Инструкция на Чиллеры MDV (сервис мануалы)
Мини сплит чиллеры MDV серии MDGA-10/SN1, MDGA-12/SN1, MDGA-14/SN1, MDGA-16/SN1. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
1. Model Names of Outdoor Units
-
3. Nomenclature
-
4. Features
4.1 R410A environment friendly refrigerant. 4.2 Energy saving and high reliability By adopting Copeland digital scroll compressor, the capacity can be stepless adjusted and the chiller can bring you more comfortable living conditions with less energy consumption. By adopting high efficiency plate…
-
5. Descriptions of Standard Unit
The air cooled reverse-cycle chillers with axial-flow fans operate with refrigerant fluid and are suitable for outdoor installation. They are factory tested and site installation is limited to water and electrical connections. Structure: Panels and base are made from galvanized steel plate painted…
-
Outdoor unit
10kW 12&14&16kW Water pump box 6 MCAC-UTSM-2013-01
-
6. Specifications
Model MDGA-10/SN1 MDGA-12/SN1 Code 220090400050 220090400030 V-Ph-Hz 220-240, 1, 50 220-240, 1, 50 kW 10 12 Input W 3912 3978 Capacity kW 13.6 14.3 Input W 4216 4164 Max. input consumption W 5430 5615 Max. input current A 27.4 28.2 Power supply Capacity Cooling Heating Starting current 124 130 Model…
-
mm 1057×439×436 1057×439×436 Net/ Gross weight kg 52/57 54/59 Type R410A R410A Charged volume kg 2.7 3.6 Liquid side mm Φ9.5 Φ9.5 Gas side mm Φ19 Φ19 Water inlet/outlet mm DN32 DN32 Refrigerant Refrigerant pipe diameter Pipe diameter Control Ambient temperature Wired controller KJR-08B/BE ℃ Cooling…
-
Model
Code Power supply V-Ph-Hz MDGA-14/SN1 MDGA-16/SN1 220090400020 220090400040 380-415, 3, 50 380-415, 3, 50 Capacity kW 14 16 Input W 4453 4904 Capacity kW 16 17 Input W 4828 4943 Max. input consumption W 6533 6573 Max. input current A 11.7 11.5 Starting current A 60 64 Model ZPD72KCE-TFD-532…
-
Type
R410A R410A Charged volume kg 4.1 4.4 Liquid side mm Φ9.5 Φ9.5 Gas side mm Φ19 Φ19 Water inlet/outlet mm DN32 DN32 Refrigerant Refrigerant pipe diameter Pipe diameter Control Ambient temperature Wired controller KJR-08B/BE ℃ Cooling: 10℃~43℃ Cooling: 10℃~43℃ Heating: -15℃~24℃ Heating: -15℃~24℃ Note…
-
7. Dimensions
-
8. Service Space
12 MCAC-UTSM-2013-01
-
9. Piping Diagram
Remark: No Name No Name No Name 1 Compressor 6 Capillary 11 Liquid receiver 2 High pressure switch 7 Liquid receiver 12 Low pressure switch 3 4 -way valve 8 Plate heat exchanger 13 Crank heater 4 Condenser 9 PWM valve 5 Filter 10 Water temperature sensor 13
-
10. Wiring Diagrams
10.1 MDGA-10/SN1 14 MCAC-UTSM-2013-01
-
10.2 MDGA-12/SN1
-
11. Electric Characteristics
-
12. Capacity Tables
-
Model
-
MDGA-14/SN1
-
Model
-
MDGA-12/SN1
-
Model
-
таблицы и схемы — в просмотре
-
13. Operation Limits
Outdoor ambient temperature: 10℃~43℃ Cooling operation Outlet water temperature: 5℃-17℃ Outdoor ambient temperature: -15℃~24℃ Heating operation Outlet water temperature: 45℃-50℃ Cooling 13.1 Heating Ethylene glycol solution Water and ethylene glycol solutions used as a thermal vector in the place of…
-
Fouling factor
Evaporator 2 (m °C/W) f1 fx1 - - - -4 0.96 0.99 0.99 -4 0.93 0.98 0.98 4.4×10 0.86×10 1.72×10 f1 capacity correction factor fk1 compressor power input correction factor fx1 total power input correction factor 13.3 fk1 -5 Volume of water installation Model MDGA-10/SN1 MDGA-12/SN1 MDGA-14/SN1…
-
14. Hydraulic Performance
14.1 Pump head curve(*) Note: (*) To obtain the useful head of the installation, subtract the pressure drop of the plate heat exchanger. 14.2 Heat exchanger pressure drop (water side) Model Water flow 10kW Pressure drop Model Water flow 12 kW 14 kW 16 kW Pressure drop m /h 3 0.8 1.0 1.2 1.4 1.6 1.8…
-
15. Sound Levels
-
17. Troubleshooting
17.1 Troubles cause and solution Troubles Causes Solution 1. Voltage is out of operation range. 2. Water flow in the water pump box is abnormal 1. Open-circuit of compressor connector 2. Open-circuit of compressor wiring Check wiring and circuit Check whether the water system is blocked with…
-
E0: Water flow test malfunction
LED indicates E0 Yes Check the water pump, and repair or replace it if necessary. Judge 1: The water pump gets faulty. No Yes Check the water flow switch, and repair or replace it if necessary. Judge 2: Water flow switch gets faulty. No Yes Judge 3: Check whether the water system is blocked. Check…
-
E1: Phase sequence malfunction
LED indicates E1 Yes Judge 1: Check whether the phase order of 3-phase power supply is incorrect. Exchange the power wire of any two phases. No Yes Judge 2: Check whether the 3-phase power supply lacks phase. Check the power supply and power wire. E2: In-outdoor unit communication checking channel…
-
E3: Inlet water temperature sensor checking channel is abnormal
LED indicates E3 Judge 1: Check whether the wiring of inlet water temperature sensor is broken. Yes Connect the wiring well. No Judge 2: Check whether the inlet water temperature sensor is broken: see whether the resistance of inlet water temperature sensor is wrong refer to the Annex 1. Yes Replace…
-
E5: Outlet water temperature sensor checking channel is abnormal
LED indicates E5 Judge 1: Check whether the wiring of outlet water temperature sensor is broken. Yes Connect the wiring well. No Yes Judge 2: Check whether the outlet water temperature sensor is broken: see whether the resistance of outlet water temperature sensor is wrong refer to the Annex 1.…
-
E7: Plate heat exchanger temperature sensor 1 checking channel is abnormal
LED indicates E7 Judge 1: Check whether the wiring of plate heat exchanger temperature sensor 1 is broken. Yes Connect the wiring well. No Judge 2: Check whether the plate heat exchanger temperature sensor 1 is broken: see whether the resistance of plate heat exchanger temperature sensor is wrong…
-
E9: Digital scroll compressor discharge temperature sensor is abnormal (thermostat display E4)
LED indicates E9 Yes Judge 1: Check whether air outlet is blocked by sundries. Clear the sundries to ensure smooth discharge. No Yes Judge 2: Check whether the condenser coil fin gets dirty. Clean the condenser. No Yes Judge 3: Check whether the ambient temperature is too high. Add sunshade…
-
P0: Current protection
LED indicates P0 Yes Judge 1: Check whether the compressor motor gets faulty. Check the compressor, and repair or replace it if necessary. No Yes Reduce the refrigerant. Judge 2: Check whether the refrigerant is charged too much (the high pressure> 3.8MPa). No Yes Judge 3: Check whether air outlet…
-
P1: High pressure protection
LED indicates P1 High pressure protection. Judge 1: Whether the wiring between the high pressure switch and main control board is connected well and correctly. No Connect it well. Yes Judge 2: Whether the high pressure switch is broken. Validate: Short connect the high pressure switch socket, check…
-
P2: Low pressure protection
LED indicates P2 Low pressure protection. Judge 1: The wiring between the low pressure switch and main control board is connected well or correctly. No Connect it well. Yes Judge 2: Whether the low pressure switch is broken. Validate: Short connect the low pressure switch socket, check whether the…
-
P3: Discharge temperature protection
Refer to the E9 to solve the problem P4: Inlet–outlet water temperature difference protection LED indicates P4 Yes Judge 1: Check whether inlet–outlet water temperature-sensor kits gets faulty. Replace the temperature-sensor kits. No Yes Judge 2: Check whether the sequence of the four…
-
P6: Plate heat exchanger low temperature protection
LED indicates P6 Yes Judge 1: Check whether the temperature-sensor kit at the plate heat exchanger side gets faulty. Replace the temperature-sensor kit. No Yes Clean the water side heat exchanger or pipe. Judge 2: The heat exchange of water side is insufficient. No Yes Refill water periodically.…
-
Pb: System anti-frozen protection
LED indicates Pb Judge 1: Check whether the circulation water is insufficient: (Q<0.6×Qrated). Yes Check the water system and make adjustment. No Yes Judge 2: Check whether the plate heat exchanger temperature sensor is abnormal. Replace the temperature sensor. No Judge 4: Check whether the ambient…
-
18. Installation
18.1 Installation of general information General warning 1. These units have been designed to chill and heat water and must be used in applications compatible with their performance characteristics; these appliances are designed for residential or similar applications. 2. Incorrect installation…
-
R410A Mini Split Chiller 50Hz Installation 18.2.1. Choice of installation site Before installing the unit, agree with the customer the site where it will be installed, taking the following points into consideration: - check that the fixing points are adequate to support the weight of the unit; - pay…
-
18.3.2 Refrigerant piping
Note: 1. Refrigerant piping connection is on the right side of outdoor unit. 2. The piping connects to refrigerant piping connection. 3. Install the refrigerant piping towards left, right or back. 4. Refer to system identifiers in valve installation board for corresponding connections of indoor…
-
Caution
Too large torque will harm the bell-mouth and too small will cause leakage. Please determine the torque according to the table below: Pipe gauge Tightening torque Φ6.4 15~16N.m (153~163kgf.cm) 25~26N.m (255~265kgf.cm) 35~36N.m (357~367kgf.cm) 45~47N.m (459~480kgf.cm) 65~67N.m (663~684kgf.cm) Φ9.5…
-
5. After vacuuming, close the Lo-lever of manifold valve and turn off vacuum pump. When doing vacuuming for more than 15 minutes, please confirm that the indicator of multi-meter points to-1.0X105Pa(-76cmHg) 6. Totally open the Hi-stop valve and Lo-stop valve. 7. Remove the charge hose from the…
-
4) The flexible pipe should be used on water pump side. (The bending angle should not exceed 90°. The bending part is preferably in the middle of the pipe, the bigger the bending radius, the better it is. Do not bend the pipe more than 3 times.) 5) Bending the connecting pipe of thin wall. ● Cut out…
-
Total iron
less than 0.3 ppm Alkalinity M less than 50 ppm Total hardness less than 50 ppm Sulphur ions none Ammonia ions none Silicon ions less than 30ppm Filling the installation - Before filling, check that the installation drain cock is closed. - Open all installation and terminal air vents. - Open the…
-
18.6 Electrical connection
18.6.1 Notice The split mini chillers leave the factory already wired, and require the installation of an omnipolar thermal overload switch, a lockable mains disconnecting switch for the connection to the mains power supply , and the connection of the flow switch to the corresponding terminals. All…
-
Electrical panel layout
No Name No Name No Name 1 Power control board 4 Terminal board 7 Transformer 2 Fan capacitor 5 Emergency switch 3 Compressor capacitor 6 Compressor contactor 18.6.3 Outdoor unit wiring specifications 10/12kW Overall power core 1 Specifications (for reference) 2 RVV-300/500 3×6.0mm 14/16kW Overall…
-
19. Maintenance
19.1 Shut down for long periods If it is previewed not to use the machine for long periods, after deactivating the chiller: ● Make sure the remote switch SA1 is in the "OFF" position, or alternatively disconnect the unit from the power supply. ● Make sure the remote keyboard (if present) is set to…
-
● Empty and dry the entire refrigerant circuit using a vacuum pump connected to the low and high pressure tap until the vacuometer reads about 10Pa. Wait a couple of minutes and check that this value does not rise to more than 200Pa. ● Connect the refrigerant gas cylinder or a filling cylinder to…
-
20. Controller
Standard wired controller: KJR-08B/BE 20.1 16 14 Operating instructions of buttons 1. ON/OFF button: In the power off status, press this key and the startup indicator comes on, and the wired controller enters the startup status and keeps the current set information such as temperature value, timing.…
-
5. Heat button
This button has no effect to KJR-08B/BE. 6 & 7 TIME ON/OFF button Every time when you press [TIME ON] button, the HOUR and MINUTE of timing startup blink at a frequency of 2Hz. They stop blinking when you adjust the hour and minute; and continue blinking 2 seconds after you stop adjustment. Press…
-
R410A Mini Split Chiller 50Hz Installation procedure: The wiring procedure and principles are shown in the figure: Black Yellow Gray Outdoor electric control box Please use 3-cord shielding wires for connection. The wire length depends on the specific situation in the installation. Communicate with…
-
The tables as below contain the operation procedure of wired controller
Operation procedure of wired controller: Step Content Press AUTO/MANUAL mode at shutdown status, you could select MANUAL or AUTO turn-on mode as you want. 1 The function is invalid at startup status. In Manual mode, press [PAGEUP/TEMP+] or [PAGEDOWN/TEMP-] button for select your require online unit…
-
R410A Mini Split Chiller 50Hz ON/OFF operating flow chart. Turn on the unit Power up to module unit and initially deliver power to wire control. Press “mode settings” key to set the intended mode. Press the key again until all modes are showed (i.e. Cooling, Heating and Pump modes.) Press…
-
Appendix
Temperature-Resistance characteristic sheet. -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 Unit: ℃--K 115.266 20 108.146 21 101.517 22 96.3423 23 89.5865 24 84.219 25 79.311 26 74.536 27 70.1698 28 66.0898 29 62.2756 30 58.7079 31 56.3694 32 52.2438 33 49.3161 34 46.5725…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.