Инструкция на Тепловые насосы Lennox серии HP14 - 24...
Тепловые насосы Lennox серии HP 22. Инструкция по монтажу, эксплуатации и техническому обслуживанию.
Смотрите также: Основной документ →
Загружаем документ…
Текст инструкции
-
its
-
TABLE OF CONTENTS
Unit Dimensions нии Start~Up and Performance Check List... Page 1 . Page 1 Installation.. Page 2 Electrical... serene Page 3 Plumbing перен незнн. Page 3 Refrigeration. Portree Page 4 Орегабоп нения не Page 7 Maintenance. (erates - Раде 7 UNIT DIMENSIONS INLET AIR MODEL NO. A в с о Е НР22-211 28 т.…
-
I-SHIPPING AND PACKING LIST
Package 1 of 1 contalns: 1—Assembled heat pump unit Check unit for shipping damage. Consult last carrier immediately if damage is found. These instructions are intended as a general guide and do not supersede local codes in any way. Authorities having jurisdiction should be consulted before…
-
FIELD WIRING DIAGRAM HP22 WITH CB19
THERMOSTAT. A REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT АМРАСТТУ AND MAXIMUM FUSE SIZE 208-230/60/1 121 оФоооо6 оо -«— DENOTES OPTIONAL COMPONENT Layne (\ А Л THERMOSTAT HEAT ANTICIPATION SETTING м 4 АМР ELECTRIC HEAT => WHEN TWO-STAGE THERMOSTAT IS USED, CONNECT SECOND-STAGE HEAT BULB ТО TER…
-
V—REFRIGERATION
A—Processing Procedure The unit is factory—charged with the amount of R-22 refrigerant indicated on the unit rating plate. This charge is based оп a matching indoor coil and outdoor coil with a 25 foot (7620mm) line set. For varying lengths of line set, refer to table 2 for refrigerant charge…
-
HP22 COOLING CYCLE
(Showing Gauge Manifold Connections) wave - SUCTION PRESSURE < |: |3 REVERSING 8 § VALVE Е = Е - FILTER DRIER Lama WITH INTERNAL STRAINER $ 4 CHECK VALVE = Е 52 82 DISCHARGE РЕ MUFFLER VAPOR LINE Е => VALVE + secoeemnermemmmtnn rn ld = —) COMPRESS: “er INDOOR UNIT ‘Ne, 4 2 VALVE 8 <= = 5 CHECK =~ §…
-
C-—Charging 6— Ifambient temperature is less than 60°F (15°C), air
It is desirable to charge the system in the cooling cycle if weather conditions permit. However, if the unit must be charged in the heating season, one of the following procedures must be followed to ensure proper system charge. If the system is completely void of refrigerant, the recommended and…
-
Vi-OPERATION
A-Discharge (Top Cap) Thermostat The scroll compressor is equipped with a discharge thermostat which prevents the occurrence of dangerously high discharge temperatures, This thermostat cuts in at 130°F and cuts out at 280°F. A CAUTION “Danger of Equipment Damage. - Do not bypass the discharge…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.