KLASIK USER MANUAL Da)
-
1. INTRODUCTION
An air handling unit is a device designed to ensure good ventilation in the premises. An air handling unit removes indoor air containing carbon dioxide, various allergens or dust and replaces it with filtered fresh outdoor air. KLASIK air handling units are designed for ventilation of large…
-
2.1. Ventilation modes
The unit operates in one of the available ventilation modes. Air volume for each fan and desired air temperature can be set individually for each mode. The unit comes with the following preset ventilation modes that may be used immediately after installation or, if required, after altering…
-
2.4. Air Quality Control (AQC)
Air quality control function is intended for adjusting ventilation intensity according to the indoor air quality. When indoor air quality drops below the user-defined limit, ventilation intensity is gradually increased until the air quality improves. This function requires an air quality sensor…
-
2.8. Summer night cooling function (SNC)
Summer night cooling function uses the night’s cool air to ventilate the premises during summer. This function removes excess heat accumulated during the day and fills the building with cooler outdoor air. Function runs at night (from 00:00 a.m. to 06:00 a.m.) when the outdoor air is cooler than the…
-
Control by external signal Recirculation damper position is changed by connecting an external device (switch, motion sensor, thermostat) to the C5 controller board, which opens or closes contacts (see “Installation Manual”). The user specifies two recirculation damper positions (as a percentage)…
-
Duration of full recuperation, min
DURATION OF FULL RECUPERATION -15 -13 -11 -9 -7 -5 -3 0 Outdoor temperature, °C If outdoor temperature drops bellow -15 °C, full recuperation is not done and segments closing/opening intervals are the same. In frost prevention mode, additionally pressure drop over the exchanger and heat-exchanger…
-
3. PROTECTIVE FUNCTIONS
The air handling unit is equipped with several protective functions that affect the operation of the unit. The operator is not allowed to change these settings values. These functions protect the unit and its components against damage as well as provide protection for the building and people when…
-
4. CONTROL AND SETTINGS. CONTROL PANEL C5.11
Air handling unit may be conveniently controlled via the following ways: Control panel. Mobile app. Web browser. C5.1 panel has a colour touchscreen. If the unit is connected to the mains, the control panel will display the home screen or screen saver that you can switch off with a single tap. • • •…
-
Explanation of the displayed symbols
Supply air temperature Extract air temperature Supply air volume Extract air volume Supply air humidity Extract air humidity Extract (room) air quality Fan operation Air flow increasing by activated function (see chapter Functions) Air flow decreasing by activated function (see chapter Functions)…
-
4.1. Parameter overview
The following parameters are displayed in the main window and parameter overview windows: air flow, temperatures, air quality sensor data and energy recovery. Use arrows on the sides of the main screen to browse across parameter windows. 16:30 16:30 16:30 16:30 21,9 °C 21,3 °C 12500 m³/h 13100 m³/h…
-
4.2.1. Calibration of the CF heat exchanger during commissioning1
The first time you turn on your CF air handling unit, you will have to perform calibration of a heat exchanger (if not performed during installation). This calibration is necessary for proper operation of the antifreeze prevention function. 16:30 °C Start 21,9 CF exchanger calibration? 21,3 °C…
-
4.4. Scheduling window and ventilation schedule settings
In menu item “Scheduling” you can create your own ventilation schedules so that the ventilation intensity or temperature settings change automatically. Scheduling Operation program Holidays Recirculation schedule • Operation program You can set up to twenty operating programs. You can assign a…
-
Holidays Here you can select a holiday program, set dates for the unit to run in a selected mode or to be stopped (e.g., stopping the air handling unit in the office during Christmas holidays). Holidays Holidays 2 Operation mode STANDBY Holidays 1 From 12/14 Till 12/26 Delete holiday Add new holiday…
-
Operation counters These meters show operating time of individual devices, amount of energy returned and consumed. To reset a meter, press an arrow next to a desired parameter. Operation counters Operation counters Air heater 121 kWh Air heater 121 kWh Supply fan 873 h SupplyReset fan air heater 873…
-
When replacing filters with filters from different manufacturers or different filtration class, calibration of clean filters is recommended. During calibration, the unit will operate at a maximum speed for a few minutes, measure the pressure difference upstream and downstream the filter and…
-
Air quality control (AQC) Selecting an air quality limit up to which the air handling unit will run during the activated mode and above which the ventilation intensity will be automatically increased. Air quality limit is set for two different ventilation modes during which the function will be used…
-
Minimum temperature control (MTC) Setting a minimum desired supply air temperature. Minimum temperature Enable Setpoint 15 °C Reset settings • Override function (OVR) Selecting conditions for activating the function (all the time, only when the unit is running, only when the unit is stopped) and…
-
– Control by external signal
Recirculation damper position is set for open (default recirculation) and closed (activated recirculation) control signal contacts. Recirculation control Recirculation control Enable Enable Setpoint 1 800 ppm Winter stop -20 °C Default recirculation 0% Min. fresh air 1 40 % Winter start -5 °C…
-
4.7.1. Air handling unit
• Temperature control The user can select a desired temperature control method (see Chapter “Temperature Control”). The user-set temperature will be maintained during ventilation modes according to the selected control method. Temperature control Supply Extract Room Balance • Flow control The user…
-
Connectivity Parameters for connecting the air handling unit to a computer network, the Internet or a building management system. Connectivity Connectivity Controller ID Default BaCnet port 47808 IP 192.168.0.50 BaCnet ID 0000166 IP mask 255.255.0.0 Modbus ID 1 RS-485 19200 1/2 2/2 • Panel sensor…
-
Screen saver Screen saver is activated after 1 minute of inactivity on the control panel. In this menu the user can enable/disable a screen saver and select parameters to be displayed on screen. Screen saver Row 1 Brightness Enable 25% Time Brightness 55% 50% Panel temperature Row 1 Time 75% Panel…
-
5. CONTROL AND SETTINGS. COMPUTER
The unit may be controlled via computer using a web browser. For information on how to connect the unit to an internal network or directly to a computer, see the “Installation Manual”. Enter the device IP address in your web browser (IP address is displayed on the control panel) (see Settings → Air…
-
5.1.1. Operation modes
In this menu item the user can select one of the five ventilation modes for the unit (see Chapter 2.1 “Ventilation Modes”). Selecting the “Program” mode: OPERATION MODES Mode selection Comfort1 Comfort2 Economy1 Economy2 Special Program You can select air volume (for supplied and extracted air…
-
5.2. Functions
Here you can enable/disable ventilation functions and change their settings. 5.2.1. Air quality control (AQC) Selecting air quality limit up to which the air handling unit will operate in a selected mode and above which the ventilation intensity will be automatically increased. Air quality limit is…
-
5.2.5. Override function (OVR)
Selecting conditions for activating the function (all the time, only when the unit is running, only when the unit is stopped) and specifying ventilation mode for the unit to run when the function starts. If the “Standby” ventilation mode is selected, the unit will be stopped. OVERRIDE FUNCTION (OVR)…
-
Control by external signal Recirculation damper position is set for open (main recirculation) and closed (activated recirculation) control signal contacts. RECIRCULATION CONTROL (REC) Enable Default recirculation 0 % Activated recirculation 60 % 5.2.8. Humidity control (HUM)1 Setting a desired…
-
5.3. Alarms/Status
This menu item shows information about the air handling unit and its assemblies. ACTUAL ALARMS ALARM HISTORY OPERATION COUNTERS EFFICIENCY STATUS VAV STATUS CONTROLLER STATUS 5.3.1. Actual alarms This menu item displays relevant messages with identification codes. “A” at the end of the code means…
-
In this menu you can also calibrate CF heat exchanger1, if not calibrated during the first start-up. If calibration was successful and the display shows “Calibrated”, there is no need to repeat it. During calibration, the unit will run for 10 minutes by changing fan speed and will be measuring…
-
5.4. Scheduling
In this menu the user can set weekly, holiday and recirculation schedules. OPERATION PROGRAM HOLIDAYS RECIRCULATION SCHEDULE Save 5.4.1. Operation program You can set up to twenty operating programs. You can assign a desired operating mode, day of the week and time interval for every program. When…
-
5.5.1. Date/time
In this menu item the used can set the time and date of the unit, used for various functions and operation by a weekly schedule. When the “Daylight Saving Time” function is enabled, the clock will automatically switch between summer time and winter time in spring and autumn. DATE/TIME Day - Month…
-
6. PERIODIC MAINTENANCE
The air handling unit must be serviced by a qualified technician or authorized service representative. • • • • • Before starting any tasks, make sure that the unit is unplugged from the mains. Use caution when performing works near internal or external heaters as their surfaces may be hot. Remove…
-
Frequency
Task Commissioning 3 months 6 months Cleaning of the heat exchanger Operation of an external unit 12 months X X X 6.9. Electrical heater Wiring X Operation of overheat protection X X X Cleaning of heating elements X 6.10. Gas heater Gas leakage X Gas leakage protection (if installed) X Burner…
-
Fig. 3. Filter clamping device
To insert/remove filters, push two handles at the top and bottom of the filter forward to release a filter clamping device. Filters are removed/inserted one by one (number of filters depends on the unit size). Once the filters are replaced/inserted, handles are retracted and the filter clamping…
-
6.6. Liquid coupled heat exchangers
Check for fluid leakage; check for proper operation of a check valve and a pump. Check threaded connections for tightness. Dirt from the heat exchanger surfaces shall be removed with compressed air. Be careful not to damage the heat exchanger lamellas while cleaning. 6.7. Water heater/cooler Check…
-
6.13. Additional works on units for hygienic and sanitary aplications
• • • • • • • Once installed, all unit sections must be cleaned with a cloth and/or a vacuum cleaner. Inner surfaces must be disinfected. Most of the unit components (heat exchangers, coils, drop eliminators, drip trays, fan units) are designed to allow easy removal for cleaning and disinfection of…
-
Code
40 Message Possible cause User‘s actions When the heater cools down, it will turn on again automatically. 1 a. Check air filters and air ducts. 1 b. Decrease the desired temperature. 1 c. Increase ventilation intensity. 2. Contact authorised service. 6B-11B Electric heater off Electrical heater…
-
Code
19A 20A 21A-23A Message Possible cause User‘s actions Low supply air flow 1. Obstacle in the duct system. 2. VAV air flow control selected but pressure sensors are not connected. 3. Faulty supply air fan. 1. Check that the air dampers, air intake and exhaust openings are not blocked, check whether…
-
APENDIX NO.1
WARRANTY INFORMATION Dear Customer, KOMFOVENT thanks you for your choice. We are pleased that you have chosen us and will strive to ensure you are satisfied with your purchased product. To avoid misunderstandings, we kindly ask you to read the installation and operating instructions of the product…
-
WARRANTY CONDITIONS
1. The warranty does not apply in the following cases: 1.1. If the product usage or operating conditions, as specified in the installation and operating instructions, are violated; 1.2. If the storage conditions of the unit are violated; 1.3. If there are signs indicating attempts of unqualified…
-
SERVICE AND SUPPORT
PARTNERS LITHUANIA UAB KOMFOVENT Phone: +370 5 200 8000 service@komfovent.com www.komfovent.com AT FINLAND Komfovent Oy Muuntotie 1 C1 FI-01 510 Vantaa, Finland Phone: +358 20 730 6190 toimisto@komfovent.com www.komfovent.com CZ GERMANY Komfovent GmbH Konrad-Zuse-Str. 2, 42551 Velbert, Deutschland…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.