Инструкция на Чиллеры MDV (сервис мануалы)
Модульные чиллеры MDV серии MGBi 30-250 R410a. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
1 General information
-
1.3 External appearance
-
2. Features
1). Low ambient temperature cooling function (Only for MGCSL-F30W/RN1 and MGCSL-D30W/RN1) The ambient temperature is down to -10℃ in cooling mode, the cooling operating temperature up to 52˚C in tropical model and heating down to -10˚C ambient by added one board (see picture1). Wide ambient…
-
S7 address on PCB should be switched to ON to realize remote control, here are reliable: Remote ON/OFF, remote heating and cooling mode selection, remote alarm. The customer can simply and conveniently control the module and acquire the running information on real time in door. 5)Digital scroll…
-
8).Environmental care
Ecological R410A refrigerant. Chlorine-free and environmental friendly refrigerant, zero ozone depletion potential. High density refrigerant, therefore, less refrigerant required. Leak-tight refrigerant circuit, Brazed refrigerant connections for increased leak-tightness. 9) Economical…
-
3. Specification
Model MGB-F25W/RN1 MGB-F30W/RN1 kW 28 30 Btu/h 95,500 102,300 Heating Capacity kW 29.5 32 Power supply V/Ph/Hz Cooling Capacity Power supply 380-415/3/50 Manual switch A 50 Fuse A 36 Type Quantity Compressor Power input Scroll (constant speed) Pieces 2 Model ZP67KCE-TFD-522 Brand Copeland Capacity W…
-
Connection wire
MCAC-ATSM-2011-12 Operation weight kg 400 Power wire mm2×No. 10×4+10×1 Signal wire 2 0.75×3-core mm ×No. Control type Wired controller 1) Protection for over-high discharge pressure. 2) Protection for over-low suction pressure. 3) Power supply phase sequence protection. 4) Anti-frozen protection in…
-
Model
MGB-D25W/RN1 MGB-D30W/RN1 kW 28 30 Btu/h 95,500 102,300 Heating Capacity kW 29.5 32 Power supply V/Ph/Hz Cooling Capacity Power supply Manual switch A Fuse A 50 36 Type Quantity 380-415/3/50 Constant Speed Scroll + Digital Scroll Pieces 1+1 ZP67KCE-TFD-522+ ZPD67KCE-TFD-532 Model Compressor Power…
-
1) Protection for over-high discharge pressure
2) Protection for over-low suction pressure. 3) Power supply phase sequence protection. 4) Anti-frozen protection in cooling mode. 5) Anti-frozen protection in Winter. 6) Protection for compressor over current. Safety protection device 7) Protection for compressor overload. 8) Outlet and inlet water…
-
Model
MGCSL-F30W/RN1 MGCSL-D30W/RN1 kW 30 30 Btu/h 102,300 102,300 Heating Capacity kW 32 32 Power supply V/Ph/Hz Cooling Capacity Power supply Manual switch A Fuse A 50 36 Type Quantity Pieces Model Compressor Power input 380-415/3/50 Fixed speed Digital Scroll + Fixed speed 1+1 1+1 ZP67KCE-TFD-522…
-
1) Protection for over-high discharge pressure
2) Protection for over-low suction pressure. 3) Power supply phase sequence protection. 4) Anti-frozen protection in cooling mode. 5) Anti-frozen protection in Winter. 6) Protection for compressor over current. 7) Protection for compressor overload. 8) Safety protection device Outlet and inlet water…
-
Model
MGB-F55W/RN1 MGB-F60W/RN1 MGB-F65W/RN1 kW Btu/h 187,660 204,700 221,780 Heating Capacity kW Power supply V/Ph/Hz Cooling Capacity Power supply 380-400/3/50 Manual switch A 125 Fuse A 100 Type Quantity Compressor Power input Fixed speed Scroll Pieces 2 Model SH140A4ALC Brand Danfoss Capacity W…
-
Connection
wire MCAC-ATSM-2011-12 Power wire 2 mm ×No. 16×4+10 ×1 Signal wire 2 0.75×3-core mm ×No. Control type Wired controller 1) Protection for over-high discharge pressure. 2) Protection for over-low suction pressure. 3) Power supply phase sequence protection. 4) Anti-frozen protection in cooling mode. 5)…
-
MBG-F130W/R(S)N1 MGB-F185W/R(S)N1 kW Btu/h 221,780 443,560 631,220 Heating Capacity kW Power supply V/Ph/Hz 380-415/3/50 380-400/3/50 380-400/3/50 Model Cooling Capacity Power supply Manual switch A Fuse A Scroll (fixed speed+digital scroll) Fixed speed Scroll Fixed speed Scroll Model…
-
Weight
MCAC-ATSM-2011-12 Net weight kg Operation weight kg 600 1150 1730 670 1270 2000 Power wire 2 mm ×No. 25×4+16×1 35×3+16×2 75×3+35 ×2 Signal wire mm2×No. 0.75×3-core 0.75×3-core Wired controller Wired controller Control type 1) Protection for over-high discharge pressure. Safety protection device 2)…
-
Model
MGBT-F250W/RN1 Cooling Capacity kW 250 Btu/h 830,000 270 Heating Capacity kW Power supply V/Ph/Hz Power supply Manual switch A Fuse A 450 350 Type Quantity Scroll (fixed speed) Copeland Model Compressor 380-400/3/50 8 SH120A4ALC Brand Copeland Capacity W 111231 Input W 10275 Rate current(RLA) A…
-
1) Protection for over-high discharge pressure
2) Protection for over-low suction pressure. 3) Power supply phase sequence protection. 4) Anti-frozen protection in cooling mode. 5) Anti-frozen protection in Winter. 6) Protection for compressor over current. 7) Protection for compressor overload. 8) Safety protection device Outlet and inlet water…
-
4 Dimension
-
Name 1 Top cover 2 Air outlet 3 Air inlet 4 Water outlet 5 Water inlet 6 Electric control box MCAC-ATSM-2011-12
-
30KW new module
317 874 1865 (Only for MGCSL-F30W/RN1 and MGCSL-D30W/RN1) Front view Left view Top view 23
-
NO. NAME Air inlet Air outlet Water inlet Make-up water inlet Water outlet Drain
-
55/60/65KW module
-
Name 1 Top cover 2 Air outlet 3 Air inlet 4 Water outlet 5 Compressor 6 Electric control box 7 Water inlet MCAC-ATSM-2011-12
-
130KW module
-
Name 1 Top cover 2 Condenser 3 Compressor 4 Evaporator 5 Electric control box Air inlet 6 Water outlet 7 Water inlet 8 Compressor MCAC-ATSM-2011-12
-
185KW module
-
Name 1 Top cover 2 Compressor 3 Evaporator 4 Water outlet 5 Electric control box 6 Water inlet 7 Condenser MCAC-ATSM-2011-12
-
F
-
Air outlet
Air outlet Air outlet Air outlet 1 Air in let Air inlet Air in let t inle Air 7 Air in let No. 32 Name 1 Top cover 2 Compressor 3 Evaporator 4 Water outlet 5 Electric control box 6 Water inlet 7 Condenser 8 Transportation guard plate (Be removed off after installation) 3
-
5 Refrigeration system drawing
5.1 25/30KW module refrigeration system sketch drawing Each module has two compressors with two separate units, one double-pipe evaporator for two systems. Compressor A Condenser 4-way valve B Compressor B Suction pipe Water inlet Water outlet Low pressure cylinder A Low pressure cylinder B 5.2…
-
65KW digital module refrigeration system sketch drawing (MGB-D65W/RN1)
Each module has three compressors with two separate units, one shell and tube evaporator for two systems. Pressure switch low pressure cylinder B Compressor B 4-Way valve B Pressure switch Discharge switch Fan A Fan B Pressure switch EXV T3B Capillary T3A Pressure switch Com. A1 digital Water flow…
-
5.4 185KW module refrigeration system sketch drawing
Each module has six compressors with three separate units, one shell and tube evaporator for six systems. low pressure cylinder B Unit 2 4-Way valve B Compressor B 3" Fan A Fan B Water flow direction EXV Capillary EXV Capillary Condenser Compressor A Dry type evaporator 4-Way valve A Unit 3 low…
-
6. Piping diagram
6.1 25/30KW module water pipeline sketch drawing The table below describes the symbols. Symbol 36 Symbol explanation Symbol Symbol explanation Stop valve Y-shaped filter Pressure gauge Thermometer Water flow switch Circulating pump Gate valve Check valve Flexible joint Automatic discharge valve
-
30KW module water pipeline sketch drawing
auto-air exchanse valve Fan coil unit Fan coil unit 2-way valve Water pump Expansion tank Y-shaped filiter Water-flow valve Water replenishing valve Fan coil unit Flexible joint 2-way valve 1.5kg<Water replenishing pres<6kg Double -pipe heat exchanger Safety valve Fan coil unit Flexible joint…
-
MCAC-ATSM-2011-12 55/60/65kw&(65kw digital) module water pipeline sketch drawing DN100 The table below describes the symbols. Symbol 38 Symbol explanation Symbol Symbol explanation Stop valve Y-shaped filter Pressure gauge Thermometer Water flow switch Circulating pump Gate valve Check valve…
-
Air-cooled modular chiller unit 50Hz 130KW module water pipeline sketch drawing The table below describes the symbols. Symbol Symbol explanation Symbol Symbol explanation Stop valve Y-shaped filter Pressure gauge Thermometer Water flow switch Circulating pump Gate valve Check valve Flexible joint…
-
MCAC-ATSM-2011-12 185KW module water pipeline sketch drawing The table below describes the symbols. Symbol 40 Symbol explanation Symbol Symbol explanation Stop valve Y-shaped filter Pressure gauge Thermometer Water flow switch Circulating pump Gate valve Check valve Flexible joint Automatic…
-
Air-cooled modular chiller unit 50Hz 250KW module water pipeline sketch drawing Expansion tank Water replenishing Main unit Dirt discharge valve Differential pressure by-pass valve Terminal Drain valve Two-way valve Auxiliary electric heater Three-way valve The table below describes the symbols.…
-
7 Wire Diagrams
7.1 Chiller wiring diagram Attached Drawing (I) Electric Drawing of Main Unit and Auxiliary Unit 25/30KW module 42
-
K1(A)
-
Attached picture (I) Electric Drawing of Main Unit and Auxiliary Unit
55/60/65KW module 44
-
S7
-
Attached picture (I) Electric Drawing of Main Unit and Auxiliary Unit
Air-cooled modular chiller unit 50Hz 46 MCAC-ATSM-2011-12 130KW module
-
N
-
Attached Drawing (I) Electric Drawing of Main Unit and Auxiliary Unit
Air-cooled modular chiller unit 50Hz 48 MCAC-ATSM-2011-12 250KW module
-
7.2 Networking communication schematic of main unit and auxiliary unit
25/30KW module 49
-
The length of wire should be shorter than 500m H1 H2 P1 P2 Yellow Query Fault Gray Black 100Ω A B C N RVV-300/500 4*10+1*6mm Notes The wiring diagram of auxiliary heater and pump is just for reference ,please follow the instructions of corresponding auxiliary heater products. Please choose such…
-
55/60/65KW module
-
130KW module
-
The length of wire
should be shorter than 500m H1 H2 P1 P2 Yellow Gray Black A B C N Notes The wiring diagram of auxiliary heater and pump is just for reference ,please follow the instructions of corresponding auxiliary heater products. Please choose such accessory as power wire , switch of auxiliary heater according…
-
8 Electric Characteristics
-
9 Capacity Tables
-
Heating
-
Cooling: Ambient temp.(℃) Chilled water outlet temp. 60 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW 5.00 33.59 8.81 31.63 9.08 29.84 9.36 28.20 9.65 26.42 10.13 24.31 10.64 6.00…
-
Heating
-
Cooling: Ambient temp.(℃) Chilled water outlet temp. 62 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW 5.00 61.58 15.41 57.98 15.89 54.70 16.38 51.70 16.89 48.44 17.73 44.57 18.62…
-
Heating
-
Cooling: Ambient temp.(℃) Chilled water outlet temp. 64 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW 5.00 67.17 17.00 63.25 17.52 59.67 18.07 56.40 18.62 52.85 19.56 48.62 20.53…
-
Heating
-
Cooling Ambient temp.(℃) Chilled water outlet temp. 66 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW 5.00 72.77 17.97 68.52 18.52 64.64 19.10 61.10 19.69 57.25 20.67 52.67 21.70…
-
Heating
-
Cooling: Ambient temp.(℃) Chilled water outlet temp. 68 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) kW kW kW kW kW kW kW kW kW kW kW kW 5.00 145.54 35.93 137.04 37.05 129.29 38.19 122.20 39.37 114.50 41.34 105.34…
-
Heating
-
Cooling: Ambient temp.(℃) Chilled water outlet temp. 70 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW 5.00 207.12 55.49 195.03 57.20 183.99 58.97 173.90 60.80 162.94 63.83 149.91…
-
Heating
-
Cooling: Chilled water outlet temp. 72 Ambient temp.(℃) 21.00 25.00 30.00 35.00 40.00 46.00 52.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW 5.00 279.89 68.96 263.55 71.09 248.63 73.29 235.00…
-
Heating
-
10 Exploded View
-
Part Air-cooled modular chiller unit 50Hz Name Rear—front net 2 Condenser right seal board 3 Double-pipe heat exchanger 4 Condenser right seal board ass'y ass'y Quantity No. Part Name Quantity 2 24 underpan parts 1 25 underpan bracket Reinforcement bracket E-part box ass'y Input pipe ass'y of B unit…
-
Part Name Rear—front net 2 Condenser right seal board 3 Double-pipe heat exchanger 4 Condenser right seal board 5 Input pipe ass'y of B unit 5.1 Electronic expansion valve 6 6.1 Input pipe ass'y of A unit Filter 7 Input pipe ass'y of A unit 7.1 Electronic expansion valve 8 Output pipe ass'y of B…
-
78 MCAC-ATSM-2011-12
-
12.1 13 14 14.1 15 16 16.1 16.2 16.3 16.4 16.5 16.6 17 17.1 17.2 17.3 17.4 17.5 18 Part Air-cooled modular chiller unit 50Hz Name Right seal plate condenser components D A condenser components Motor holder Cover C components of the left seal plate condenser Part B condenser A seal plate condenser…
-
19.1 19.2 19.3 19.4 19.5 19.6 19.7 19.8 19.9 19.10 19.11 19.12 19.13 19.14 19.15 80 Part Name Electrical box ass'y Electronic installation board Dual Relay Compressor capacitor Low temp. cooling module ass'y Relay Contactor Contactor Three-phase power protection devices Wire joint Wire joint Wire…
-
12.1 16.1 16.2 16.3 16.4 16.5 16.6 17 17.1 17.2 17.3 17.4 82 Part Name Right seal plate condenser components D A condenser components Motor holder Cover C components of the left seal plate condenser Part B condenser A seal plate condenser components of the right Supporting board Cover board Cover…
-
18 19 19.1 19.2 19.3 19.4 19.5 19.6 19.7 19.8 19.9 19.10 19.11 19.12 19.13 19.14 19.15 Part Air-cooled modular chiller unit 50Hz Name Pipe joint Base ass'y Electrical box ass'y Electronic installation board Dual Relay Compressor capacitor Low temp. cooling module ass'y Relay Contactor Contactor…
-
21.1 21.2 Part Name A combination of pieces of fixed plate condenser Condenser side board Condenser ass'y A Condenser ass'y B Mid horizontal support Fixed board Mid upright support Pipe fixing clamp Evaporator input pipe ass'y Evaporator input pipe ass'y Cover Cover Triangle reinforcement ass'y…
-
Qty
BOM code No. 1 2024901A0004 202300800003 202401000410 43 44 21.4 21.5 Part Name Three-phase protection device signal output line group Relay Compressor capacitor 21.6 AC contactor 2 202300850050 45 21.7 21.8 Wire joint Wire joint 3 1 202301450122 202301450110 46 21.3 86 Part Name Qty BOM code Motor…
-
Qty
BOM code 1 201290108627 26 2 Part Name A combination of pieces of fixed plate condenser Condenser side board 2 201290108624 27 3 Condenser ass'y A 1 201590100023 No. Part Name Qty BOM code Pole 4 201290108623 Electronic control box door A machine back to the tube components 1 201290190139 1…
-
Part Air-cooled modular chiller unit 50Hz Name Condenser ass'y of A Qty 1 BOM code 201590100030 No. 28.1 Qty 1 BOM code 202301820073 3.2 Fluted pipe ass'y A 1 201690101439 29 1 201690191377 3.3 The condenser assemblies A 1 201690101393 29.1 1 202301820073 4 Condenser ass'y B 1 201590100024 30 4.1…
-
90 MCAC-ATSM-2011-12
-
12.3 Part Air-cooled modular chiller unit 50Hz Name The top beam The condenser seal fittings. II Iron nets fixed plate. II Protect net around pole Trough fixation plate Left right panel by. II Iron nets fixed board I Protect network and In the frame beams Cover Air-cooled electronic control box…
-
Part Name Base weld parts Compressor Storage tank bottom II weld installation Compressor installed base II weld MCAC-ATSM-2011-12 Qty BOM code No. 1 201290100286 50 4 201402300130 50.1 1 201290100264 51 1 201290100273 51.1 Part Name A2 machine back to the tube components Pressure controller B1…
-
2 3 Part Name Column About the protective screen Network Rail fixed plate II Qty BOM code 201290100384 201290100347 201290100349 No. 41.1 41.2 41.3 4 Vertical beam in the frame 2 201290100386 42 5 Roof rack crossbar 2 201290100377 42.1 6 I sealed connector condenser 3 201290100378 43 7 Vertical beam…
-
Qty
BOM code 1 201290100389 55 19.4 19.5 Part Name Electrical component mounting plate II Main control board ass'y Relay 3 6 201390100009 202300800003 55.1 56 19.6 AC contactor 6 202300830520 57 19.7 Transformer 3 202300900109 58 19.8 19.9 19.10 19.11 Wire joint, 5p Wire joint Wire joint Compressor…
-
96 MCAC-ATSM-2011-12
-
69.1 No. 69.1 69.15 Part Name 69.9 69.8 69.14 69.6 69.4 69.7 Part Name 69.1 69.10 Qty BOM code 201290100387 201290100365 201290100386 201290100370 201290100373 201290100369 No. Top cover Front panel II Fixed part of panel Bottom pillar I Pipe support IV Front panel I Qty BOM code 201195300051…
-
Qty
BOM code 1 201690191445 Part Name Outlet pipe ass'y II of condenser Wire casing I Cover of wire casing I Shell-tube heat exchanger Installation base welding parts of compressor Inclined support II Name Qty BOM code 74 Seal plate condenser 8 201290100382 201290190279 201290190280 201790190021 Motor…
-
11 Troubleshooting
11.1 Failure & Protection Codes of the Module 25/30kw module No, Code Trouble 1 E0 Water flow detection error (The third time) 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total water outlet temperature sensor error 5 E4 Outlet water temperature sensor in Shell and tube exchanger…
-
New 30kw module
(For MGCSL-F30W/RN1 and MGCSL-D30W/RN1 only) No, Code 1 E0 Error of outdoor EEPROM 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Error of total outlet water.temp sensor(Be valid for main unit) 5 E4 Error of unit outlet water.temp sensor 6 E5 Pipe temperature sensor in condenser A…
-
55/60/65kw module (Fixed speed)
No, Code Trouble 1 E0 Water flow detection error (The third time) 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total water outlet temperature sensor error 5 E4 Outlet water temperature sensor in Shell and tube exchanger error 6 E5 Pipe temperature sensor in condenser A error 7 E6…
-
No, Code 1 E0 EEPROM error 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total water outlet temperature sensor error 5 E4 Outlet water temperature sensor in heat exchanger error 6 E5 Pipe temperature sensor in condenser A error 7 E6 Pipe temperature sensor in condenser B error 8 E7…
-
130kw module
No, Code Trouble 1 E0 Water flow detection error (The third time) 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total water outlet temperature sensor error 5 E4 Outlet water temperature sensor in Shell and tube exchanger error 6 E5 Pipe temperature sensor in condenser A error 7 E6…
-
185kw module
No, Code 1 E0 Water flow detection error (The third time) 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total water outlet temperature sensor error 5 E4 Outlet water temperature sensor in Shell and tube exchanger error 6 E5 Pipe temperature sensor in condenser A error 7 E6 Pipe…
-
250kw module
No, Code Trouble 1 E0 Error of outdoor EEPROM 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Error of total outlet water.temp sensor(Be valid for main unit) 5 E4 Outlet water temperature sensor in Shell and tube exchanger error 6 E5 Pipe temperature sensor in condenser A error 7 E6…
-
11.2 Troubles and Solutions
Troubles Over high air discharge pressure (Cooling operation) Possible reasons Solutions Air or other non-condensing gas still in the system Discharge gas from refrigerant charging inlet. Re-vacuum the system if necessary. Fins in the condenser are dirty or foreign substance blocking fins Clean…
-
Troubles
Possible reasons Solutions Compressor stops because of integrate temperature sensor or air discharge temperature protection. Over high or over low voltage Confirm voltage not higher or lower than the rated voltage 20V Over high air expelling pressure or excessive low air suction pressure See “Over…
-
12 Installation
12.1 Unit Installation 12.1.1 Transportation The angle of inclination should not be more than 15º when carrying the unit, to avoid overturn of the unit. a. Rolling handling: several rolling rods of the same size are placed under the base of the unit, and the length of each rod must be more than the…
-
55/60/65kw module
130kw module 109
-
185kw module
The position should be provided with an at least 50mm thick wood block, cloth or hard paper, to avoid damages to the unit. The position should be provided with an at least 50mm thick wood block, cloth or hard paper, to avoid damages to the unit. Lifting angle 250KW module The position should be…
-
12.1.2 Installation space
● Requirements of arrangement space of the unit 1) To ensure adequate airflow entering the condenser, the influence of descending airflow caused by the high-rise buildings around upon the unit should be taken into account when installing the unit. 2) If the unit is installed where the flowing speed…
-
130kw module
-
B
Input of airflow A D C 250kw module Input of airflow E Input of airflow Input of airflow The recommend space parameter Module MGB-F(D)25W/RN1 MGB-F(D)30W/RN1 MGCSL-F30W/RN1 MGCSL-D30W/RN1 MGB-F55W/RN1 MGB-F60W/RN1 MGB-F65W/RN1 MGB-D65W/RN1 MGB-F130W/RN1 MGB-F185W/RN1 MGBT-F250W/RN1 A B Installation…
-
12.1.3 Installation Foundation
The unit should be located on the horizontal foundation, the ground floor or the roof which can bear operating weight of the unit and the weight of maintenance personnel. Refer to the operating weight parameters in specification table. If the unit is located so high that it is inconvenient for…
-
185kw module
250kw module 1551 Hole for anchor bolt Drainage channel Concrete Cement mortar 80 Drainage channel 1551 1888 350 Schematic diagram of installation dimension of the unit 12.4 Installation of damping devices ※ Damping devices must be provided between the unit and its foundation. By means of the Φ15mm…
-
MCAC-ATSM-2011-12 The lock bolts can be tightened after the correct operational height is reached. 12.2 Water System Installation Notice: ● After the unit is in place, chilled water pipes can be laid. ● The relevant installation regulations should be abided with when conducting connection of water…
-
l. All possible water pipes in the system to be chilled should be under heat preservation, including inlet pipes and flanges of the heat exchanger. m. The outdoor chilled water pipelines should be wrapped with an auxiliary heating belt for heat preservation, and the material of the auxiliary heat…
-
d. Special grounding screws should be used for earth connection. Bolts should not be installed or removed at will; otherwise flow switches may suffer deformation and failure. e. Flow switches have been set at minimal flow value before leaving the factory. They should not be adjusted below the…
-
Installation of multi-module water system pipeline
1) Installation mode I (recommended installation mode) n :the module quantity, max 16 2) Installation mode II n :the module quantity, max 16 12.2.5 Installation of water system pipeline for 55/60/65KW module Installation of single-module water system pipeline Installation of multi-module water…
-
less than 6 modules
2) Installation mode II n : the module quantity, max 6 less than 6 modules 3) Installation mode III (recommended installation mode) n : the module quantity, max 16 Installation mode A: less than 16 modules Installation mode B: less than 16 modules 120
-
4) Installation mode IV
n : the module quantity, max16 No.n module No.(n-1) module No.1 module No.(n-1) address No.(n-2) address No.0 address Drill dead hole at the position, and move the total effluent temperature sensor at No.0 address to the position No.(n-2) module No.(n-3) module No.2 module No.(n-3) address No.(n-4)…
-
Installation mode A: less than 16 modules
n : the module quantity, max6 m : the module quantity, max6 Installation mode B: less than 12 modules 122
-
12.2.6 Installation of water system pipeline for 130KW module
Installation of single-module water system pipeline Electric control box Total water outlet temp sensor Water intlet Water outlet Installation of multi-module water system pipeline 1) Installation mode I (recommended installation mode) n : the module quantity, max8 No.1 unit No.0 address(main unit)…
-
12.2.7 Installation of water system pipeline for 185KW module
Multi-module combination installation involves special design of the unit, so relevant explanation is given as follows.Installation mode of multi-module combination water system pipeline n : the module quantity, max5 a. Installation mode I (recommended installation mode) No.1 unit No.0 address(main…
-
No.1 unit
No.0 address(main unit) No.1 address No.2 unit No.2 address No.3 address No.n unit (n≤8) No.(2n-2) address No.(2n-1) address Water flow switch Pump Drill dead hole at the position, and move the total effluent temperature sensor at No.0 address to the position (less than 8 modules) Notice: 1) For…
-
55×8 60×8 65×8 MCAC-ATSM-2011-12 65×15 55×16 60×16 65×16 DN125 Table of diameter parameters of main inlet and outlet pipes for 130KW module Unit model x quantity 130×1 130×2 130×3 130×4 Total inlet and outlet water pipe diameter DN65 DN100 DN100 DN125 Unit model x quantity 130×5 130×6 130×7 130×8…
-
Item
Model Water flow rate(m3/h) Minimum Maximum 3.96 4.84 4.68 5.72 MGCSL-F30W/RN1 4.68 5.72 MGCSL-D30W/RN1 4.68 5.72 MGB-F55W/RN1 8.46 10.4 MGB-F60W/RN1 9.28 11.35 MGB-F65W/RN1 10.08 12.32 MGB-D65W/RN1 10.08 12.32 MGB-F120W/RN1 18.54 22.66 MGB-F185W/RN1 27.9 34.1 MGBT-F250W/RN1 38.7 47.3 MGB-D25W/RN1…
-
Vs=volume of water in system, gal(m3) p1=absolute pressure at lower temperature,psia(kPa abs.) p2=absolute pressure at higher temperature,paia(kPa abs.) v1,v2=specific volume of water at lower and higher temperature, respectively, ft3/lb(m3/kg) α=linear coefficient of thermal expansion; for steel…
-
7. Please carefully read the labels on the electric cabinet
8. The user’s attempt to repair the controller is prohibited, since improper repair may cause electric shock, damages to the controller, and so on. If the user has any requirement of repair, please contact the maintenance center. 12.3.2 Power supply specification Items Outdoor power supply Wiring…
-
● All inductive components provided by the user (such as coils of contactor, relay, and so on) must be suppressed with standard resistance-capacitance suppressors, to avoid electromagnetic interference, thus leading to failure of the unit and its controller and even damages to them. ● All weak…
-
12.3.4 Wiring steps
Content 1 Check the unit and ensure that it is connected with grounding wires correctly, to avoid leakage, and the grounding devices should be mounted in strict accordance with the requirements of electrical engineering rules. The grounding wires can prevent electric shock. 2 The control box of the…
-
Fielding wiring
Water pump wiring diagram reference, the control circuit of water pump AC contactor must be passed P1 and P2 contacts of master unit. One water pump 380V 3P 50HZ 380V 3P 50HZ XT4 A B C N P1 P2 Creepage Switch 0# Main unit PCB Contactor winding Contactor Over charge relay Over charge relay Water pump…
-
1 .Wiring of “ON/OFF” weak electric port ○ Corresponding parallel connect the “ON/OFF” port of the main unit’s electric control box, then, connect the “ON/OFF” signal (provide by user) to the “ON/OFF” port of main unit as follows. Red ON/OFF signal Power (DC 12V) Main control board is provided 0#…
-
13 Commissioning
1. Preparation ● After the water system pipeline is flushed several times, please make sure that the purity of water meets the requirements; the system is re-filled with water and drained, and the pump is started up, then make sure that water flow and the pressure at the outlet meet the…
-
14 Maintenance
Maintenance for main components: ● Close attention should be paid to the discharge and suction pressure during the running process. Find out reasons and eliminate the failure if abnormality is found. ● Control and protect the equipment. See to it that no random adjustment be made on the set points…
-
system is discharged. Before injecting refrigerant, the whole refrigeration system must be completely dry and of vacuum pumping. ● Connect vacuum pumping pipe at the fluoride nozzle at low-pressure side. ● Remove air from the system pipe with vacuum pump. The vacuum pumping lasts for above 3 hours.…
-
15 Control System
15.1 PCB Outline and Description 15.1.1 25/30kw module PCB, outlook view 15.1.2 25/30kw module components description No. Detail information 1 Detection of current of the compressor B (protection code P5) Detection of current of the compressor A (protection code P4) 2 Current is not detected within…
-
T4: outdoor ambient temperature sensor (fault code E7)
MCAC-ATSM-2011-12 T3B: pipe temperature sensor of the condenser B (fault code E6 and protection code P7) T3A: pipe temperature sensor of the condenser A (fault code E5 and protection code P6) 1) T4: if there is one system that requires starting outdoor fans, the fans are started through electric…
-
Each modular part of modular unit has the same electric control function, and the main unit and slave units can be set through address code on the electric control board. The address code 0 # is provided as the main unit. The priority of being the main unit is given to the unit with digital…
-
Electronic expansion valve of the system B 17 MCAC-ATSM-2011-12 Electronic expansion valve of the system A Electronic expansion valve is used to control refrigerant flow under different operating modes and different loads. Auxiliary electric heater Attention: the control port value of auxiliary…
-
15.1.3 New 30kw module PCB, outlook view
(Only for MGCSL-F30W/RN1 and MGCSL-D30W/RN1) 15.1.4 New30kw module components description (Only for MGCSL-F30W/RN1 and MGCSL-D30W/RN1) No. Detail information 1 Detection of current of the compressor A1 (protection code P4) Detection of current of the compressor B1 (protection code P5) 2 Current is…
-
3) T4, T3B and T3A: when the temperature sensor is detected to suffer open circuit or short circuit, fault alarm will occur. ● When the main unit suffer fault of temperature sensor: the main unit and subordinate units will be shut down. ● When the subordinate unit suffer fault of temperature sensor…
-
2) Subordinate unit: (water flow detection will not be done)
Air-cooled modular chiller unit 50Hz COM (I) 485 communication port (fault code E2) COM (O) is interconnected with P, Q and E of COM (I), used for RS-485 communication. 1) If faults occur between the wired controller and the main unit module, all modules will be shut down. 18 2) If faults occur…
-
Each modular part of modular unit has the same electric control function, and the main unit and subordinate units can be set through address code on the electric control board. The address code 0 # is provided as the main unit. The priority of being the main unit is given to the unit with digital…
-
15.1.5 55/60/65kw module PCB(Fixed speed), outlook view
-
15.1.6 55/60/65kw module components description
No. Detail information 1 Detection of current of the compressor B (protection code P5) Detection of current of the compressor A (protection code P4) 2 Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the compressor is detected to exceed…
-
Each modular part of modular unit has the same electric control function, and the main unit and slave units can be set through address code on the electric control board. The address code 0 # is provided as the main unit. The priority of being the main unit is given to the unit with digital…
-
PUMP
MCAC-ATSM-2011-12 Attention: the control port value of the pump actually detected is ON/OFF but not 220V control power supply, so special attention should be paid when installing the pump. 20 1) After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up…
-
No. Detail information 1 Detection of current of the compressor A1 (protection code P4) Detection of current of the compressor B1 (protection code P5) 2 Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the compressor is detected to exceed…
-
Adjustment range of constant speed capability: ON and OFF. Adjustment range of constant speed capability: ON and OFF. Total outlet water temperature sensor (fault code E3) 6 Only the main unit is valid, and the subordinate units are invalid. Under refrigerating mode and heating mode, conduct…
-
high-pressure protection of the system B and discharge temperature switch protection (protection code P2); low-pressure protection of the system A (protection code P1); low-pressure protection of the system B (protection code P3); Constant speed compressor: connection of discharge temperature switch…
-
When the power supply returns to normal condition, fault is removed. Attention: phase lace and phase dislocation of power supply are detected only in the early period after the power supply is connected, and they are not detected while the unit is in operation. 29 Output of transformer 30 Output of…
-
15.1.7 130kw module PCB, outlook view
15.1.8 130kw module components description No. Detail information 1 EEV B of No.1 unit 2 EEV A of No.1 unit high-pressure protection and discharge temperature switch protection of the system A of No.1 unit (protection code P0); high-pressure protection and discharge temperature switch protection of…
-
No.1 unit T41 :outdoor ambient temperature sensor(malfunction code E7)
8 MCAC-ATSM-2011-12 As long as one system has requirement to run outdoor fan,the unit controller sent the signal to restart outdoor fan.whether the system runs one fan or two fans is controlled by T41 9 No.1 unit T3-1B :pipe temperature sensor of condenser B (malfunction code E6,protection code P7)…
-
No.2 unit low-temperature ant-freeze sensor TBH2-A 25 Air-cooled modular chiller unit 50Hz No.2 unit Inlet water temperature sensor TBH2-B No.2 unit outlet water temperature sensor (fault code E4) 26 Under cooling mode and heating mode, conduct adjustment according to the magnitude of unit outlet…
-
2)Under heating mode, when the main unit board detects total water outlet temperature to be lower than 45 C, the switch will be closed, and the auxiliary electric heater will begin to work; when the total water outlet temperature is higher than 50 C, the switch will be opened, and the auxiliary…
-
Four-way valve of the system B of No.1 unit;
Air-cooled modular chiller unit 50Hz Neutral line 48 No.1 unit outdoor fan B, controlled by T41 Compressor of the system A of No.1 unit; 49 Neutral line Four-way valve of the system A of No.1 unit; Neutral line 50 No.1 unit outdoor fan A, controlled by T41 1) No.1 unit auxiliary electric heater(only…
-
15.1.9 185kw Module PCB, outlook view
15.1.10 185kw module components description No Detail information 1 Detection of current of the compressor B (protection code P5) 2 Detection of current of the compressor A (protection code P4) Current is not detected within the initial 5 seconds after the compressor is started up. When the current…
-
Air-cooled modular chiller unit 50Hz Total outlet water temperature sensor (fault code E3) Only the main unit is valid, and the subordinate units are invalid. Under refrigerating mode and heating mode, conduct adjustment according to the magnitude of total outlet water temperature. Adjustment range…
-
Control port (reserved) 17 Electronic expansion valve of the system B 18 Electronic expansion valve of the system A Electronic expansion valve is used to control refrigerant flow under different operating modes and different loads. Auxiliary electric heater Attention: the control port value of…
-
15.1.11 250kw Module PCB, outlook view
15.1.12 250kw module components description No Detail information 1 Detection of current of the compressor A1 (protection code P4) 2 Detection of current of the compressor A (protection code P4) Current is not detected within the initial 5 seconds after the compressor is started up. When the current…
-
Spot check. The operating status of outdoor system can be observed through spot check, and specific display contents are as shown in the following figure: 7 ● Display contents of “operating mode”: 1. cooling; 2. heating; 4. pump; 8. Stand-by ● Display contents of “number of online units”: the main…
-
Attention!
Under heating mode, when the main unit board detects total water outlet temperature to be lower than 45℃, the switch will be closed, and the auxiliary electric heater will begin to work; when the total water outlet temperature is higher than 50℃, the switch will be opened, and the auxiliary electric…
-
15.2 Wired controller
KJR-08B/BE: Name of keys on the wired controller and the keypad operation description: 1. ON/OFF button: In the power off status, press this key and the startup indicator comes on, and the wire controller enters the startup status and keeps the current set information such as temperature value…
-
Every time when you press [TIME ON] button, the HOUR and MINUTE of timing startup blink at a frequency of 2Hz. They stop blinking when you adjust the hour and minute; and continue blinking 2 seconds after you stop adjustment. Press [TIME ON] key to select the timing HOUR for adjusting, and the…
-
2. Installation procedure
The wiring procedure and principles are shown in the figure: Note: Please connect the attached shorted wires to the corresponding communication port COM(I) or COM(O) in the main control board of the last parallel unit (dial code ). Directly connect to the last parallel unit if only one unit is…
-
The tables as below contain the operation procedure of wired controller
Operation procedure of wired controller: Step Content 1 Press AUTO/MANUAL mode at shutdown status, you could select MANUAL or AUTO turn-on mode as you want. The function is invalid at startup status. In Manual mode, press [PAGEUP/TEMP+] or [PAGEDOWN/TEMP-] button for select your require online unit…
-
3.ON/OFF operating flow chart
Turn on the unit Power up to module unit and initially deliver power to wire control. Press “mode settings” key to set the intended mode. Press the key again until all modes are showed (i.e. Cooling, Heating and Pump modes.) Press “Manual/Auto” key, enter to manual settings mode. Press “ADD +” and…
-
R 1 ON/OFF TIME ON 6 8 TEMP. SET TIME OFF 7 9 OK MODE 2 12 PAGEUP/TEMP+ ALARM CLEAR 3 QUERY 4 CLOCK 5 LOCK 14 13 PAGEDOWN/TEMP- LOC K HYSTERESIS 10 ADDRESS - 11 ADDRESS+ 16 ADDRESS SET 15 HYSTERESIS ADDRES S SE T 1. Operating instructions of buttons All empires fall, you just have to know where to…
-
minute can be adjusted by “ADDRESS/+” and “ADDRESS/-”, after the adjustment then press the OK
button for the setting confirmation. ⑥⑦ TIME ON/TIME OFF button Press the “TIME ON” button once Press for the first time , and enter to the hour adjustment of timing on, and press again Press for the second time , and enter to the minute adjustment of timing on. The numerical valve of hour and…
-
LCD Diagram of Wired Controller
Display operation mode Display operation status Display Query data Display time-on/off 2. OPERATION PROCEDURE OF WIRE CONTROLLER ● Operation procedure of mode setting 1). Press MODE at shutdown status, you could select appropriate mode as you want. The function is invalid at startup status. 2). The…
-
● Operation procedure of HYSTERESIS TEMP.SET(δ )
1).Through the hysteresis setting, the system can adjust the load effectively. 2). The adjusting logic of cooling mode : (the parameter of δ1,δ2,Tj1 and Tj2 are decided by the outdoor unit) 3). The adjusting logic of heating mode: (the parameter of δ1,δ2,Tj1 and Tj2 are decided by the outdoor unit)…
-
3. INSTALLATION PROCEDURE
Installation procedure: Outdoor unit Outdoor unit #00 #01 Outdoor unit #02 Outdoor unit #15 Wire Controller Wire Controller Wire Controller Wire Controller #00 #01 #02 #15 Use PQE connect with each other when several wire-controllers are parallel. NOTE Please connect the attached shorted-wires to…
-
OUTLINE OF FUNCTIONS
This wired controller provides the following functions: 1). Connect with the outdoor unit through the terminals P, Q and E. Connect with the upper unit through the terminals X, Y and E(reserved).Connect with other wired controllers through the terminals P, Q and E. 2). Set the action mode through…
-
2.Temperature-Resistance characteristic sheet for pipe temperature sensor,ambient temperature
sensor,inlet water temperature sensor and outlet water temperature sensor. Sensor characteristic sheet Unit:Temp:℃--K, Ratio:KΩ Temp. Ratio Temp. Ratio Temp. -20 115.266 20 12.6431 60 2.35774 Ratio Temp. 100 0.62973 Ratio -19 108.146 21 12.0561 61 2.27249 101 0.61148 -18 101.517 22 11.5 62 2.19073…
-
3.Temperature-Resistance characteristic sheet for discharge temperature sensor of digital
compressor. Sensor characteristic sheet Unit:temp:℃--K, Ratio:KΩ Temp . -40 -39 -38 -37 -36 -35 -34 -33 -32 -31 -30 -29 -28 -27 -26 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 Ratio 2889.60000 2704.61400 2532.87200 2373.34200 2225.07800 2087.22000…