KLASIK
INSTALLATION MANUAL komfovent
-
1. INTRODUCTION
This Installation Manual is intended for professionals, qualified to install KLASIK air handling units. Qualified professionals are people with sufficient professional experience and knowledge of ventilation systems and installation thereof, knowledge of electrical safety requirements and having…
-
1.2. Unit Types and Sizes
An air-handling unit is a device designed to ensure good ventilation in the premises. An air- handling unit removes indoor air containing carbon dioxide, various allergens or dust, while replacing it with filtered fresh air from outside. As the outside air is usually colder or warmer than the air…
-
KLASIK RA – air handling units with a liquid coupled heat exchanger that uses a liquid heat carrier for heat exchange. The heat exchanger consists of two coils (in the supply and extract air flows) connected via a circulation pipework unit (sold separately) and filled with a non-freezing heat…
-
1.3. Unit Components and Sections
KLASIK air handling units are assembled from separate sections. Depending on the order and unit size, sections may be pre-assembled in a factory or transported separately. Type of each section is marked with a label attached to the section door. The following are the main sections of the air…
-
Fig. 3. Filter section labels 1 – section with one row of filters, 2 – section with additional pre-filters 1.3.2. Fan section KLASIK R, CF and RA air handling units have two fan sections. In KLASIK S air handling units there is one fan section. Depending on the unit size, it may be several fans…
-
1.3.3. Counter-Flow Heat Exchanger (CF) Section
Due to heat exchange and condensation in counter-flow heat recovery units, heat exchangers may freeze at lower air temperatures. To prevent freezing or to defrost, a heat exchanger is equipped with an air bypass damper or a multi-stage damper system (according to the order). Formed condensate flows…
-
1.3.4. Rotary heat exchanger (R) Section
Rotor wheel of a rotary recuperator is belt driven by an electric gear motor. Brush seals are installed at the perimeter of a rotating wheel and between air flows to prevent different air flows from mixing. Heat exchanger section is also fitted with an automation box to which many of the main…
-
1.3.6. Recirculation Section
Recirculation section is intended for mixing extract and supply air for heating or cooling thereof by reducing energy consumption of heaters/coolers. 1. 1 2 2. 3. Fig. 8. Recirculation section 1 – air mixing damper, 2 – damper actuator, 3 – recirculation section label 1.3.7. Cooler and Heater…
-
Fig. 10. Heater section 1 – electric heater section and label, 2 – water heater section and label 1.3.8. Air Dampers Air dampers are mounted on the outside of the unit and are fastened with self-tapping screws. Air dampers are designed to isolate the unit and to protect against air flows and…
-
1.3.9. Silencers
Noise suppressor sections are intended for reducing noise generated by an air handling unit and air flows. Depending on the unit type and location of a silencer section, suppressor sections may be separate for each air flow (e.g., for supply air only) or double, intended for both air flows. Silencer…
-
1.4. Inspection Sides
Depending on the installation position and connection of air ducts, KLASIK air handling units are available in four inspection sides. Inspection side is determined by a supply air duct (SUP) position: L1 Air duct for supply air connected on the left bottom side of the unit. KLASIK R ETA EHA ODA SUP…
-
L2 Air duct for supply air connected on the left upper side of the unit
KLASIK R KLASIK CF ODA SUP ETA SUP EHA ETA EHA ODA R1 Air duct for supply air connected on the right bottom side of the unit KLASIK R KLASIK CF EHA ETA ODA ODA EHA SUP KLASIK RA ETA SUP KLASIK S EHA ODA SUP ODA ETA SUP R2 Air duct for supply air connected on the right upper side of the unit KLASIK R…
-
2. UNIT TRANSPORTATION AND STORAGE
On arrival of the ventilation unit, carefully inspect the packaging for any damage. If any mechanical or other defects are visible (e.g. wet cardboard packaging), immediately notify the carrier. If damage is significant, do not accept the goods. Notify the Seller or KOMFOVENT UAB representative1…
-
Depending on the dimensions of the unit and its individual sections, the installation frames and the available methods for their transport or lifting vary. Special retractable holders are foreseen for lifting bulky equipment assembled on solid installation frames. These holders are placed in special…
-
When a forklift is used for lifting or transporting the unit, its forks must be long enough to prevent the device from tipping over or to avoid mechanical damage to its bottom part. Ventilation units are heavy, therefore care must be taken during lifting, carrying or moving operations. Use personal…
-
Mounting of separate ventilation units in stacks is not allowed unless these devices are intended for such installation. Two-tier sections are placed on top of each other with a crane in the following procedure: 1 Lift corners of the section one after another using a long crowbar to place wooden…
-
3. MECHANICAL INSTALLATION
3.1. Requirements for Mounting Location and Installation Base KLASIK air handling units are designed for ventilation of medium or large commercial or industrial premises (e.g., stores, offices, hotels, etc.) where standard air temperature and humidity is maintained. These units are not intended for…
-
Minimum service area A defines an area which must be free of any stand-alone or immovable devices, equipment, partitions, structure or furniture. This area is sufficient for performing service and filter replacement works. For repair and replacement of components (e.g., removal of rotary heat…
-
Some panels of the unit do not have handles. They are fixed with special screws or knobs that need to be turned to remove the panel. Fig. 17. Panel fixing knob 1 - removable panel, 2 - fixing knob, 3 - unit frame 3.4. Connection of Sections unit. Connect connecting cables and wires of the sections…
-
Fig. 18. External connection and sealing of sections 1 – nut M10, 2 – washer, 3 – screw M10, 4 – adhesive gasket, 5 – gasket on a shelf between different air flows, 6 – external tightening elements, 7 – external tightening brackets Depending on the unit size and purpose of sections thereof, separate…
-
3.5. Installation of Heating/Cooling Devices
• • • • • Pipes of water heaters/coolers are connected to a water mixing unit (PPU) that supplies hot/cold water from the building’s water system. Pipes of liquid-coupled heat exchangers are connected to a PPU-LCHX mixing unit, that circulates thermal liquid and controls recuperation. Coils of…
-
When operating air handling unit in temperatures lower than 0°C, it is necessary to use water-glycol mixture as a heat carrier or to maintain a return water temperature of at least 25°C. Pipework package1 must include circulation pump, which circulates heating/cooling medium through the coil…
-
Height H of a siphon without a one-way valve is selected according to static pressure p inside the air handling unit: Ø40 mm H [mm] = 25 + p [mm H2O] = 25 + 0.1 x p [Pa] Fig. 24. Example of a siphon with a one-way valve • • • • Each drain outlet of the drip pans must be equipped with a separate…
-
3.7. Connection to Air Ducts
• • • • Ducts and air closing dampers connecting the unit to the exterior of the building must be insulated (insulation thickness 50–100 mm) to prevent condensation on cold surfaces. Air intake and exhaust ducts must be fitted with air shut-off dampers (electric with actuators) to protect the unit…
-
3.8. Outdoor Units
KLASIK air handling units for outdoor installation must be additionally protected against environmental effects by installing a protective roof and exhaust air hoods. Units shall be mounted on an installation frame which is attached to an installation base. Ventilation devices, when possible, should…
-
~ 350 mm ~ 350 mm 3 4 ~ 350 mm ~ 350 mm 5 Fig. 29. Installation of a separately ordered protective roof for KLASIK 1–7 size1 1 Part count and measurements may differ depending on the unit type or project requirements. UAB KOMFOVENT we reserve the right to make changes without prior notice…
-
~ 350 mm ~ 350 mm 3 4 ~ 350 mm ~ 350 mm 5 6 ~ 350 mm Fig. 30. Installation of a separately ordered protective roof for KLASIK 8–14 size1 1 30 Part count and measurements may differ depending on the unit type or project requirements. UAB KOMFOVENT we reserve the right to make changes without prior…
-
4. ELECTRICAL INSTALLATION
Only qualified professionals may perform electrical installation works in accordance with the manufacturer’s instructions and applicable legal acts and safety requirements. Before installation of any electrical components: • • • • Make sure the unit is unplugged from the mains. If the unit has been…
-
Units fitted with an additional electric heater section will be equipped with a separate main circuit breaker inside the section. OFF ON 2 1 OFF ON Fig. 32. Main circuit breaker inside an electric heater section 1 – lead-in cable grommet, 2 – main circuit breaker handle, 3 – main circuit breaker, 4…
-
4.2. Connection of Electrical Components
All internal and external devices are connected to the main board of the C5 control panel (RG1 in wiring diagrams) located in the automation box. Automation box is fitted at the front of the unit, top part of the heat exchanger section. Box is airtight and is opened by removing four screws and…
-
B9
Humidity sensor Cold water mixing valve / DX capacity control Hot water mixing valve Water pump for cooling 230V AC, 1A S2 Water pump for heating 230V AC, 1A S1 Water pump/ coil alarm Humidifier control TG1 INPUT Supply air temperature sensor 0..10V GND 0..10V ~24V N 0..10V ~24V N L N L N OUTPUTS…
-
Fig. 37. Return water temperature sensor with thread1
B1 (11–12) – terminal for a supply air temperature sensor (NTC 10kΩ) for controlling air temperature. Fig. 38. Supply air temperature sensor For the most accurate temperature measurement, sensor in a duct must be installed after all heating/cooling devices at least two duct diameters away from the…
-
Indication (40–42) – terminals are used when a normally open (NO) contact is necessary for operation status or fault indication. Terminals 40 and 42 are closed when AHU is in operation, thus it can be connected to any external device, which needs such a signal (for example humidifier). Terminals 41…
-
4.2.1. Connection terminals of KLASIK RA air handling units
KLASIK RA units can be designed as a single (mono-block) unit, or divided into two separate assemblies (for supply and exhaust airflows). If divided, each block will have a separate automation or connection box with terminals inside. The main C5 controller board can be found in the automation box…
-
4.3. Control Panel Installation
The control panel must be installed in a room with: Ambient temperature – 0..40°C; Relative humidity – 20..80 %; Guaranteed protection against accidental water drops. Control panel can be mounted in a concealed mounting box or directly on the wall (screws supplied with the panel). You can also use…
-
4.4. Connection of Cables and Wires Between Sections
X1 2 X1 Before fastening parts of the air handling unit, you shall connect connecting cables and wires of the sections. Cable connectors are labelled with connector numbers; only connect connectors with the same number. Number of cables and connectors in different sections may differ depending on…
-
4.5. Connecting the Unit to the Internal Computer Network or the Internet
Your AHU may be controlled not only with a control panel, but also with a computer or smart phone. For this reason the unit must be connected to the internal computer network or the Internet. In case of a computer, the unit is controlled via a web browser, and in case of a smart phone - via the…
-
In order to control your AHU over the Internet, connect it to the network router which has access to the Internet. Follow the router manual to configure port forwarding to the unit IP address. Depending on whether you will use your computer or smart phone with the Komfovent app to control your AHU…
-
5.1. Control panel C5.11
C5.1 is control panel with coloured touch-screen for remote control of your air handling unit. This control panel is designed for indication and changing of various functions and settings of the unit. 16:30 21,9 °C 21,3 °C Temperature ECONOMY 1 Fig. 51. Control panel tap. If the unit is connected to…
-
Without calibration, CF heat exchanger may get frozen and will be damaged during low outdoor temperatures. To change the ventilation mode settings: select a desired mode and set a desired air volume or temperature with the arrows. To turn of the AHU and return to a home screen: UAB KOMFOVENT we…
-
5.2. Starting the Unit With a Computer
If the unit was ordered without a control panel or it is not used, you can start it with your computer. In this case the unit is controlled via a web browser. Connect your computer directly to the AHU or to the same computer network as described in Chapter 4.5. Run the Internet browser on the…
-
To start the unit and change the ventilation mode settings
1. Press button “Modes”. 2. Select a desired ventilation mode from the list. 3. Enter desired air flow and temperature in the selected mode settings. 4. Press “Save” button at the bottom of the screen. You can stop the unit by pressing ON/OFF button in the “Overview” window. UAB KOMFOVENT we reserve…
-
5.3. Calibration of Clean Filters
KLASIK control automation continuously monitors filter contamination. Pressure drop of clean filters is preset in the factory. If filters are from another manufacturer or of different filtering class, we recommend performing initial calibration of clean filters before commissioning of the unit.…
-
5.4. Quick Inspection
The first time you start your device, make sure that: Task Yes No Comments Control panel is working, responds to touch, no error messages All air filters are installed Air dampers fully open There are no unusual noise or vibrations Changing the ventilation modes changes the fan speed The unit is…
-
APENDIX NO. 1. ADJUSTMENT OF THE ROTARY HEAT EXCHANGER WHEEL
In the KLASIK 8 and larger units, a large-diameter rotary heat exchanger is used. Since, during the operation, the airflow constantly pushes the rotor wheel, due to its dimensions, to one side, it can eventually distort, causing the rotor sealing brushes and axle bearings to wear out faster or even…
-
5 1/2 L L AIR FLOW DIRECTION 6 After adjusting the wheel tilt, loosen the adjusting screw so that the rotor shaft presses firmly against the adjusting plates. UAB KOMFOVENT we reserve the right to make changes without prior notice KLASIK_installation manual_26-10 1/2 L 1/2 L L AIR FLOW DIRECTION L…
-
APENDIX NO. 2
WARRANTY INFORMATION Dear Customer, KOMFOVENT thanks you for your choice. We are pleased that you have chosen us and will strive to ensure you are satisfied with your purchased product. To avoid misunderstandings, we kindly ask you to read the installation and operating instructions of the product…
-
WARRANTY CONDITIONS
1. The warranty does not apply in the following cases: 1.1. If the product usage or operating conditions, as specified in the installation and operating instructions, are violated; 1.2. If the storage conditions of the unit are violated; 1.3. If there are signs indicating attempts of unqualified…
-
SERVICE AND SUPPORT
PARTNERS LITHUANIA UAB KOMFOVENT Phone: +370 5 200 8000 service@komfovent.com www.komfovent.com AT FINLAND Komfovent Oy Muuntotie 1 C1 FI-01 510 Vantaa, Finland Phone: +358 20 730 6190 toimisto@komfovent.com www.komfovent.com CZ GERMANY Komfovent GmbH Konrad-Zuse-Str. 2, 42551 Velbert, Deutschland…