Инструкция на Чиллеры MDV (сервис мануалы)
Чиллеры MDV серии MGCi. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
Introduction
Introduction Midea Mini Unitary Chiller is air-cooled chiller and heat pump system, the chiller itself built in with water pump, expansion tank, plate heat-exchanger; it is very simple for installer to install such kind of system. Expansion Tank Pressure Difference Switch Plate Heat-exchanger Water…
-
Model Names of Outdoor Units
-
External Appearance
-
Nomenclature
-
Features
MCAC-TSM-2008-02 4. Features 1. 2. Adopts R410A refrigerant, friendly to our environment. Compact design: built-in with water pump and expansion tank, only need to connect the water pipe, making simple installation. 3. Built-in with emergency switch: switch off the unit manually in any emergency…
-
1. Specification
Model Power supply Capacity Input Capacity Heating Input Max. input consumption Max. input current Starting current Model Type Brand Capacity Input Compressor Rated current (RLA) Locked rotor Amp (LRA) Thermal protector Capacitor Refrigerant oil Model Type Brand Outdoor fan motor Input (Hi/Lo)…
-
Model
Power supply Capacity Cooling Input Capacity Heating Input Max. input consumption Max. input current Starting current Model Type Brand Capacity Input Compressor Rated current (RLA) Locked rotor Amp (LRA) Thermal protector Capacitor Refrigerant oil Model Type Brand Outdoor fan motor Input (Hi/Lo)…
-
Model
Power supply Capacity Cooling Input Capacity Heating Input Max. input consumption Max. input current Starting current Model Type Brand Capacity Input Compressor Rated current (RLA) Locked rotor Amp (LRA) Thermal protector Capacitor Refrigerant oil Model Type Brand Outdoor fan motor Input (Hi/Lo)…
-
Model
Power supply Capacity Input Capacity Heating Input Max. input consumption Max. input current Starting current Model Type Brand Capacity Input Compressor Rated current (RLA) Locked rotor Amp (LRA) Thermal protector Capacitor Refrigerant oil Model Type Brand Outdoor fan motor Input (Hi/Lo) Capacitor…
-
2. Dimensions (unit: mm)
-
3. Service Space (unit: mm)
-
4. Piping Diagram
Remark: No 16 Name No Name No Name 1 Compressor 6 Capillary 11 Water differential pressure switch 2 High pressure switch 7 Liquid receiver 12 Accumulator 3 4-way valve 8 Plate heat exchanger 13 Low pressure switch 4 Condenser 9 Defrost heater 14 Crankcase heater 5 Filter 10 Water temperature sensor…
-
5. Wiring Diagrams
-
6. Electric Characteristics
-
7. Capacity Tables
Cooling MGC-F05W/N1 Ta 25.0 30.0 35.0 40.0 43.0 Tw 5.0 6.0 7.0 8.0 9.0 10.0 Pf 5.1 5.2 5.4 5.5 5.6 5.8 Pa 1.5 1.5 1.5 1.5 1.6 1.6 Pat 1.8 1.8 1.8 1.8 1.9 1.9 Qev 0.88 0.89 0.93 0.95 0.96 1.00 ΔPev 21.6 23.0 24.6 26.3 27.8 29.5 Pf 4.9 5.0 5.1 5.3 5.4 5.5 Pa 1.8 1.8 1.8 1.8 1.9 1.9 Pat 2.1 2.1 2.1 2.1…
-
Ta 25.0 30.0 35.0 40.0 43.0 Tw 5.0 6.0 7.0 8.0 9.0 10.0 Pf 7.3 7.4 7.6 7.7 7.8 8.0 Pa 2.3 2.3 2.3 2.3 2.4 2.4 Pat 2.6 2.6 2.6 2.6 2.7 2.7 Qev 1.26 1.27 1.31 1.32 1.34 1.38 ΔPev 35.6 37.0 38.6 40.3 41.8 43.5 Pf 7.1 7.2 7.3 7.5 7.6 7.7 Pa 2.6 2.6 2.6 2.6 2.7 2.7 Pat 2.9 2.9 2.9 2.9 3.0 3.0 Qev 1.22…
-
Ta Tw Pf 8.3 8.6 8.9 9.2 9.5 9.8 Pa 2.6 2.6 2.6 2.7 2.7 2.7 Pat 2.9 2.9 2.9 3.0 3.0 3.0 Qev 1.4 1.5 1.5 1.6 1.6 1.7 △Pev 46.4 48 51 Pf 7.9 8.2 8.5 8.8 9.1 9.4 Pa 2.8 2.8 2.8 2.9 2.9 2.9 Pat 3.1 3.1 3.1 3.2 3.2 3.2 Qev 1.3 1.4 1.4 1.5 1.5 1.6 △Pev 29.5 32.1 35.6 39.0 41.8 47.0 Pf 7.5 7.8 8.0 8.2 8.5…
-
Ta Tw Pf 10.9 11.2 11.5 11.8 12.1 12.4 Pa 2.6 2.6 2.7 2.7 2.7 2.8 Pat 3.1 3.1 3.2 3.2 3.2 3.3 Qev 1.9 1.9 2.0 2.0 2.1 2.2 △Pev 31.5 31.7 33.0 33.5 36.0 38.0 Pf 10.4 10.8 11.1 11.5 11.8 12.1 Pa 2.9 2.9 3.0 3.1 3.1 3.1 Pat 3.4 3.4 3.5 3.6 3.6 3.6 Qev 1.8 1.8 1.9 2.0 2.0 2.0 △Pev 29.8 30.4 31.8 33.2…
-
Ta Tw Pf 10.9 11.2 11.5 11.8 12.1 12.4 Pa 2.6 2.6 2.7 2.7 2.7 2.8 Pat 3.1 3.1 3.2 3.2 3.2 3.3 Qev 1.9 1.9 2.0 2.0 2.1 2.2 △Pev 31.5 31.7 33.0 33.5 36.0 38.0 Pf 10.4 10.8 11.1 11.5 11.8 12.1 Pa 2.9 2.9 3.0 3.1 3.1 3.1 Pat 3.4 3.4 3.5 3.6 3.6 3.6 Qev 1.8 1.8 1.9 2.0 2.0 2.0 △Pev 29.8 30.4 31.8 33.2…
-
Ta Tw Pf 12.4 12.7 13.0 13.3 13.9 Pa 3.5 3.5 3.5 3.6 3.6 3.6 Pat 4.1 4.1 4.1 4.2 4.2 4.2 Qev 2.2 2.2 2.3 2.3 2.3 2.4 △Pev 29.1 29.9 31.0 32.4 34.1 37.5 Pf 11.9 12.2 12.5 12.8 13.1 13.4 Pa 3.8 3.8 3.8 3.9 3.9 3.9 Pat 4.4 4.4 4.4 4.5 4.5 4.5 Qev 2.0 2.1 2.1 2.2 2.2 2.3 △Pev 23.1 23.2 25.4 27.0 28.8…
-
Ta Tw Pf 14.8 15.1 15.4 15.7 16.1 16.4 Pa 3.6 3.6 3.6 3.7 3.7 3.7 Pat 4.1 4.1 4.1 4.2 4.2 4.2 Qev 2.6 2.6 2.7 2.7 2.8 2.8 △Pev 29.0 29.4 30.4 31.2 33.0 34.0 Pf 14.1 14.4 14.7 15.0 15.3 15.6 Pa 4.1 4.1 4.1 4.2 4.2 4.2 Pat 4.6 4.6 4.7 4.7 4.7 4.7 Qev 2.4 2.5 2.5 2.6 2.6 2.7 △Pev 25.8 28.2 28.4 28.9…
-
Ta Tw Pf 15.5 15.7 16.0 16.3 16.5 16.8 Pa 5.0 5.0 5.0 5.1 5.1 5.1 Pat 5.5 5.5 5.5 5.6 5.6 5.6 Qev 2.7 2.7 2.8 2.8 2.9 2.9 △Pev 30.5 32.0 33.0 34.5 36.2 37.6 Pf 14.8 15.0 15.3 15.6 15.8 16.1 Pa 4.5 4.5 4.5 4.6 4.6 4.6 Pat 5.0 5.0 5.0 5.1 5.1 5.1 Qev 2.6 2.6 2.7 2.7 2.8 2.8 △Pev 28.3 29.4 28.3 30.4…
-
Heating
-
8. Operation Limits
Outdoor units 37
-
8.1 Ethylene Glycol Solutions
Water and ethylene glycol solutions used as a thermal vector in the place of water reduce the performance of the unit. Multiply the performance figures by the values given in the following table. Freezing point (°C) 0 -5 -10 -15 -20 -25 Percentage of ethylene glycol in weight 0 12% 20% 28% 35% 40%…
-
9. Sound Level
-
10. Exploded View
-
Part
Quantity No. Part 1 Rear net 1 17 Grille Name 1 Quantity 2 Baffle ass'y 1 18 Axial flow fan 1 3 Rear net clap 1 19 Bearing base 1 4 Condenser ass'y 1 20 Heat-exchanger base ass'y 1 4.1 Condenser inlet pipe ass'y 1 21 Clamp 1 4.2 Condenser outlet pipe ass'y 1 22 Shield pump ass'y 1 4.3 Condenser 1 23…
-
42 Installation
-
Part
Quantity No. Part 1 Rear net 1 17 Grille Name 1 Quantity 2 Baffle ass'y 1 18 Axial flow fan 1 3 Rear net clap 1 19 Bearing base 1 4 Condenser ass'y 1 20 Heat-exchanger base ass'y 1 4.1 Condenser 1 21 Clamp 1 4.2 Condenser inlet pipe ass'y 1 22 Shieled pump ass'y 1 4.3 Condenser outlet pipe ass'y 1…
-
Part name
1 Outdoor units Quantity No. Rear support board II 1 22 Differential pressure valve below joint pipe assembly 1 2 Condenser 1 23 water-up pipe assy subassembly 1 3 Condenser outlet subassembly 1 24 water-inlet pipe assy subassembly 1 4 Condenser inlet subassembly 1 25 Liquid storage pot connect pipe…
-
46 Installation
-
Part
Outdoor units Name Quantity No. Part Name Quantity 1 Rear support board II 1 24.1 Water charge valve 1 2 Condenser 1 24.2 Safety valve 1 3 Fluted pipe ass'y 1 24.3 Water-inlet pipe adapter 1 4 Input pipe ass'y 1 25 Connecting pipe ass'y of liquid accumulator 1 5 Expansion vessel 1 25.1 Capillary 1 6…
-
Part
Quantity No. Part 1 Condenser ass'y 1 23.2 Rubber gasket Name 1 Quantity 2 Partition board ass'y 1 23.3 Electric heating strip 1 3 Expansion vessel 1 23.4 Plate Heat-exchanger 1 4 Accumulator cylinder 1 24 4-way valve ass'y 1 5 Drain Pump 1 24.1 4-way valve 1 6 Rear net clip 1 24.2 Pipe joint 2 7…
-
50 Installation
-
Quantity
No. Condenser assembly 1 18 Handle 2 2 Middle partition plate subassembly 1 19 Adapter, drain pipe 1 3 Expansion vessel 1 20 Display cover subassembly 1 4 Accumulator cylinder 1 21 Bearing 1 5 Water Pump 1 22 Left fixing board 1 6 Rear net clip Expansion tank joint pipe assembly 1 1 Part name Part…
-
11. Troubleshooting
Displaying contents Malfunction or protection STY Remote switch in Standby position (automatic reset) Er01 High pressure protection ( manual reset ) Er05 Low pressure protection Er41 3-phase sequence, current and over-heat condenser temperature protection (manual reset) Er30 Frost prevention alarm…
-
2. Er01
High pressure>4.4MPa, display Er01, compressor and outdoor fan stop, the chiller can only resume from protection manually. Values display indication Er01 Refer to the instruction manual: High pressure protection No Judge 1: check the high pressure switch is well. Replace the high pressure switch Yes…
-
3. Low pressure protection (code: Er05)
Low pressure<0.15MPa, display Er05, compressor and outdoor fan stop; Low pressure>0.3MPa, compressor and outdoor fan restart (3 minutes delay necessary) If Er05 appears 3 times in 1hour, the chiller can only resume from protection manually. Values display indication Er05 Refer to the instruction…
-
1) 2) Outdoor units Electric protection Er41: Phase protection of power supply: When the chiller is powered on, if there is wrong sequence of power phase, lack of power phase, it will show Er41, the chiller can not run. Compressor current protection: If the operating current of compressor reaches…
-
MCAC-TSM-2008-02 Error code Er30: Values display indication Er30 Refer to the instruction manual: Frost prevention alarm. Judge 1: Whether the unit has electric, because: When water outlet temperature (T02)<4℃, water pump and electric heater start working, when water outlet temperature (T02)>6℃…
-
Outdoor units Error code Er61: Values display indication Er61 Refer to the instruction manual: Water delivery sensor T02 malfunction. Yes Judge 1: Whether the sensor falls off. Insert it well. No Judge 2: Check the electrical connection, whether the sensor connects well. No Connects it well. Yes Yes…
-
MCAC-TSM-2008-02 Error code Er62: Values display indication Er62 Refer to the instruction manual: Coil sensor T03 malfunction. Yes Judge 1: Whether the sensor falls off. Insert it well. No Judge 2: Check the electrical connection, whether the sensor connects well. No Connect it well. Yes Judge 3…
-
Outdoor units Error code Er60: Values display indication Er60 Refer to the instruction manual: Water return sensor T01 malfunction. Yes Judge 1: Whether the sensor falls off. Insert it well. No Judge 2: Check the electrical connection, whether the sensor connects well. No Connects it well. Yes Judge…
-
MCAC-TSM-2008-02 Error code Er20: Values display indication Er20 Refer to the instruction manual: Water flow protection. Judge 1: Check whether the differential pressure switch is close. No Close the differential pressure switch Yes Judge 2: Check whether the pump is setting high. No Setting the…
-
10. Error code Er47
Values display indication Er47 Refer to the instruction manual: Remote keyboard communication error Judge : Whether the three connecting lines(red, blue and black) are wrong connected. Yes Connect them well in right sequence. 11. Error code Er45/ Er46 Values display indication Er45/ Er46 Refer to…
-
12. Error code Er90
Values display indication Er90 Refer to the instruction manual: Alarm history records exceeded 99 times In this condition, it must be recovered by manual reset, please do as follow on the control interface Press [esc + set] in the main screen. The label ‘PAr’ will appear. Scroll with ‘UP’ and ‘DOWN’…
-
General Information
MCAC-TSM-2008-02 1. General Information General warning 1. 2. 3. 4. 5. 6. These units have been designed to chill and heat water and must be used in applications compatible with their performance characteristics; these appliances are designed for residential or similar applications. Incorrect…
-
Description of Standard Unit
2. Description of Standard Unit These air cooled reverse-cycle chillers with axial-flow fans operate with refrigerant fluid and are suitable for outdoor installation. They are factory tested and on site installation is limited to water and electrical connections. Structure: Panels and base are made…
-
Installation of Outdoor Unit
MCAC-TSM-2008-02 3. Installation of Outdoor Unit 3.1 Choice of installation site Before installing the unit, agree with the customer the site where it will be installed, taking the following points into consideration: - check that the fixing points are adequate to support the weight of the unit…
-
таблицы и схемы — в просмотре
-
4. Hydraulic Connection
The choice and installation of components is the responsibility of the installer who should follow good working practice and current legislation. Before connecting the pipes, make sure they do not contain stones, sand, rust, dross or other foreign bodies which might damage the unit. Construction of…
-
close to plate heat exchanger. Provided the pump installed outside of unit, the pump shall be connected at water pipe’s outlet. The pump can be easily installed on the unit by removing the pump connection pipe. 1) 2) Important The chillers must be provided with a filling/top-up system connected to…
-
Size and position of connections
-
5. Electrical Connection
The MGC chillers leave the factory already wired, and require the installation of an omnipolar thermal overload switch, a lockable mains disconnecting switch for the connection to the mains power supply, and the connection of the flow switch to the corresponding terminals. All the above operations…
-
Electrical Panel Layout
Electrical Power Connection For the functional connection of the unit, bring the power supply cable to the electrical panel inside the unit and connect it to terminals L-N and respecting the (L) phase, (N) neutral and earth in the case of single phase units (220-240V~50Hz), or L1-L2-L3 phases, N…
-
To install the kit, proceed as follows: - disconnect the power supply and then access the inside f the electrical panel; - connect the remote control module with 3 wires to terminals 15, 16 and 17 on the installer terminal board: connect terminal 15 to terminal Black/gnd on the module; connect…
-
Checking and Starting Up the Unit
MCAC-TSM-2008-02 6. Checking and Starting Up the Unit 6.1 Preparing for first start up Restarting after shutting down for long periods The chiller must be started up for the first time by the Technical Service. Before starting up the chillers, make sure that: All safety conditions have been…
-
Checking and Starting Up the Unit
- Use grommet A for the electrical power cable and grommet B for the other external wires. - Replace the inspection panel. - Position the main switch QF1 (outside the unit) in the “ON” position. - The “POWER” LED on the control panel “ST542” comes on to signal that voltage is present. 6.3 Activating…
-
7. Running and Maintenance
7.1 Operating characteristics Set point in cooling (factory set) = 10°C, Hysteresis = 3°C. The compressor starts with water temperatures above 13°C. The compressor shuts down with water temperatures of less than 10°C. Set point in heating (factory set) = 45°C, Hysteresis = 3°C. The compressor starts…
-
7.2 Routine maintenance
Never perform any cleaning operations before having disconnected the unit from the mains power supply. Regular maintenance is fundamental to maintain the efficiency of the unit both in terms of operation and energy consumption. The Technical Assistance Service maintenance plan must be observed, with…
-
2. 3. MCAC-TSM-2008-02 Prohibition The refrigerant circuit must not be filled with a refrigerant other than that indicated of specification. The use of a different refrigerant may cause serious damage to the compressor. Oxygen, acetylene or other inflammable or poisonous gases must never be used in…
-
Part 4
Controller 1. Standard Controller 80 Installation 79
-
1. Standard Controller
ST542 It is built-in with the chiller at the factory. The front panel of the device functions as the user interface and is used to perform all operations relating to the device. 1.1 Introduction of Keys There are 4 keys on the front panel. Each key has: ● A “direct” action (indicated on the key). ●…
-
(folder Par/CF), parameter CF01=0), analogue input AI2 will not be displayed
• For example the hours of functioning of compressor 2 - CP02 - not available on single compressor machines. Label Visibility Description Change Ai Ai1 Ai2 Ai3 Ai4 // // Dynamic Analogue inputs // di di1 di2 di3 di4 di5 // Dynamic Digital inputs // AO AO1 AO2 AO3 // // // Dynamic Analogue outputs //…
-
NOTE
The local ON/OFF function is deactivated if the device has been turned OFF remotely or if a digital input is configured as a remote ON/OFF. Remote on/standby and cooling / heating possibilities Remote control of the unit can be done by a voltage free contact. Depending on the setting on the digital…
-
2) Select Operating Mode
There are three different operating modes: • Standby mode (StbY) • Heat mode • Cooling mode Instructions are provided below on how to change the operating mode. Controller 83
-
3) Select the Clock(CL)
84 Controller
-
4) Modifying a parameter
Instructions are provided below on how to change a machine parameter. By way of example, let’s look at the CF configuration parameters folder, parameter CF26 (folder PAr/CF/CF26). Controller 85
-
5) Set the set point(SP)
By way of example, we will change the set point value in COOL mode by 12.0 degrees centigrade to12.5 degrees centigrade. 86 Controller
-
Controller
Standard Controller 87
-
6) View and Reset compressor/pump time
Example display and reset time (hours x10) for Pump 2 Press the set key from the main display The label Ai will appear on the display. Use the UP and DOWN keys to scroll the other labels until you find the Hr label. Press the set key to view the first label - which in this case is the running time…
-
The tens of hours of functioning are 2. (Hours expressed
in tens: 2 means 20 hours of operation). To clear pump running time PU02, press and hold the [set] key. To reset the hours of functioning of pump PU02, press and hold [set]. Note: Repeat the procedure described to reset the hours of functioning of the other resources.…
-
8) Manual alarm acknowledgment and reset
Alarm messages blink. How to acknowledge an alarm is explained below. All error messages are shown in the AL folder (see state Menu) An error message will be shown, alternating with the error alert and the main display. The ALARM LED will be permanently on. An error can be acknowledged by pressing…
-
The device will return to the
main display. 9) LEDs and Display The display has 18 icons (LEDs) split into 3 categories (+ decimal point): • Decimal point • States and Operating Modes • Values and Units of Measure • Loads Display Values of up to 4 figures or 3 figures plus a sign can be displayed. LED: decimal point Values are…
-
MCAC-TSM-2008-02 Controller