Инструкция на Наружные блоки мини VRF-системы V4+ 22~26kw (сервис мануалы)
Наружные блоки мини VRF-системы V4+ (R410a). Часть 4. Устранение неисправностей. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
1. PCB ports instructions
PCB ports instruction No. 1 CN41 2 CN21 3 CN22 4 CN20 5 CN19 6 CN42 7 CN44 8 CN45 9 CN46 10 CN47 11 CN48 12 CN201 13 14 CN205 15 CN250 16 CN4 62 Content Power input port of the main panel valve Load output port, crankcase heater HAET 1&HEAT 2 Load Load output output port port Load output port Load…
-
17 CN7
18 CN24 19 CN9 20 CN19 21 CN13 22 CN14 23 CN20 24 CN27 R410a Full DC Inverter Individual VRF Indoor and outdoor units communication port, indoor unit network port, outdoor unit network port, and network charging connection port Signal input port for system high pressure and low pressure detection…
-
18 7. -8. Working indoor unit quantity Program version 19 9. Last fault or protection code 20 0. MCAC-VTSM-2013-04 Actual value -00 is displayed if no fault occurs or protection has not been activated. Check completed. Remark: 1) Normal display: In standby mode, the number of indoor units that…
-
S5 Function definition
S5 On S5 On Heatin g priorit y mod e (sette d by factor y default ) S5 On Heatin g onl y mod e S5 Coolin g priorit y mod e On Coolin g onl y mod e S5 On Inicial-star t priorit y mod e S6 function definition: S6 On 1 2 S6 On 1 2 S6 On 1 2 Automatic addressing Non-automatic addressing(setted by…
-
LED4: Malfunction indicator lamp of inverter module. The lamp will flash if the inverter module is faulty and the error code will display on digital tube. LED5: Running indicator lamp of inverter module. The lamp will be on if the compressor is running. 2.5 Description of Main Control Board of…
-
Shape 2
Dial codes definition 0/1 definition Means 0 Means 1 SW1 definition Troubleshooting 1 means factory test mode 0 means default auto addressing mode 1 means DC fan is chosen 0 means AC fan is chosen 00 means DC fan static pressure is 0 (reserved) 01 means DC fan static pressure is 1 (reserved) 10…
-
SW2 definition
00 means shutting down the unit to stop cold air at 15℃ 01 means shutting down the unit to stop cold air at 20℃ 10 means shutting down the unit to stop cold air at 24℃ 11 means shutting down the unit to stop cold air at 26℃ 00 means the time of stopping fan (when no capacity need) is 4 minutes 01…
-
E4
Run LED flashes Temperature sensor T2B error E7 Defrost LED flash slowly EEPROM error Ed Alarm LED flashes slowly Outdoor unit error EE Alarm LED flash Water level alarm Note: Some unit that has digital tube will show the error code when error occurs, others show lamp indication. Explanation of main…
-
3. Error code table (ODU)
Error Content Note H0 IR341 and 78F0034 communication error H1 0537 and 78F0034 communication error H4 P6 protections happen 3 times in 30 minutes. Recover until electricity reset. H5 P2 protections happen 3 times in 30 minutes. Recover until electricity reset. code H7 will display after the unit is…
-
4. Troubleshooting
4.1 H0/H1 H0: IR341 and 78F0034 communication error H1: 0537 and 78F0034 communication error IR341 chip: IR 341chip is used for inverter compressor drive. 0537 chip: 0537chip is used for control the communication between indoor unit and outdoor unit, and the communication between outdoors 78F0034…
-
4.2 H4: when P6 protection happens 3 times in 30 minutes,H4 displays
H4 displays P6 protection happens 3 times in 30 minutes. Recover until power on again. P6 displays IPM module protection (IPM refers to inverter module) Adjust to the right range, Check whether the P-N voltage range of and then check whether Check whether the input power supply NO IPM mode is normal…
-
4.3 H5: when P2 low voltage protection happen 3 times in 30 minutes, H5 displays
LED display H5 P2 low voltage protection happen 3 times in Recover until power on again. 30 minutes. NO Judge1: wiring between low voltage switch and main PCB is connected Connect well again. right or not. YES Judge 2: check whether the low voltage is damaged or not? YES Check: low voltage switch…
-
4.4 H7: Quantity of indoor units decrease
LED display H7 Check the quantities of indoor unit Check the communication wiring between outdoor NO unit and indoor unit is connected well. Connect the communication wire again. YES Check the address of indoor unit is YES Reset the address again repeated or not. NO Check whether there is…
-
4.5 HF: not matched with M_Home series
LED display HF The communication between indoor unit chip and outdoor unit chip is not matched. Check whether the model of indoor and outdoor unit is NO matched or not. Replace indoor unit or chip of indoor unit YES Whether the chip of indoor unit is right or not. NO Replace indoor unit or chip of…
-
4.6 E2: Communication malfunction between indoor unit chip and outdoor unit chip
LED displays E2 Communication malfunction between indoor unit chip and outdoor unit chip. Judge 1: Check whether the indoor unit is power on NO Plug the indoor unit in. YES Judge 2: check whether the three-cored shielded wire is used as the communication wire and earthed properly. Replace shielded…
-
LED displays E4 YES Judge 1: T3&T4 sensor malfunction Replace T3/T4 sensor NO YES Judge: whether the body is broken. Connect the wire again. NO Judge whether temperature sensor pin connects properly. YES Connect again. NO Replace main PCB Troubleshooting 77
-
4.8 E5: Voltage protection malfunction
LED displays E5 Voltage protection malfunction Judge whether the input voltage is 180-260V NO Check the power supply. YES Replace the filter board to check whether the unit operates normally. YES OK NO Replace the main PCB 78 Troubleshooting
-
4.9 E6: Outdoor unit DC fan cannot work
LED displays E6 Outdoor unit DC fan cannot work. YES Check whether there is strong air blows the fan wheel when the fan running. It belongs to normal protection. NO NO Refers to the wiring nameplate to check whether the DC fan wiring correct or not. Connect again. YES Check whether PN voltage of the…
-
4.10 E7: Discharged temperature sensor malfunction
LED displays E7 YES Judge whether the discharged temperature sensor is installed inside the branch pipe. Install again. YES Judge whether the plug of the discharged temperature sensor is connected properly. Judge: whether the wiring body is broken. Connect again. YES Connect again. NO Replace the…
-
4.11 EA: T3 pipe temperature exceeds 27 degrees for more than 5 minutes when heating mode
LED displays EA System faulty that T3 pipe temperature exceeds 27 degrees for more than 5 minutes when heating mode. Whether the outdoor ambient temperature is higher than the unit’s operating condition when heating mode. YES Belongs to system normal protection NO Check whether the refrigerant…
-
4.13 P1 malfunction: High pressure protection or discharged temperature switch protection
LED displays P1(high pressure protection) High pressure protection NO Judge 1: whether the wiring is correct. Connect again. YES Judge 2: whether the wire body is broken. NO Judge: short-circuit high pressure switch. Check the system can operate normally. Replace the high pressure switch. YES Check…
-
LED displays P1(discharged temperature switch protection)
P1(discharged temperature switch protection) Discharged temperature switch protection YES Check whether the discharged temperature is higher than 115 degrees. NO Check whether the discharged temperature sensor of the compressor connect with PCB correctly according to the wiring diagram. NO Connect…
-
4.14 P2: Low pressure protection
LED displays P2 Low pressure protection NO Judge 1: whether wiring connection between low pressure switch and PCB is connected well or properly. Connect well again. YES Judge 2: whether the low pressure switch is damaged. YES Confirm: short-circuit low pressure switch and check whether the system…
-
4.15 P3: Input current protection
It will protect when input current is more than 23A. It will recover when input current is less than 23A. It will recover automatically. LED displays P3 Input current protection Judge 1: check whether the input current of the power wire is more than 23A. YES Check cooling system is normal or not.…
-
4.16 P4:When the discharged temperature of the compressor is higher than 115°C, the unit will stop
running. When the discharged temperature of the compressor is lower than 80°C , the unit resumes normal operation automatically. LED displays P4 Discharged temperature of the compressor Check whether the discharged temperature of the compressor is higher than 115°C. YES NO Check whether the…
-
4.17 P5: When condenser temperature is higher than 62 degrees for 3 seconds, the unit will stop
operating. Then when pipe temperature outside is lower than 52 degrees, the unit will resume operate. LED displays P5 Condenser T3 high temperature protection YES Check whether condenser temperature is higher than 62 degrees for 3 seconds. NO NO Check whether the resistance of condenser Replace the…
-
4.18 P6: Module protection
LED displays P6 IPM module protection Check whether P-N voltage on the IPM module NO Check if wiring connection between main PCB and IPM module is fasten or not. NO Check whether wiring connection of the compressor is connected right and firmly. Connect firmly again and check whether it is connected…
-
4.19 P8: Typhoon protection
LED displays P8 Typhoon protection When air conditioner is standby or in malfunction stopping status, YES Belongs to normal protection check if there is strong air blows the fan phenomenon. NO NO Check whether the fan motor is normal. Replace fan motor. YES Replace outdoor PCB or transfer board of…
-
4.20 PE malfunction
When the middle average temperature of the evaporator is higher than 63 degrees for 50 seconds, the unit will stop operating. When pipe temperature is lower than 50 degrees, the unit will resume running. LED displays PE Evaporator T2 high temperature protection YES Check whether average temperature…