Инструкция на Мультизональные системы серии CH-UNIT
Мультизональные системы серии CH-UNIT - CH-6.0N1, CH-10.0N1. Инструкция по монтажу и эксплуатации.
Смотрите также: Инструкция по монтажу и эксплуатации →
Загружаем документ…
Текст инструкции
-
ENGLISH
ESPAÑOL MANUAL DE INSTALAÇÄO E DE FUNCIONAMENTO BRUGER- OG MONTERINGSVEJLEDNING INSTALLATIE- EN BEDIENINGSHANDLEIDING HANDBOK FÖR INSTALLATION OCH ANVÄNDING ΕΓΧΕΙΡΙΔΙΟΕΓΚΑΤΑΣΤΑΣΗΣΚΑΙΛΕΙΤΟΥΡΓΙΑΣ PORTUGUÊS ITALIANO FRANÇAIS INSTALLATION AND OPERATION MANUAL MANUAL DE INSTALACIÓN Y FUNCIONAMIENTO…
-
Specifications in this manual are subject to change without notice in order that HITACHI
may bring the latest innovations to their customers. Whilst every effort is made to ensure that all specifications are correct, printing errors are beyond Hitachi’s control; Hitachi cannot be held responsible for these errors.
-
ATTENTION
This product shall not be mixed with general house waste at the end of its life and it shall be retired according to the appropriated local or national regulations in a environmentally correct way. Due to the refrigerant, oil and other components contained in Air Conditioner, its dismantling must be…
-
DANGER – Immediate hazard which WILL result in severe injury or death
PELIGRO – Riesgos inmediatos que PRODUCIRÁN lesiones personales graves e incluso la muerte. GEFAHR – Unmittelbare Gefahrenquellen, die zu schweren Verletzungen oder zum Tod führen. DANGER – Dangers instantanés de blessures corporelles sévères ou de mort. PERICOLO – Pericolo immediato che PRODURRÀ…
-
SAFETY SUMMARY
1. Safety Summary WARNING: −− Do not perform installation work, refrigerant piping work and electrical wiring connection without referring to our installation manual. −− Check that the ground wire is securely connected. −− Connect a fuse of specified capacity. CAUTION: Do not install the CH unit…
-
STRUCTURE
2.2. REFRIGERANT CYCLE 2.2.1. CH Unit - CH-(6.0/10.0)N1 To Indoor Unit To Outdoor Unit Electric Expansion Valve MVD1 Strainer S High Pressure Gas Low Pressure Gas Electric Expansion Valve MVD2 Capillary Tube MVD1 Electric Expansion Valve MVS2 Electric Expansion Valve MVS1 Strainer S High Pressure…
-
TRANSPORTATION AND
HANDLING 3. TRANSPORTATION AND HANDLING Transport the product as close to the installation location as practical before unpacking WARNING: Do not put any foreign material into the CH Unit and check to ensure that none exists in the outdoor unit before the installation and test run. Otherwise, a…
-
4. CH UNIT INSTALLATION
DANGER: Do not install the Indoor Unit in a flammable environment to avoid fire or an explosion. WARNING: Check to ensure that the ceiling slab is strong enough. Do not install the CH Unit outside. If installed outdoors, an electric hazard electric leakage will occur. 4.1. FACTORY-SUPPLIED…
-
4.2 Initial Check
−− Install the CH unit with a proper clearance around it for maintenance working space, as shown in next figure. Unit: mm Electrical Box Service Space (300 x 300) Upper Side Min. 70 Min. A sustain the CH unit. If the ceiling is weak, abnormal sound and vibration may occur. −− The refrigerant flow…
-
4.3 Suspension Bolts
Step 1 Unit: mm 1. Select a final location and installation direction of the CH unit paying careful attention to the space for the piping, wiring and maintenance. 23 330 (For Suspension Bolt) 40 Suspension Bracket 2-11 x 34 Slotted Hole 2. Mount suspension bolts after selecting the final location of…
-
4.4 Installation
4.4.1 Changing the Location of Electrical Box Depending on the installation space, changing the location of electrical box is available. In case of changing the location of electrical box, follow the procedure below. 1. Remove the service cover for the electrical box. 2. Remove the service cover for…
-
4.4.2 Marking of the Positions of the
Suspension Bolts and Wiring Connections 1. Mark the positions of the suspension bolts, refrigerant piping connections and wiring connection. 2. Installation dimensions are shown in chapter 2 “Structure”. 4.4.3 Mounting the CH Unit 1. How to put Nuts Put nuts on each of the two suspension bolts…
-
5. REFRIGERANT PIPING WORK
DANGER: −− Use refrigerant R410A in the refrigerant cycle. Do not charge oxygen, acetylene or other flammable and poisonous gases into the refrigerant cycle when performing a leakage test or an air-tight test. These types of gases are extremely dangerous and can cause an explosion. It is…
-
5.3 Refrigerant Piping Work
Provide the refrigerant pipe in the field. Make sure that the refrigerant pipe should be connected to the same refrigerant cycle unit. ¡¡ Position of Piping Connection 20 301 Service Cover for Electrical Box Electrical Box (Available for Both Sides) Low Pressure Gas Pipe Connection (Ø Flare Nut) 38…
-
Piping Connection Connected Indoor Unit Capacity (HP) CH-6.0N1 Field Flaring Work 0.8 to 1.5 Low Pressure Gas Pipe (Field-Supplied) (Ø15.88) High Pressure Gas Pipe (Field-Supplied) (Ø12.7) CH Unit T1 Gas Pipe (Field-Supplied) (Upper Surface) Accessory Pipe Accessory Pipe Field Flaring Work 1.6 to…
-
Piping Insulation Insulation (ID38) Insulation (ID16) CH-6.0N1 Clamp CH Unit (Upper Surface) Clamp Insulation (ID38) Insulation (ID43) Insulation (ID22) Insulation (ID16) Clamp CH Unit CH-10.0N1 Insulation (ID38) Insulation (ID43) (Upper Surface) Insulation (ID20) Insulation (ID43) Clamp Insulation…
-
6.2 Electrical Wiring Connection
The electrical wiring connection for the CH unit is shown in next figure. 1. Turn OFF the main power switch and take off the electrical box cover of CH unit. 2. Connect the power supply and earth wires to the terminals in the electrical box. 3. Connect the wires of the operating line to the…
-
Example of Electrical Wiring The following figure shows the example of electrical wiring around the CH units. Refer to the Technical Catalog for Outdoor Unit regarding the electrical wiring of the whole system. Outdoor Unit Outdoor Unit Power Supply AC 1~ 220-240V/50Hz AC 1~220V/60Hz Earth Leakage…
-
TEST RUN
7. TEST RUN NOTE: Test run should be performed according to “Installation & Operation Manual” of Outdoor unit. Refrigerant piping and connecting wires should be connected to the same refrigerant cycle system. If they are connected to the dissimilar refrigerant cycle systems, a malfunction may…