1. INTRODUCTION
This manual is intended for qualified technicians installing the DOMEKT air handling unit. Qualified professionals are persons with sufficient professional experience and knowledge of ventilation systems, their installation, knowledge of electrical safety requirements and ability to work without…
-
Counter flow (CF) heat exchangers may freeze at low outside air temperatures. For this reason, these units are equipped with several different frost protection functions: • Standard – Air-handling unit is stopped when outside air temperature drops below -4°C for longer than 1 hour. Then the unit is…
-
1.3. Components
Below are the principal diagrams of air handling units, including the marking of assemblies of the unit. 1.3.1. Vertical units Domekt R 200 V - R 200 V E1 - R 200 V E2 EHA ETB ETA ODA SUP SUP ODA ETA ETB EHA C8 C8 ETB ETH ETH ETA SUP ODA ODA EHA 6 SUP EHA ETA RIGHT INSPECTION SIDE ETB LEFT…
-
Domekt R 350 V
EHA ODA ETB SUP ETA SUP ETB ETA 10 C8 EHA ODA C8 ETB ODA EHA ETB SUP ETA ETA SUP EHA ODA RIGHT INSPECTION SIDE LEFT INSPECTION SIDE 1.3.2. Flat units Domekt R 150 F RIGHT INSPECTION SIDE ODA SUP SUP ODA EHA ETA ETA EHA LEFT INSPECTION SIDE 3 5 ETB ETB 5 3 Domekt R 250 F ODA RIGHT INSPECTION SIDE EHA…
-
Domekt R 300 F
ETB ETB EHA RIGHT INSPECTION SIDE EHA SUP SUP LEFT INSPECTION SIDE C8 ODA ETA ETA ODA C8 Domekt CF 200 F EHA ETA ODA SUP SUP RIGHT EHA INSPECTION SIDE ODA LEFT ETA INSPECTION SIDE Domekt CF 200 F E0 EHA SUP SUP EHA ODA ETA ETA ODA RIGHT INSPECTION SIDE C8 LEFT INSPECTION SIDE C8 – outdoor air 1…
-
2. UNIT TRANSPORTATION AND STORAGE
Equipment must be transported and stored in the original packaging. During transportation, equipment must be properly secured and further protected against possible mechanical damage, rain or snow. Fig. 3. Examples of equipment packaging Forklift truck or crane can be used for loading or unloading.…
-
3. MECHANICAL INSTALLATION
3.1. Installation site requirements DOMEKT units are designed for installation in household or technical rooms with an air temperature of 0°C to +40°C, relative humidity from 20% to 80% (non-condensing). It is recommended to install the air handling unit in a separate room or in an insulated attic…
-
Unit model
A, mm Domekt R 150 F 830 B, mm 830 Domekt CF 200 F 344 344 Domekt CF 200 F E0 255 255 Domekt R 200 V - R 200 V E1 - R 200 V E2 375 375 Domekt R 250 F 892 892 Domekt R 300 F 1140 1140 Domekt R 300 V 655 655 Domekt R 350 V 650 650 Make sure to provide a suitable installation location for…
-
h2
-
3.3. Hanging of the units
Smaller vertical units can be hung on the walls, partitions, or other vertical structures. Such units come with their wall mounting brackets and mounting screws. If necessary, use other fixing screws suitable for the specific type of wall or partition (concrete, plasterboard, brick, etc.) Flat units…
-
3.3.1. Types and dimensions of suspension brackets
Special brackets, wall screws with plastic bushings and self-tapping screws are provided for mounting the units. When mounting the units, care must be taken to ensure that vibrations of the unit are not transmitted to the building structures, as it may lead to additional noise. In order to eliminate…
-
3.4. Installation of Domekt R 200 V with kitchen exhaust hood
Domekt R 200 V - R 200 V E1 - R 200 V E2 air handling units may be supplied with two types of kitchen hoods. These units are designed to be integrated into the kitchen furniture above the cooker. Available kitchen hoods are equipped with a damper that closes airflow when not in use. When kitchen…
-
The kitchen hood wires are connected to the terminal block, located under a breakaway tab at the bottom of the unit. 3.4.1. Dimensions of Domekt R 200 V with a kitchen hood The following are the dimensions of the unit and mounting dimensions for a kitchen hood. 280 x 2 = ~690 Fig. 8. Dimensions with…
-
When installing the Domekt R 200 V, R 200 V E1 or R 200 V E2 ventilation unit in the kitchen or another visible place, additionally a decorative panel or furniture board can be attached to the unit. “Panel mounting brackets kit” is used in this case.1. 1 x1 2 x1 3 x6 1 Bracket (left) 2 Bracket…
-
The decorative panel is hung directly on to the installed brackets
Fig. 12. Installation of the decorative panel To hang the furniture board onto the unit, it is needed to screw the fixing plates1 on the board. Plates are fixed with wood screws designed for the specific type and weight of the material from which the furniture board is made. Ø2 th ep (d 3 –5 )x m m…
-
3.5. Duct system installation
The air in and out of the unit flows through the duct system. The duct system should be designed and selected to have low airflow rates and low pressure differentials, ensuring more accurate airflow rates, lower energy consumption, lower noise levels and longer life of the unit. Outdoor vents must…
-
4 WC C8 controller board 2 Switch 3 Spring return actuator with end position contacts (e.g. Belimo LF-230S) 4 Air closing damper Additional extraction duct 6 Air handling unit Fig. 15. Example of mounting of an additional air extraction duct • • • • • Ducts connecting the unit to the exterior of the…
-
When connecting the heater/cooler pipes, they must be supported by a box spanner – otherwise they will be damaged. If water is used in the heater, for frost protection water temperature sensor (B5), must be installed and fixed with strap on the return water pipe as close to the heater as possible.…
-
The drainage pipeline must be mounted with a slope, without any constrictions or loops, which might prevent water from draining easily. If the drainage pipeline passes through the outdoors or unheated premises, it must be adequately insulated or equipped with a drainage heating cable to prevent…
-
4.2. Connecting electrical components
All internal and external unit elements are connected to the main controller board. C8 AB Local network or internet connection Control panel connector Fuse for electric heaters (T 10A) ID : CD 1-A BC D2 -A BC D3 Fuse for power supply (T 3,15A) -A BC D4 Controller board type and QR code for the…
-
The terminals of the external elements of the controller board are numbered and are used only to connect optional components and may remain empty if no additional features are required. B GND 0..10V Air quality sensor / Humidity sensor Water mixing valve actuator / GND DX control 0..10V Frost…
-
• Inputs (13–15) – to switch between the “Override” ventilation modes (see “Domekt User Guide”), connect the respective terminals together with the common terminal 13 (ventilation modes will operate until the terminals are connected). To activate these modes, a switch, a motion detector or kitchen…
-
4.3. Control panel installation
The control panel must be installed in a room with: ambient temperature − 0...40°C; relative humidity 20% to 80%; protection against accidental water droplets. The control panel can be mounted on a concealed mounting box or directly on the wall – the screws are supplied with the panel. You can also…
-
4.4. Connecting the unit to an internal computer network or the Internet
The unit can be controlled not only by the control panel, but also by computer or smart phone. In such cases, the air handling unit must be connected to an local computer network or to the Internet. The unit is controlled by a computer using a web browser, or a smartphone with a Komfovent Control…
-
To control the unit over the Internet, it must be connected to a network router with Internet access. Subsequent settings vary depending on whether the unit is controlled by a computer or a smartphone. • The easiest way to manage your unit over the internet is to use a smartphone with the Komfovent…
-
By default, the following standard ventilation modes are preprogrammed in the unit
AWAY NORMALUS NORMAL MINIMALUS Vėdinimo intensyvumas 20% 20% Pageidaujama 20°C temperatūra 20°C Ventilation intensity Set temperature INTENSYVUS INTENSIVE BOOST MAKSIMALUS Vėdinimo intensyvumas 70% 70% Pageidaujama 20°C temperatūra 20°C Vėdinimo intensyvumas 50% 50% Pageidaujama 20°C temperatūra…
-
5.2. Control panel C6.2
If the unit is connected to the mains and is currently stopped, a red indicator next to the power button will light up. To turn ON/OFF the AHU or select the operating mode: Press the desired operating mode button. The blue indicator light will be on next to the active mode. The unit is switched off…
-
To start the unit, press the required ventilation mode button
user user CONTROL SETTINGS TURN ON ALARMS SETTINGS TURN ON OPERATION CONTROL OPERATION MODES OPERATION CONTROL NORMAL INTENSIVE BOOST AWAY NORMAL INTENSIVE BOOST KITCHEN FIREPLACE OVERRIDE HOLIDAYS KITCHEN FIREPLACE OVERRIDE HOLIDAYS Logout ALARMS CONTROL OPERATION MODES AWAY Logout ECO АUТО ECO…
-
5.4. Quick check
When you start your unit for the first time, check whether: Task Yes No Notes The control panel operates responds to touches, and there are no error messages The air dampers opens fully There are no extraneous sounds and vibrations Changing the ventilation modes changes the fan speed The unit is…
-
APENDIX NO.1
WARRANTY INFORMATION Dear Customer, KOMFOVENT thanks you for your choice. We are pleased that you have chosen us and will strive to ensure you are satisfied with your purchased product. To avoid misunderstandings, we kindly ask you to read the installation and operating instructions of the product…
-
WARRANTY CONDITIONS
1. The warranty does not apply in the following cases: 1.1. If the product usage or operating conditions, as specified in the installation and operating instructions, are violated; 1.2. If the storage conditions of the unit are violated; 1.3. If there are signs indicating attempts of unqualified…
-
SERVICE AND SUPPORT
PARTNERS LITHUANIA UAB KOMFOVENT Phone: +370 5 200 8000 service@komfovent.com www.komfovent.com AT FINLAND Komfovent Oy Muuntotie 1 C1 FI-01 510 Vantaa, Finland Phone: +358 20 730 6190 toimisto@komfovent.com www.komfovent.com CZ GERMANY Komfovent GmbH Konrad-Zuse-Str. 2, 42551 Velbert, Deutschland…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.