pressure of the system is smaller than the setting…
-
Common troubleshooting
1) High voltage protection High voltage protection Yes Yes Adjust operation mode Reversed cooling and heating No Blower stops rotating or rotates in reversed direction when cooling; water pump is not open or the flow insufficient when heating Yes Inspect the blower or open the water pump. No Yes…
-
Low voltage protection
Low voltage protection Yes Yes Reversed cooling and heating Adjust operation mode No Yes Compressor suction stop valve is not open. Open the suction stop valve. No Yes Blower stops rotating or rotates in reversed direction when cooling; water pump is not open or the flow insufficient when heating…
-
Overheat discharge temperature protection
Overheat discharge temperature Yes Yes Inspect and repair the leakage point and then add refrigerant. Leakage of refrigerant No Yes Expansion valve can not open (broken capillary pipe or leakage). Replace the expansion valve. No Yes Replace the one way valve. One way valve is blocked. No Yes Wrong…
-
MCAC-CTSM-2014-03 Compressor overload protection Compressor overload Yes Yes Replace the protection module. Compressor protection module is in trouble. No Inform the customer service center. 5) Differential pressure alarm Differential pressure alarm Yes Yes Reduce water flow for air conditioning by…
-
MCAC-CTSM-2014-03 Flow switch failure Flow switch failure No Yes Water pump is not open. Open the water pump. No Yes Install or Inspect the installation of water flow switch. Water flow switch is not installed or properly installed. No Yes Water flow switch is in trouble. Service the water flow…
-
MCAC-CTSM-2014-03 Power failure Power failure Yes Yes Wrong power phase sequence Adjust wiring. No Yes Phase loss Inspect power supply. No Yes Failure of phase loss protection False alarm of controller Replace phase loss protection. Inspect whether it is frequent, if yes, replace PCB. Inform the…
-
Appendix 1
IX. 1. Temperature-Resistance characteristic sheet for discharge temperature sensor NTC sensor characteristic sheet Unit:Temp:℃--K.Ratio:KΩ,5K@90℃ Temp. Ratio Temp. Ratio Temp. Ratio Temp. Ratio -20 542.7 20 68.66 60 13.59 100 3.702 -19 511.9 21 65.62 61 13.11 101 3.595 -18 483 22 62.73 62 12.65 102…
-
2. Temperature-Resistance characteristic sheet for water temp. sensor, ambient temp. sensor, oil
temp. sensor. Unit:Temp:℃--K . Ratio:KΩ,10K@25℃ NTC sensor characteristic sheet Temp. Ratio Temp. Ratio Temp. Ratio Temp. Ratio -20 103.882 20 12.598 60 2.383 100 0.623 -19 97.868 21 12.023 61 2.296 101 0.605 -18 92.246 22 11.478 62 2.213 102 0.587 -17 86.987 23 10.961 63 2.134 103 0.570 -16 82.065…
-
3. Temperature-Resistance characteristic sheet for EXV temp. sensor
Unit:Temp:℃--K. Ratio:KΩ10K@25℃ NTC Sensor characteristic sheet Temp. Ratio Temp. Ratio Temp. Ratio Temp. Ratio -20 67.74 20 12.09 60 3.02 100 0.97 -19 64.54 21 11.63 61 2.92 101 0.94 -18 61.52 22 11.20 62 2.83 102 0.92 -17 58.66 23 10.78 63 2.75 103 0.90 -16 55.95 24 10.38 64 2.66 104 0.87 -15…
-
Temperature-Resistance characteristic sheet for EXV temp. sensor
Unit:Temp:℃--K. Ratio:KΩ 50K@25℃ NTC Sensor characteristic sheet Temp. Ratio -40 1630,77 -35 1178,11 -30 860,97 -25 636,08 -20 474,78 -15 357,83 -10 272,18 -5 208,83 0 161,56 5 125,97 10 98,96 15 78,29 20 62,37 25 50,00 30 40,34 35 32,73 40 26,71 45 21,92 50 18,08 55 14,99 60 12,48 65 10,44 70 8,78…