INSTALLATION
INSTRUCTIONS LHA090 (7 1/2 TON) LHA120 (10 TON) PRODUCT LITERATURE Litho U.S.A. E1998 HEAT PUMP UNITS 503,924M 8/98 Supersedes 503,577M TABLE OF CONTENTS DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PARTS ARRANGEMENT . . . . . . . . . . . . . . . . . . . . . . .…
-
LHA090 & 120 DIMENSIONS
OPTIONAL OUTDOOR AIR HOOD (Factory or Field Installed) OUTDOOR COIL INTAKE AIR OUTDOOR COIL FAN (2) 4 (102) AA 4 (102) 28 (711) 5 1/2 (140) OUTDOOR COIL INTAKE AIR INDOOR COIL 28 (711) 20 (508) EE BOTTOM POWER ENTRY 5 x 8 inches (127 x 203 mm) CENTER OF GRAVITY FF DD BLOWER MOTOR OUTDOOR COILS…
-
LHA090 & 120 PARTS ARRANGEMENT
FILTERS (FOUR − 18 X 24 X 2") INDOOR COIL OUTDOOR FANS ECONOMIZER (OPTIONAL) BLOWER BLOWER MOTOR OUTDOOR COILS CONDENSATE DRAIN COMPRESSORS SHIPPING AND PACKING LIST Package 1 of 1 contains: 1− Assembled unit Check unit for shipping damage. Receiving party should contact last carrier immediately if…
-
The LHA unit is Canadian Gas Association (C.G.A.)
certified as a heat pump with cooling and with or without auxiliary electric heat for non−residential use only at the clearances to combustible materials as listed on the unit nameplate and in figure 1. 3− Duct must be attached to the roof mounting frame and not to the LHA unit; supply and return…
-
DUCT CONNECTION
CONDENSATE DRAINS All exterior ducts, joints, and openings in roof or building walls must be insulated and weatherproofed with flashing and sealing compounds in accordance with applicable codes. Any duct passing through an unconditioned space must be insulated. Make drain connection to the 1" N.P.T.…
-
FACTORY−INSTALLED OPTIONS
A−Economizer The A56 EM1 economizer board controls economizer operation and provides potentiometers to control minimum damper position and enthalpy control adjustments. The A56 EM1 economizer board is positioned on the A55 M1 main control board in the unit control box. See the Integrated Modular…
-
ELECTRICAL CONNECTIONS
POWER SUPPLY Do not apply power or close disconnect switch until installation is complete. Refer to start−up directions. Refer closely to unit wiring diagram. Figure 7 shows a typical LHA090 and 120 wiring diagram. Refer to unit nameplate for minimum circuit ampacity and maximum fuse size. 1−…
-
TYPICAL LHA UNIT WIRING SCHEMATIC
FIGURE 7 Page 7
-
COOLING START−UP
IMPORTANT−Crankcase heaters must be energized for 24 hours before attempting to start compressor. Set thermostat so there is no demand to prevent compressors from cycling. Apply power to unit. NOTE − These units must not be used as a construction heater" at any time during any phase of construction.…
-
TABLE 3
TABLE 1 LHA090 NORMAL OPERATING PRESSURES Outdoor Coil Entering Air Temp. CIRCUIT 1 Discharge Suction + 10 +5 psig psig CIRCUIT 2 Discharge Suction + 10 +5 psig psig OUTDOOR FAN CYCLES AT 65_F 65_F 75_F 85_F 95_F 105_F 115_F TABLE 2 LHA120 NORMAL OPERATING PRESSURES Outdoor Coil Entering Air Temp.…
-
Defrost switches close to initiate defrost when outdoor coil suction temperature falls to 35°F (1.7°C). C−Determining Unit CFM 8− Defrost Termination Switches (S46, S104) Defrost pressure switches open to terminate defrost when suction (discharge pressure during cooling and defrost) pressure reaches…
-
BLOWER ASSEMBLY
TO INCREASE BELT TENSION 1−Loosen four bolts securing motor base to mounting frame. 2−Turn adjusting bolt to the right, or clockwise, to move the motor outward and tighten the belt. 3−Tighten two bolts on motor pulley side. ALIGN TOP EDGES PAR ALLEL BEFORE TIGHT ENING MOTOR IN PLACE IMPORTANT −…
-
TABLE 4
LHA090 AND 120 BASE UNIT BLOWER PERFORMANCE BLOWER DATA BLOWER TABLE INCLUDES RESISTANCE FOR LCA102 BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 − Wet indoor coil air resistance of selected unit. 2 − Any factory installed options air resistance (heat section…
-
F−Field−Furnished Blower Drives
-
SERVICE
C−Indoor Coil The unit should be inspected once a year by a qualified service technician. Inspect and clean coil at beginning of each cooling and heating season. Clean using mild detergent or commercial coil cleanser. Flush coil and condensate drain with water taking care not to get insulation…