UTOPIA IVX PREMIUM / IVX STANDARD SERIES
-
Contents
Contents i SMGB0079 rev.0 - 01/2013 General information 1 Unit Installation 2 Piping work and refrigerant charge 3 Electrical Wiring 4 Control System 5 Optional functions 6 Test Run 7 Troubleshooting 8 Spare Parts 9 Servicing 10 Electrical checks of main parts 11 Maintenace notes 12
-
1.1 General information
1.1.1 General notes No part of this publication may be reproduced, copied, filed or transmitted in any shape or form without the permission of HITACHI Air Conditioning Products Europe, S.A. Within the policy of continuous improvement of its products, HITACHI Air Conditioning Products Europe, S.A.…
-
1.2 Safety
1.2.1 Applied symbols During normal air conditioning system design work or unit installation, greater attention must be paid in certain situations requiring particular care in order to avoid damage to the unit, the installation or the building or property. Situations that jeopardise the safety of…
-
1.3 Product guide
1.3.1 Classification of outdoor unit models IVX series Unit type (Outdoor unit): RAS Position-separating hyphen (fixed) Capacity (HP): 2, 2.5, 3, 4, 5, 6, 8, 10, 12 H = Heat pump V = Single phase unit (1~ 230V 50Hz) - = Three phase unit (3N~ 400V 50Hz) N = R410A refrigerant P: Premium series C…
-
1.3.3 Product guide: Outdoor units
IVX Premium 1~ 230V 50Hz Unit Code Unit RAS-2HVNP 60288519 RAS-2.5HVNP 60288520 RAS-3HVNPE 1 3N~ 400V 50Hz Code Unit Code Unit Code Unit Code 7E304005 RAS-4HVNPE 7E304007 RAS-4HNPE 7E304107 RAS-5HVNPE 7E304008 RAS-5HNPE 7E304108 RAS-6HVNPE 7E304009 RAS-6HNPE 7E304109 RAS-8HNPE 7E310110 RAS-10HNPE…
-
1.3.4 Outdoor unit accessory code list
Name Description Code DBS-26 Drain discharge connection 60299192 AG-264 Air flow guide - AG-335A Air flow guide 60291431 WSP-264 Wind guard 60291728 WSP-335A Wind guard 60291432 ASG-NP80F Snow protection hood; air outlet (Zinc plate) - ASG-NP80FS2 Snow protection hood; air outlet (Stainless plate)…
-
1.3.5 Product guide: Indoor units & complementary systems
RCI and RCIM indoor units FSN(2/3)(E)(i) indoor units 1 RCI RCIM 4-way cassette 4-way cassette (compact) Unit Code Unit Code Unit Code RCI-1.0FSN3Ei 7E403014 RCI-1.0FSN3 60278119 RCIM-0.8FSN2 60278010 RCI-1.5FSN3Ei 7E403015 RCI-1.5FSN3 60278120 RCIM-1.0FSN2 60278011 RCI-2.0FSN3Ei 7E403016…
-
RCD and RPC indoor units FSN2(E) indoor units RCD RPC 2-way cassette Ceiling type Unit Code Unit Code RCD-1.0FSN2 60278029 RCD-1.5FSN2 60278030 RCD-2.0FSN2 RCD-2.5FSN2 60278031 RPC-2.0FSN2E 7E440003 60278032 RPC-2.5FSN2E RCD-3.0FSN2 7E440004 60278033 RPC-3.0FSN2E 7E440005 RCD-4.0FSN2 60278034…
-
RPC, RPI and RPIM indoor units
-
RPK, RPF and RPFI indoor units
FSN(H)(2/3)(E/M) indoor units RPK RPF RPFI Wall type Floor type Floor concealed type Unit Code RPK-0.8FSN3M 60278146 RPK-0.8FSNH3M 60278154 RPK-1.0FSN3M 60278147 RPK-1.0FSNH3M 60278155 Unit Code Unit Code RPF-1.0FSN2E 7E450001 RPFI-1.0FSN2E 7E460001 RPF-1.5FSN2E 7E450002 RPFI-1.5FSN2E 7E460002…
-
DX-Interface
-
2.1 Safety summary
DANGER • Install the outdoor unit with sufficient clearance around it for operation and maintenance as shown in the next pages. • Install the outdoor unit where good ventilation is available. • Do not install the outdoor unit where exists a high level of oil mist, salty air or sulphurous atmosphere.…
-
2.2 Transportation of outdoor unit
DANGER Do not put any foreign material into the outdoor unit and check to ensure that none exists in the outdoor unit before the installation and test run. Otherwise a fire or failure will occur. CAUTION 2 Transport the products as close to the installation location as practical before unpacking.…
-
2.3 Center of gravity
-
2.4 Factory-supplied accessories for RAS-12HN(P/C)
Make sure that the following accessories are packed with the unit. NOTE If any of these accessories are not packed with the unit please contact your dealer. Accessory Quantity Pipe with Flare Nut for Refrigerant Piping 1 17 SMGB0079 rev.0 - 01/2013 2
-
2.5 Installation space (Initial ckeck)
NOTE The following images are for illustration purposes only. 2.5.1 Basic sizes ≥ ≥ RAS-2HVNP - RAS-2.5HVNP - RAS-3HVNC ≥ ≥ ≥ ≥ ≥ All models (except RAS-2HVNP - RAS-2.5HVNP - RAS-3HVNC) ≥ Units in mm. 18 SMGB0079 rev.0 - 01/2013 ≥ ≥ ≥ ≥
-
2.5.2 RAS-(2-2.5)HVNP / RAS-3HVNC
-
(Unit: mm) Blocked in Inlet Side Upper Side Open Single Installation Multiple Installation (Two units or more) 200 or more of the back space is acceptable when the right and left sides are open. Dimensions in ( ) shows numbers especially for RAS-3HVNPE. Allow 100 mm of space between units. Leave…
-
Outlet Side Blocked
Upper Side Open Single Installation Multiple Installation (Two units or more) Allow 100 mm of space between units. Both right and left sides shall be open. Be sure to use the fan direction guide. Leave open both right and left sides. Be sure to use the fan direction guide. Allow 100 mm of space…
-
Stack installation (allowed up to 2 Units)
Upper Side Open Single Installation Multiple Installation Close the part A not to allow the outlet air bypassed. Install to avoid the drain water from upper unit falling on the lower unit. Allow 100 mm of space between units. Serial sideways installation allowed up to two units. Leave open both…
-
2.6 Place provision
2.6.1 Place provision for RAS-(2-2.5)HVNP / RAS-3HVNC 1 Secure the outdoor unit with the anchor 1. Base of outdoor unit 2. Nut 1 3. Special washer (M12) 2 4. Anchor bolts 5. Filled mortar 3 A 6. Concrete 4 A. Max. 17 mm 6 5 Fix the outdoor unit to the anchor bolts by special washer of…
-
The whole of the base of the outdoor unit should be installed on a foundation. When using vibration-proof mat it should also be positioned the same way. When installing the outdoor unit on a field-supplied frame use metal plates to adjust the frame width for stable installation as shown in Figure.…
-
RAS-12HN(P/C) Concrete foundation • Foundation could be on flat and it is recommended to be 100-300 mm higher than ground level. • Install a drainage around foundation for smooth drain. • When installing the outdoor unit fix it by M10 anchor bolts. • When installing the unit on a roof or a…
-
Recommended Metal Plate Size
-
Suspended unit
Suspend the unit as shown in the figures. Ensure that wall can withstand the weight of the outdoor unit indicated on the specifications plate. It is advisable that each foot support should bear the full weight of the unit (in order take account of applied stress fatigue when unit is operating).…
-
Installing location where the unit will be exposed to strong wind
Follow the instructions below to install on the roof or in a place which is not surrounded by buildings and where the product may be buffeted by strong winds. 1 2 Select a place where the input or outlet side of the product is exposed to strong winds. When the outlet is exposed to strong winds…
-
2.7 Optional parts and installation
2.7.1 Optional parts and installation for RAS-(2-2.5)HVNP / RAS-3HVNC Air flow guide wind guard and snow protection hood Optional parts Model Air flow guide AG-264 Wind guard WSP-264 Zinc Plate Air outlet ASG-NP80F Air inlet of rear side ASG-NP56B Air inlet of side face ASG-NP56L Air outlet…
-
Locations of fixing holes
The holes Location shall be made by using self-screws (M4x13) and later shall be used SUS screw (M5x12) for fixing air flow guide. Outdoor Unit Hole (4 locations) 2 One flow guide installation Air discharge grille Air flow Outdoor unit M5 fixing screw x4 (Accessories) Air flow guide 1 • In case of…
-
Specifications Model WSP-264 Quantity 1 per unit Material Galvanized sheet metal + baked painting Color UTOPIA Beige Weight 4.0 kg 1 Fixing screw x 4 [M5 (SUS) x 30]- Unit Accessories 2 Fixing Screw x 10 [M5 (SUS) x 12]- Wind Ward Installation manual 2 Installation restriction “Guard net” “Air flow…
-
Air discharge hood Nº Part name Quantity 1 Right side plate 1 2 Left side plate 1 3 Front panel 1 4 Fixing screw (Accessories) 5 Hole for safety wire rope to prevent overturning Rear suction hood Nº Part name 1 Right side plate Quantity 1 2 Left side plate 1 3 Upper front panel (Upside) 1 4 Upper…
-
A
B C 1. Fixing screw (accessories) 2. Air inlet hood 3. Wire rope (optional for over turning protection) 4. Air discharge hood 5. Outdoor unit A. Rear side B. Left side C Front side NOTE • The holes locations marked with a mark shall be made by using sel screw (M4X13) and later shall be used SUS…
-
2.7.2 Optional parts and installation RAS-3HVNPE / RAS-(4-6)H(V)NCE
Air flow guide wind guard and snow protection hood Optional parts Model Air flow guide AG-335A Wind guard WSP-335A Zinc plate Air outlet ASG-NP335F Air inlet of rear side ASG-NP80B Air inlet of side face ASG-NP80L Air outlet ASG-NP335F52 Air inlet of rear side ASG-NP160BS2 Air inlet of side face…
-
One flow guide installation
Air discharge grille Air flow Air flow guide Outdoor unit M5 fixing screw x4 (Accessories) Service space (In case of upward air discharge) • In case of right and left sides air discharge enough space for air discharge is required. • The downward air discharge is also available. In such case install…
-
Specifications Model WSP-335A Quantity 1per unit Material Galvanized sheet metal + baked painting Color Gray (1.0Y8.5/0.5) Weight 5.5 kg Accessories Fixing screw x 4 [M5 (SUS) x 12] Installation manual Installation restriction “Guard net” “Air flow guide” or “Snow protection hood” is not available…
-
Air discharge hood
Nº Part name Quantity 1 Right side plate Left side plate 3 Front panel 1 4 Stay 4 5 Fixing screw (Accessories) 6 Hole for safety wire rope to prevent overturning Rear suction hood Nº Part name Quantity 1 Right side plate 1 2 Left side plate 1 3 Upper front panel (Upside) 1 4 Upper front panel…
-
A B 1 7 C 1. Fixing screw (Accessories). 2. Rear suction hood 3. Wire rope (Optional. For overturning protection) 4. Air discharge grille 5. Left suction hood 6. Air discharge hood A. Left side B. Front side C. Rear side Specifications of snow protection hood Product name Air discharge hood Model…
-
Air flow guide wind guard and snow protection hood Optional parts Model Air flow guide AG-335A X 2 Wind guard WSP-335A X 2 Zinc plate Snow protection hood Stainless plate (NSSC 180) Air outlet ASG-NP335F X 2 Air inlet of rear side ASG-NP280B Air inlet of side face ASG-NP280L Air outlet…
-
Two flow guides installation
Air discharge grille Air flow Air flow guide (see the note) Outdoor Unit M5 fixing screw x4 (Accessories) NOTE • Air flow direction of both air flow guides should be the same. Service space (In case of upward air discharge) • In case of right and left sides air discharge enough space for air…
-
Specifications Model WSP-335A Quantity 2 per unit Material Galvanized sheet metal + baked painting Color Gray (1.0Y8.5/0.5) Weight 5.5 kg Accessories Fixing screw x 4 [M5 (SUS) x 12] Installation manual Installation restriction “Guard net” “Air flow guide” or “Snow protection hood” is not available…
-
Air discharge hood Nº Part name 1 Right side plate Quantity 1 2 Left side plate 1 3 Front panel 1 4 Stay 4 5 Fixing screw (Accessories) 6 Hole for safety wire rope to prevent overturning Rear suction hood Nº Part name Quantity 1 Right side plate 1 2 Left side plate 1 3 Upper front panel (Upside) 1 4…
-
1. Left suction hood 2. Fixing screw (Accessories) 3. Rear suction hood Upper side 4. Wire rope (Optional. For overturning protection) 5. Rear suction hood Lower side 6. Air discharge hood 7. Air discharge grille 8. Air discharge grille A. Front side B. Left side C. Rear side 43 SMGB0079 rev.0…
-
Specifications of snow protection hood
Product name Air discharge hood Model ASG-NP335F Quantity ASG-NP335FS2 Rear suction hood ASG-NP280B Left suction hood ASG-NP280BS2 2 per unit Bonderized steel sheet Material Iron Color Weight ASGNP280LS2 1 per unit Stainless (NSSC 180) Gray (1.0Y8.5/0.5 or approximation) ASG-NP280L — 3 kg Bonderized…
-
2.7.4 Optional parts and installation RAS-12HN(P/C)
Air flow guide wind guard and snow protection hood Optional parts Model Air flow guide AG-335A X 2 Wind guard WSP-335A X 2 Zinc plate Snow protection hood Strainless plate(NSSC 180) Air outlet ASG-NP335F X 2 Air inlet of rear side ASG-NP335B Air inlet of side face ASG-NP335L Air outlet…
-
Two flow guides installation
Air discharge grille Air flow Air flow guide (see the note) Outdoor Unit M5 fixing screw x4 (Accessories) NOTE Air flow direction of both air flow guides should be the same. Service space (In case of upward air discharge) • In case of right and left sides air discharge enough space for air discharge…
-
Specifications Model WSP-335A Quantity 2 per unit Material Galvanized sheet metal + baked painting Color Gray (1.0Y8.5/0.5) Weight 5.5 kg Accessories Fixing screw x 4 [M5 (SUS) x 12] Installation manual Installation restriction “Guard net” “Air flow guide” or “Snow protection hood” is not available…
-
Air discharge hood Nº Part name Quantity 1 Right side plate 1 2 Left side plate 1 3 Front panel 1 4 Stay 4 5 Fixing screw (Accessories) 6 Hole for safety wire rope to prevent overturning Rear suction hood Nº Part name Quantity 1 Right side plate 1 2 Left side plate 1 3 Upper front panel (Downside)…
-
A 1650 C 1. Left suction hood 2. Fixing screw (Accessories) 3. Rear suction hood Upper side 4. Wire rope (Optional. For overturning protection) 5. Air discharge hood 6. Air discharge grille 7. Rear suction hood Lower side 8. Outdoor unit A. Front side B. Left side C. Rear side 49 SMGB0079 rev.0…
-
Specifications of snow protection hood
Product name Air discharge hood Model ASG-NP335F Quantity ASG-NP335FS2 Rear suction hood ASG-NP335B Left suction hood ASG-NP335BS2 2 per unit Bonderized steel sheet Material Iron Color Weight ASGNP335LS2 1 per unit Stainless (NSSC180) Gray (1.0Y8.5/0.5 or approximation) ASG-NP335L — Bonderized steel…
-
3.1 General notes before performing pipe work
3.1.1 Piping Materials 1 In order to avoid supply problems in terms of local regulations and quality, prepare locally-supplied copper pipes. NOTE In case of using copper pipes for piping sections bigger than Ø19.05 mm (3/4 inches), flaring work cannot be performed. If necessary, use a joint adapter.…
-
CAUTION
• Cap the end of the pipe when pipe is to be inserted through a wall hole. • Do not put pipes on the ground directly without a cap or vinyl tape at the end of the pipe. • If piping installation is not completed until next day or over a longer period of time, braze off the ends of the piping and…
-
3.1.2 Three principles on refrigerant piping work
In case of using refrigerant R410A in the refrigeration cycle, the refrigeration oil should be of a synthetic type one. In order to avoid oxidation, pay much careful attention to basic piping work control to avoid infiltration of moisture or dust during the refrigerant piping work. Three principles…
-
3.1.4 Brazing work
The most important work in the refrigerant piping installation work is the brazing of the pipes. If it accidentally occurs a leakage due to a careless brazing process, it will cause clogged capillary pipes or serious compressor failure. In order to guarantee a proper brazing neck between different…
-
3.2 Piping connection for outdoor unit
3.2.1 RAS-(2-2.5)HVNP / RAS-3HVNC 1 Take the piping cover away from the unit. Then fetch the pipes through the rear side and route piping according to the installation place as shown in the figure. Make holes by cutting along the guideline at the rear of the cover or punching with a driver. Remove…
-
1 The pipes can be connected from 4 directions. Make holes in the piping cover or cabinet for taking out pipes. Nº Description Rear side piping work Pipe Cover Right side piping work Bottom side piping work (Knock out hole) Front side piping work Piping work Stop Valve Removing…
-
For the front and side piping
Select the correct knock-out size depending on whether it is for power wiring or transition wiring RAS-3HVNPE / RAS-(4-6)H(V)N(P/C)E / RAS-(8-10)HN(P/C)E RAS-12HN(P/C) Right-SIde Piping Hole Right side piping hole Front piping hole Front-SIde Piping Hole Front piping hole Rigth side piping hole B…
-
For the rear side piping
After removing the rear-side piping cover, punch out the “A” holes along the guide line. Rear Cover 3 NOTE Remove the rear pipe cover under the rear cover and remove part following the slit. Mount the piping cover in order to avoid water entering into the unit. Seal the holes where pipes and…
-
3.2.3 Outdoor unit stop valve
Remove the stop valve cap before performing the air tight test after connecting the flare nut. Tighten the spindle valve in clockwise according to the following table “Tightening Torque of Stop Valves.” Tighten the flare nut according the specified torque. If the tightening torque is excessive, it…
-
Hexagonal wrench size used for spindle valve
2HP, 2.5HP 3HP, 4-6HP Standard Gas valve 4 mm 5 mm - Liquid valve 4 mm 4 mm 4 mm (*) Size Do not apply two spanners at this position. If applied, leakage will occur. 4-6 HP Premium, 8-12HP Stop valve (Spindle type) Flare nut Use two spanners here for pipe connection Don not apply two spanners work…
-
3.3 Refrigerant piping range
3.3.1 Refrigerant piping length The refrigerant piping between the indoor unit and the outdoor unit should be designed using the following chart. Keep the design point within the area of the chart, which is showing the applicable height difference according to piping length. 3.3.2 Piping system for…
-
Maximum refrigerant piping length
-
IVX Standard series
-
3.3.3 Piping system for line branch
IU quantity allowed OU 3 HP 4 HP IVX Premium 2 -3 2-5 IVX Standard 5 HP 6 HP 8 HP 10 HP 2-6 12 HP 2-8 2-4 3 (picture is as example) Maximum refrigerant piping length (Line branch system) IVX Premium series (m) Outdoor Unit 3HP Maximum piping length between the Actual Length (L1) 4HP 5HP 6HP 8HP…
-
3.3.4 Combinations of piping size and piping length
IVX Premium series Liquid Gas Ø6.35 Ø9.52 Ø9.52 Ø12.70 Ø15.88 Ø19.05 Ø12.70 Ø15.88 15 Ø19.05 Ø12.70 Ø22.20 Ø25.40 Ø15.88 Ø19.05 Ø22.20 Ø15.88 Ø25.40 Ø28.60 Ø22.20 Ø25.40 Performance capacity Ø28.60 (m) 2 HP - 15 - - - - - - - - - - - 2.5 HP - 50 30 - 20 (3) 20 (3) - - - - - - - - - - - 3 HP - (1)(2)…
-
3.3.5 Refrigerant piping size and multikit/distributor selection
CAUTION • Do not use refrigerant pipe sizes other than those indicated in this Technical Catalogue. The diameter of the refrigerant pipes depends directly on the outdoor unit capacity. • If larger diameter gas refrigerant pipes are used, the circuit lubrication oil tends to separate from the gas…
-
3 indoor units system
-
Line branch system
-
3.3.6 System installation
NOTE • Pipe connection size on outdoor units, indoor units and the multikit or distributor vary according to the system. • The sizes of the indoor and outdoor units could be different. Adjust the flare adapter (accessory) to the indoor pipe connection in these cases. Height Difference Between Indoor…
-
Correct position of distributor (available also for quad installation)
• This is the correct position: Up Branch pipe Greater than 0.5 m Refrigerant direction Main pipe Main pipe Refrigerant direction Down • This is wrong position. Refrigerant direction Branch pipe Main pipe Refrigerant direction Main pipe Branch pipe Branch pipe 4 Correct position of Triple Branch…
-
3.4 Refrigerant charge
CAUTION • Do not charge OXYGEN, ACETYLENE, or other flammable and poisonous gases into the refrigerant, as an explosion could occur. It is recommended that oxygen free nitrogen be charged for these types of test cycles when performing a leakage test or an airtight test. These types of gases are…
-
3.4.1 Caution of the pressure by check joint
When the pressure is measured, use the check joint of gas stop valve (A), and use the check joint of liquid piping (B) in the figure below. At that time, connect the pressure gauge according to the following table because of high pressure side and low pressure side changes by operation mode.…
-
3.4.2 Refrigerant charge quantity
Although refrigerant has been charged into this unit, additional refrigerant charge is required according to piping length. 1 2 The additional refrigerant quantity should be determined and charged into the system according to the following procedure. Record the additional refrigerant quantity in…
-
Additional refrigerant charge calculation method
Calculate the additional refrigerant charge amount according to the following steps: Step 1: Additional refrigerant charge calculation for liquid piping (W1 (kg)) Outdoor units have been charged with refrigerant for 30m (20m for RAS-3HVNC) of actual piping length, an additional refrigerant…
-
Step 3: Calculation of total additional refrigerant charge (W (kg))
• For all UTOPIA units except RAS-(8-12)HN(P/C)(E) Put weight W1 and W2 calculated in step 1 and step 2 into the following formula: W = W1 + W2 System example (W) = • + = kg For UTOPIA units RAS-(8-12)HN(P/C)(E) In case of RAS-(8-12)HN(P/C)(E), it must be used the following formula: W = W1 + W2 - C…
-
Setting of pipe length DSW
DSW2 setting will be required only when the refrigerant pipe length is shorter than 5 m or longer than 30 m. Pipe length setting shall be performed as shown below. (The ■ side in the DIP switch show the position.) DSW2 on outdoor PCB1 Factory setting Piping length between 5 m and ℓ(m) Pipe Length…
-
3.5 Caution in case of refrigerant leakage
The installers and those responsible for drafting the specifications are obliged to comply with local safety codes and regulations in the case of refrigerant leakage. 3.5.1 Maximum permitted concentration of hydrofluorocarbon (HFC) The refrigerant R410A, charged in the UTOPIA series system, is an…
-
3.6 Piping work for compatibility with the piping of current installations where is
used R22 or R407C. NOTE Contact your Hitachi dealer for specific support on your instalation. The new IVX Premium and IVX Standard are compatible with those installations that have been operating with R22 or R407C. This allows installing the IVX Premium/Standard Outdoor Units, which operate with…
-
3.6.3 Permissible range for existing Air-Conditioning Pipes
-
3.6.4 Renewal kit selection model
Hitachi offers, as an accessory, a renewal kit: Recommended renewal kit Renewal Kit IVX Premium External Attachment to Outdoor Unit [Short Pipe (local) + Kit + Existing Piping] RAS-(2/2.5)HVNP TRF-NP63S RAS-3HVNPE TRF-NP160S RAS-(4-6)H(V)NPE (TRF-NP160S) Renewal Kit Internal Attachment to Outdoor…
-
Model
TRF-NP160U Pipe 130 For liquid pipe Pipe connecting port Pipe connecting port for O.U (Ø38.1) for I.U (Flare connection) (Flare connection) 262 130 For gas pipe Pipe connecting port (Ø38.1) Pipe connecting port for I.U (Flare connection) for O.U (Flare connection) O.U.: Outdoor Unit I.U.: Indoor…
-
Renewal kit installation (Example)
RAS-(2/2.5)HVNP - RAS-3HVNC Field-Supplied pipes (with insulation) Strainer for liquid pipe (with accessory insulation) Put tape on insulation crossover (c) Existing refrigerant pipes b (a) Put tape on insulation crossover Strainer for gas pipe (with accessory insulation) RAS-3HVNP…
-
Existing refrigerant pipe (Outlet on the rear side) Existing refrigerant pipe (Brazing connection) Strainer for liquid pipe Flare connection Strainer for gas pipe Brazing connection Elbow connection (Field-Supplied) Existing refrigerant pipe (Outlet on the rear side) Existing refrigerant pipe…
-
3.7 Drain piping
3.7.1 Drain discharging boss When the base of the outdoor unit is temporarily utilized as a drain receiver and the drain water in it is discharged, this drain boss is utilized to connect the drain piping. Model Applicable Model DBS-12L RAS-(2/2.5)HVNP RAS-3HVNC DBS-26 RAS-3HVNPE RAS-(4-6)H(V)N(P/C)E…
-
4.1 General notes
CAUTION • Before any electrical wiring work or regular inspections, switch off the main power supply switches of the indoor and outdoor units. Wait three minutes before starting installation or maintenance work. • Make sure that the indoor and outdoor are completely stopped before starting work on…
-
MODEL
Z max (Ω) RAS-2HVNP - MODEL Z max (Ω) RAS-2.5HVNP - RAS-3HVNPE 0.39 RAS-3HVNC - RAS-4HVNPE 0.27 RAS-4HVNCE 0.27 RAS-5HVNPE 0.27 RAS-5HVNCE 0.27 RAS-6HVNPE 0.27 RAS-6HVNCE 0.27 RAS-4HNPE - RAS-4HNCE - RAS-5HNPE - RAS-5HNCE - RAS-6HNPE - RAS-6HNCE - RAS-8HNPE - RAS-8HNCE - RAS-10HNPE - RAS-10HNCE…
-
4.2 Electrical wiring connection for the outdoor unit
The correct electrical wiring connection for the outdoor unit is shown below. 1 Insert the power source cables L1, L2, L3 and N (for 400V/50Hz) or L1 and N (for 230V/50Hz ) and the ground cable into the ring core, coiling them with two turns and fix the cables using the cable tie (accessory). As…
-
Connect the wires between the outdoor unit and the indoor unit to the terminals 1 and 2 on the terminal board. 1. Power supply 1~ 230V. 1. Power supply 3N~ 400V. 2. Control cable (5V). 2. Control cable (5V). Fix the cable with the clamp supplied in the Electrical Box to ensure strain relief. When…
-
4.3 Setting the DIP switches for the outdoor unit
4.3.1 Quantity and position of DIP switches The PCB in the outdoor unit is operating with DIP switches and push switches. The location is as follows: RAS-(2/2.5)HVNP / RAS-3HVNC PCB2 PCB1 RAS-(3-12)H(V)N(P/C)(E) 92 SMGB0079 rev.0 - 01/2013
-
4.3.2 Function of the of DIP switches and RSW switches
NOTE • The mark “■” indicates the position of dips switches. • No mark “■” indicates pin position is not affecting. • The figures show the settings before shipment or after selection. DANGER Before setting dips switches, first turn the power source off and then set the position of the dips switches.…
-
DSW2: Pipe length setting (setting is required) / Optional function setting
-
DSW4 / RSW1: Refrigerant cycle number setting (Setting is required)
In case of using an H-Link II net it is required to set the refrigerant cycle number. ON Setting for the ten digit (Factory setting) Setting position. Set by inserting slotted screwdriver into the groove (setting for the last digit) Rotary switche’s positions (RSW1) are set by inserting a screw…
-
end terminal resistance setting
Outdoor Unit Outdoor Unit Outdoor Unit Outdoor Unit DSW5 DSW5 DSW5 DSW5 Control Wiring (H-LINK II or H-LINK) Indoor Unit Control Wiring (H-LINK II or H-LINK) Control Wiring (H-LINK II or H-LINK) Indoor Unit Indoor Unit Indoor Unit DSW6: Setting of multiple indoor units operation (setting is…
-
4.3.3 Jumpers
Jumper lead setting (JP1~6) Setting before shipment: System JP1 JP2 JP3 JP4 JP5 JP6 Single phase (1~) Three-phase (3N~) NOTE • 0: Open • 1: Short circuit The function selection using the jumper lead setting is shown in the tables below: RAS-(2-2.5)HVNP / RAS-3HVNC Setting Function Details JP1 Not…
-
4.4 Common wiring
4.4.1 Electrical wiring between outdoor and indoor unit • Connect the electrical wires between the indoor unit and the outdoor unit as show in the figure. • When installing the electrical wiring, follow local codes and regulations. • The refrigerant piping and the control wiring are connected to the…
-
4.4.2 Wire size
Connection wiring Recommended minimum sizes for field provided wires: Model Power supply All Indoor Units 1~ 230V 50HZ Power source cable size Transmitting cable size EN60 335-1 EN60 335-1 0.75 mm² 0.75 mm² IVX Premium Series RAS-2HVNP 2.5 mm² RAS-2.5HVNP RAS-3HVNPE RAS-4HVNPE 4.0 mm2 1~ 230V…
-
Main switch protection
Select the main switches in according to the next table: Model All Indoor Units Power supply Max. current (A) CB (A) ELB (no. poles/A/mA) 1~ 230V 50Hz 5.0 6 2/40/30 ELB: Earth switch; CB: Circuit braker IVX Premium series Outdoor unit MC (A) CB (A) RAS-2HVNP 12.0 16 RAS-2.5HVNP 14.0 20 RAS-3HVNPE…
-
The H-LINK II is the wiring connection system between units. The H-LINK II wiring system only needs: • Two transmission wires connecting each indoor and outdoor unit for a total of 64 refrigerant cycles. • Connection wiring for all indoor and outdoor units in series. CAUTION The H-LINK II system…
-
4.5.3 DIP Switch setting for twin, triple and quad systems
Dip switch of indoor PCB and outdoor H-LINK II The DIP switches of all the indoor and outdoor units have to be set and the impedance of the transmission circuit adapted. • Example of the setting of the DIP switches. A D E F G H E F I J A: Cycle No. 0. B: Cycle No. 1. C: Cycle No. 2. D: Terminal…
-
Unit
Name of DIP switch Mark Setting before the Shipment Function DSW4 RSW1 For setting the refrigerant cycle address of the outdoor unit. Set the DSW4 and RSW1 to overlap the setting of other outdoor units in the same H-LINK system. Resistance of terminal DSW5 To adapt the impedance of the transmission…
-
Two cases: 1. Using H-LINK II system for air conditioning systems without a central control device (CSNET WEB or PSCA64S). • Line connection with all units (including Utopia and/or Set Free, Mini Set Free and DC Inverter). A B C A: Outdoor units. B: Indoor units. C: Do not install wiring in a loop.…
-
Connection with one main line and with the branch lines for the units. A A: Outdoor units. B: Indoor units. CAUTION • The maximum number of units than can be connected is 64 outdoor units and 160 indoor units (including Utopia and/or Set Free, Mini Set-free). • Do not install the wiring in a loop. •…
-
4.6 System Control
4.6.1 Individual Operation Control Wiring (H-LINK II) Indoor Unit Outdoor Unit DSW6 ON OFF 1 2 Dip Switch 6 setting is NOT required. ( The factory setting position is for the individual operation.) Remote Control Switch (PC-ARF) Individual Thermo ON/OFF Operation The individual Thermo ON/OFF is…
-
4.6.2 Simultaneous Operation
This unit can be operated simultaneously with twin, triple and quad combinations. One remote control switch (PC-ARF) can control without transition wiring up to 4 units of FSN2 series or later model types (H-LINK II supported models) simultaneously (Available if it is with the transition wiring.)…
-
4.7 Electrical wiring diagrams
317S139290 / 317S139291 /317S139294 108 SMGB0079 rev.0 - 01/2013 RAS-2.5HVNP RAS-3HVNC RAS-2HVNP 4.7.1 RAS-(2-2.5)HVNP / RAS-3HVNC (1~ 230V 50Hz)
-
W Surface
4.7.2 RAS-3HVNPE (1~ 230V 50Hz) U Surface V Surface 4 XEK01261_0 109 SMGB0079 rev.0 - 01/2013
-
U Surface
V Surface W Surface 4.7.3 RAS-(4-6)HVNPE (1~ 230V 50Hz) XEK01262_0 110 SMGB0079 rev.0 - 01/2013
-
таблицы и схемы — в просмотре
-
W Surfac
-
W Surface
-
XEK01288_0 114 SMGB0079 rev.0 - 01/2013
-
4 317S136064 115 SMGB0079 rev.0 - 01/2013
-
317S136071 116 SMGB0079 rev.0 - 01/2013
-
5.1 Device control system
Purpose Control subject Control frequency of inverter compressor Opening degree expansion valve of outdoor unit Cooling operation Heating operation The frequency control is determined with the next parameters: The frequency control is determined with the next parameters: • Ratio (I.U. capacity/O.U.…
-
The figure below shows the outline of the control system
Multiple signals Wireless remote control switch Thermistor for inlet air Transmission circuit Remote control MCU Single signals Suction gas pressure sensor Thermistor of discharge air Discharge gas pressure sensor Thermistor for gas pipe Thermistor for liquid pipe Operation signals Thermistor for…
-
5.2 Outdoor units PCB
5.2.1 RAS-(2-2.5)HVNP / RAS-3HVNC PCB1 PCB2 PCB1 Connector indication Connector Name PCB1 LED indication LED Colour Name PCN5 Crankcase heater of compressor (oil) LED1 Red Power source for the PCB PCN6 Reversing valve relay PCN13 Pressure switch control LED2 Green This LED indicates the transmission…
-
5.2.2 RAS-3HVNPE
5 Connector indication Switch indication PCN1 Fuse DSW1 Test run PCN5 Crankcase heater of compressor (oil) DSW2 Auxiliary function setting PCN8 High pressure switch protection DSW3 Capacity code PCN9 Compressor contactor PCN10 Low pressure switch protection DSW4/ RSW1 Refrigerant cycle number PCN14…
-
Connector indication Switch indication PCN1 Fuse DSW1 Test run PCN5 Crankcase heater of compressor (oil) DSW2 Auxiliary function setting PCN7 Solenoid valve DSW3 Capacity code PCN8 High pressure switch protection PCN9 Compressor contactor DSW4/ RSW1 Refrigerant cycle number PCN10 Low pressure switch…
-
5 Connector indication Switch indication PCN1 Fuse DSW1 Test run PCN5 Crankcase heater of compressor (oil) DSW2 Auxiliary function setting PCN6 4-way solenoid valve DSW3 Capacity code PCN7 Solenoid valve PCN8 High pressure switch protection DSW4/ RSW1 Refrigerant cycle number PCN9 Compressor…
-
PCB1 PCB3 PCB1 Connector indication Connector Name PCB1 Switch indication Connector Name PCN1 Fuse DSW1 Test run PCN5 Crankcase heater of compressor (oil) DSW2 Auxiliary function setting PCN7 Solenoid valve DSW3 Capacity code PCN8 High pressure switch protection PCN9 Compressor contactor DSW4/ RSW1…
-
5.2.6 RAS-12HNP - Preliminary data
5 Connector indication Switch indication PCN1 Fuse DSW1 Test run PCN5 Crankcase heater of compressor (oil) DSW2 Auxiliary function setting PCN7 Solenoid valve DSW3 Capacity code PCN8 High pressure switch protection PCN9 Compressor contactor DSW4/ RSW1 Refrigerant cycle number PCN10 Low pressure…
-
5.2.7 RAS-12HNC - Preliminary data
Connector indication Switch indication PCN1 Fuse DSW1 Test run PCN5 Crankcase heater of compressor (oil) DSW2 Auxiliary function setting PCN6 4-way solenoid valve DSW3 Capacity code PCN7 Solenoid valve PCN8 High pressure switch protection DSW4/ RSW1 Refrigerant cycle number PCN9 Compressor contactor…
-
5.3 Protection and safety control
Compressor protection The following devices and their combinations protect the compressor High-pressure switch This switch cuts out the operation of the compressor when the discharge pressure exceeds the setting. Oil heater This band heater protects against the oil carry-over during the cold…
-
5.4 Standard operation sequence
-
(for RAS-(2-2.5)HVNP<60ºC)
-
5.4.2 Dry operation
Continues in the next page. 130 SMGB0079 rev.0 - 01/2013
-
(for RAS-(2-2.5)HVNP<60ºC)
-
5.4.3 Heating operation
-
(for RAS-(2-2.5)HVNP<60ºC)
RAS-3HVNC Td target temp. -10ºC (for RAS-(2-2.5)HVNP 60ºC) RAS-3HVNC Power to Y52C or RY1 : ON IU Air outlet temperature Higher than 50ºC HEAT 133 SMGB0079 rev.0 - 01/2013 5
-
5.4.4 Automatic cooling and heating operation
134 SMGB0079 rev.0 - 01/2013
-
5.4.5 Defrost operation control
Power to YH2:ON RAS-(2-2.5)HVNP / RAS-3HVNC * DSW2-1 ON (and DSW2-2ON for RAS-2.5HVNP) After 30 seconds N 5 Other than above IU demand frequency <90Hz 90Hz Power to YH2:ON 135 SMGB0079 rev.0 - 01/2013 After 90 seconds * Power to YH2:OFF
-
Defrosting Operation
The following defrosting operations, “Standard Defrost”, “Forced Defrost” and “Manual Defrost” are available. 1 Standard Defrost This operation is started according to the outdoor temperature, the outdoor evaporating temperature and operating time. 2 Forced Defrost This operation starts when the…
-
NOTE
For RAS-(2-2.5)HVNP / RAS-3HVNC: • (*1) More than 39 minutes. • (*2) If outdoor temperature is less than -6ºC then the compressor is operated continuously for more than 2 minutes. If outdoor temperature is more than -6ºC then the compressor is operated continuously for more than 9 minutes. • (*3)…
-
5.5 Standard control functions
5.5.1 Freezing protection during cooling process or dry operation Cooling or Dry Operation Cooling or Dry Operation 138 SMGB0079 rev.0 - 01/2013
-
5.5.2 Prevention Control for High Pressure Increase during Cooling Operation
This function is performed to prevent the abnormal condition (Alarm Code: 02) when the air flow volume is decreased by a seasonal wind against air outlet of the outdoor unit. When the following conditions are met, the forced Thermo-OFF operation will be performed. The cause of stoppage will be 13…
-
5.5.3 Prevention control for excessively high discharge gas temperature
-
5.5.4 Activation for protection device control
N Current of the EHW circuit > 10A or >20A Blow EHW fuse 141 SMGB0079 rev.0 - 01/2013 N 5
-
5.5.5 Preheating control of compressor
RAS-(2-2.5)HVNP / RAS-3HVNC During stopping and operating compressor Other than above During stopping compressor 142 SMGB0079 rev.0 - 01/2013 During operating compressor
-
5.5.6 Prevention control for high pressure increase
This function is performed to prevent the abnormal condition (Alarm: 02) when the outdoor air flow is decreased by a seasonal wind against air outlet. When the CMC is ON during cooling operation, PSC is ON and Tc is higher than Tc1+4 °C, forced thermo-off operation will be performed. Tc: Outdoor…
-
6.1 Optional input and output signals (By 7-segment display)
The system has several input and output signals, which can be selected using the following connectors of the outdoor unit’s PCB: Input connectors CN1 and CN2, which have two and one ports respectively to configure three optional input signals. Output connector CN1, which has two ports to configure…
-
Specification of the components for a correct installation
Component Manufacturer or specifications Remarks Auxiliary relay (X3) OMRON mini power relay model: MY1F or equivalent Voltage between relay terminals 12 Vdc - 75 mA (SS1) (x1), (x2) contact example Manual type Voltage between terminals of the 230V - 5 mA contactor 3P connector cable Optional…
-
6.1.2 Available optional signals
The outdoor units have the following signals that are described in the following table. These signals are set up through the PCB of the outdoor unit. RAS-(2-2.5)HVNP / RAS-3HVNC Input signals Ind. Input signal 0 No setting application No setting Application Port 1 Fixing the heating mode This…
-
Input signals Ind. Input signal 0 No setting application No setting 1 Fixing the heating mode This signal allows to pre-fix the operation mode, in this case the heating mode, independently of what the indoor unit requests. If the indoor units request the oposite mode than the outdoor unit, the…
-
6.1.3 Setting of the optional signals
The optional signals of the outdoor unit are set up from the PCB of the outdoor unit and can be selected by pushing switches PSW1, PSW2 and PSW3. Input setting 1 CN1, 1-2 1 1 Factory setting PSW1 SET* PSW2 PSW3 NOTE 0 ~ 10 Before setting the optional signals, must be complied the following…
-
6.1.4 Description of optional signals
Input signals RAS-(2-2.5)HVNP / RAS-3HVNC 1 Fixing operation mode (heating / cooling)(1/2) This input function is fixed in terminals CN1 or CN2 of the PCB of the outdoor unit, to use it as a cooling and heating mode. CN1 must be set up as follows. Short circuit between the terminals 1 and 2 of…
-
1 Fixing operation mode (heating / cooling)(1/2) This input function is fixed in terminals CN1 or CN2 of the PCB of the outdoor unit, to use it as a cooling and heating mode. CN1 must be set up as follows. Short circuit between the terminals 1 and 2 of CN1: set heating mode. Short circuit between…
-
Output signals
Operation signal (01) This optional signal is used to pick up the operation signal. It can be used to turn on or off complementary units of the airconditioning system,such as fans, humidifiers, etc. Connect the cabling and use the materials as shown in Available ports. Note that the contact of…
-
6.2 Optional functions (By 7-segment display)
The outdoor unit has several optional functions which can be selected through the 7-segment display of the outdoor unit PCB. 6.2.1 Setting of the optional functions The optional functions of the outdoor unit are set up from the PCB of the outdoor unit and can be selected by pushing switches PSW1…
-
IVX Premium
↓ SEG2 Control of the indoor unit fan during ThermoOFF in heating mode Cancelation of outdoor ambient temperature limit of heating Change of defrost condicion Slo defrost setting Cancellation of outdoor hot start limit (12HP) Capacity adjustment for long piping (for 3 to 12HP) Compressor frequency…
-
IVX Standard
↓ SEG2 Control of the indoor unit fan during ThermoOFF in heating mode Cancelation of outdoor ambient temperature limit of heating Change of defrost condicion Slo defrost setting Cancellation of outdoor hot start limit (12HP) ni 1 0 Available Available G5 1 0 Jo 1~3 0 Available bJ 1 0 Available nU…
-
6.2.2 Description of the optional functions
Control of the indoor unit fan during Thermo-OFF in heating mode (FA) Press PSW1 and select the setting condition “1” at the circulator function at heating thermo-OFF “FA”. In case that the fan speed is changed to “LOW” at heating Thermo-OFF, there is a case that the room air temperature is too high…
-
Cancellation of Outdoor Ambient Temperature Limit (GS)
Press “PSW1” and select the setting condition “0” to “3” at the cancellation of outdoor ambient temperature limit of “GS”. Then, this function can be set. The heating operation is continued under a high outdoor temperature or the cooling operation is continued under a low temperature. Setting…
-
Slo defrost setting (bJ)
Press “PSW1” and select the setting condition “1” at the slow defrost setting “bJ“. Indoor fan operation is stopped during the defrost operation. Setting condition* Indoor fan operation 0 Indoor fan stop during defrost operation 1 Indoor fan SLo during defrost operation Cancellation of outdoor hot…
-
Fixing on demand function (dE)
Press “PSW1” and select the setting condition “1”, so that the fixing of demand function “dE” can be set. However, it is not necessary to short-circuit the demand input terminals on the outdoor unit PCB. (Refer to section Description of optional signals in the input Current control demand) The…
-
6.3 Optional functions (By remote control switch)
Additionally to the possible optional functions by the 7-segment display of the outdoor unit’s PCB, there are available a large quantity of optional functions for each remote control switch connected to the system. An example of the available optional functions by one of the HITACHI remote control…
-
Optional function
Individual setting Setting condition “- -” Fixed Not used 00 Not used 01 (Use as 00 conditions) 00 Not used 01 (Use as 00 conditions) 00 Average static pressure (factory set) 01 High static pressure 02 Low static pressure 00 Normal 01 Speed increase 1 02 Speed increase 2 00 Not available 01…
-
Optional function
Individual setting KPI: Ventilation mode E1 ○ Econofresh: all fresh mode KPI: Increasing air supply volume E2 ○ Econofresh: Enthalpy sensor E3 Not prepared ○ KPI: Pre-cooling / Pre-Heating period E4 ○ Econofresh: gas sensor E5 Not Prepared E6 Indoor fan operation time after cooling operation…
-
F1
Optional function Automatic timer OFF setting Individual setting × F2 Main and secondary remote control setting × F3 Automatic temperature setting release (*3) × F4 Automatic release time × Setting condition 00 Function not valid 01 1h 02 2h 03 3h 04-24 (04-24) h 0A 0.5 h 0B 1.5 h 0C 40 mins 0D 45…
-
FC
Fd FE Optional function Cooling lower limit for setting temperature (*4) Heating upper limit for setting temperature (*5) Not prepared Individual setting × × - Setting condition 00 Standard 01 Lower limit +1ºC 02 Lower limit +2ºC 09 Lower limit +9ºC 10 Lower limit +10ºC 00 Standard 01 Upper limit…
-
Optional function
Individual setting JA Not prepared - Jb Not prepared - K1 Not prepared x K2 Not prepared x K3 Not prepared x K4 K5 Not prepared - Motion sensor detection level - Setting condition Contents 00 Not available 01 (Use as 00 condition) 00 Not available 01 (Use as 00 condition) 00 Not available 01 (Use as…
-
7.1 Checking procedure before the test run
When you have finished the installation, perform the test run according to the following procedure. After performing the test run, hand over the system to the customer. Perform the test run of the indoor units one by one in order. Make sure that the electrical wiring and the refrigerant piping are…
-
Check to ensure the operating temperature: Cooling operation: Indoor DB 21.5 ºC and above, Indoor WB 16 ºC and above, Outdoor DB 0 ºC and above Heating operation: Indoor DB 27 ºC and below. (*) About insulation resistance • The insulation may lower during a test run or after being left…
-
7.2 Test run procedure using the remote control switch (PC-ART)
Turn ON the power source of the units Procedure for TEST RUN mode of remote control switch. Depress the MODE and the than 3 seconds. Operation lamp OK switches together for more Counting number of connected units a. If TEST RUN and the counting number of the connected units to the remote control…
-
Remote control switch
indication Unit condition Inspection points after power source OFF Wrong portions 1 2 The operation lamp flickers. (1 time/1 sec.) and the unit number and alarm code 03 flicker. The unit does not start. The power source of outdoor unit in not turned ON. The connecting wires of operating line are…
-
7.3 Test run procedure using the remote control switch (PC-ARF)
Display Part Schedule Timer Indicator Fan Speed Indicator It is indicated when the schedule timer Swing Louver Indicator Room Name Indicator function is set. Operation Lock Indicator Operation Mode Indicator It is indicated when the operation lock function is set. The indications of “HEAT” and…
-
Test Run Setting: 2 units
b. Select “Test Run” and press “OK”. The test run settings will be displayed. COOL MED MODE SPEED LOUV. T-RUN TIME 120MIN SEL. ADJ RUN RTN. Test Run Setting: 00 unit When “00” is indicated, the auto-address function may be performing. Cancel “Test Run” mode and set it again. 4 COOL MED MODE SPEED…
-
Test Run: 2 units
9 To finish the test run, press “ ” (run/stop) again or pass over the set test run time. When changing the test run time, press “ ” or “ ” to select “T-RUN TIME”. Then, set the test run time (30 to 600 minutes) by pressing “ ” or “ ” LOUV. T-RUN TIME SEL. The RUN indicator on the remote control…
-
7.4 Test run procedure using the wireless remote control switch (PC-LH3A/B)
NOTE If the wired remote control switch is used or if multiple units (SET-FREE, DC INVERTER and utopia series) are operating simultaneously, you cannot perform the test run by means of the remote control switch. If that is the case, perform the test run by means of the wired remote control switch.…
-
c. Alarm code display
If some malfunction occurs because of the activation of a safety device or any other reason, the red RUN LED blinks (0.5 seconds ON / 0.5 seconds OFF). Refer to section Alarm codes on chapter Troubleshooting. The alarm code displays the number of blinks of the green DEF LED and the yellow FILTER LED…
-
7.5 Test run procedure from the outdoor unit side
The test run procedure from the outdoor unit side is shown below. You can set this DIP switch while the power source is ON. Setting of dip switch DSW1 Test Run COOL/HEAT (Setting ON: Heat Operation) COOL / HEAT intermediate season Manual Compressor stop DANGER • Do not touch any other electrical…
-
Manual
Defrost Manual Defrost Operation Defrost operation is available regar- • dless of frosting condition and total time Starts of heating operation. Press PSW1 for more than 3 seconds during heating operation, Defrost operation in not performed the defrost operation is started when the temperature…
-
7.6 Check list
-
21 Does the drain water flow smoothly from the drain pipe? __________
7.6.2 Check list on compressor CLIENT: MODEL: DATE: Serial N°: Production date: Checker: N° 1 Check item Is THM9 correctly connected? THM9: Discharge gas thermistor Check method (1) Is wire of thermistor correctly connected by viewing? (2) Check to ensure the 7-segment indication of Td when comp. is…
-
Additional information for “Check list on compressor”
Check item Additional information (mechanism of compressor failure) 1&2 The liquid refrigerant return volume to the compressor is controlled by the discharge gas temperature Td when compressor is operating. If Td thermistor is disconnected, the liquid refrigerant return volume will become small by…
-
8.1 Initial troubleshooting
8.1.1 Checking by means of the 7-segment display Simple checking procedure by means of the 7-segment display Turn on all the indoor units which are connected to the outdoor unit. Turn on the outdoor unit Auto-addressing starts. (Outdoor unit printed circuit board PCB1). During the auto-addressing…
-
8.1.2 Failure of the power supply to the indoor unit and the remote control switch
• The LED and the LCD are not indicated. • Not operated If the fuses are blown out or a breaker is activated, investigate the cause of the overcurrent and take the necessary action. Check item Action (Turn OFF the main switch) Measure the voltage by means of the voltmeter Supply the power Short…
-
8.1.3 Abnormal transmission between the remote control switch and the indoor unit
• RUN LED on the remote control switch: Flickering every 2 seconds. Check item Action (Turn OFF the main switch) Disconnection or insufficient contacting of the remote control cable Check the cable and the connections Repair the cable or connect the cable Failure of the remote control switch Check…
-
Cause
Failure of air inlet thermistor Check item Action (Turn OFF the main switch) Check it by self-checking *2) Replace or correctly connect the wires if Abnormal Operation exists Check PCB by means of the self-check mode *1) Replace PCB if it failed Failure of thermistor Disconnection of thermistor…
-
Cause
Check item Action (Turn OFF the main switch) Indoor cool load is greater than the cooling capacity Calculate the cool load Use a bigger unit Gas leakage or shortage of refrigerant Measure superheat Correctly charge the refrigerant after repairing the gas leakage Excessively small diameter tube or…
-
Check item
Action (Turn OFF the main switch) Clogging of the outdoor unit heat exchanger? Remove the clogging Obstacles at the inlet or the outlet of the outdoor unit heat exchanger Remove the obstacles Is the service area for the outdoor unit sufficient? Secure the service area Correct fan speed? Replace the…
-
Cause
Check item Action (Turn OFF the main switch) Indoor heat load is greater than the heating capacity Calculate the heat load Replace the unit with a bigger unit Gas leakage or insufficient refrigerant charge Measure superheat Correctly charge the refrigerant after the gas leakage check and repairing…
-
Cause
Check item Action (Turn OFF the main switch) Foreign particles inside of the fan casing Visually inspect it Remove the foreign particles Indoor unit fan runner is hitting the casing Visually inspect it Adjust the position of the fan runner Outdoor unit propeller fan is hitting the shroud Visually…
-
8.2 Troubleshooting procedure
8.2.1 Alarm display On-screen displays during abnormal operation • Malfunction The RUN (red) indicator flashes.The ALARM indicator appears on the liquid crystal display.The screen also displays the indoor unit number -A-, the alarm code -B- and the model code -C-. If there are various indoor units…
-
8.2.2 Alarm codes for the outdoor and indoor units
Code No. Category 01 Indoor unit Activation of protection device (float switch) Failure of fan motor, drain discharge, PCB, relay, float switch activated. 02 Outdoor unit Activation of protection device (high pressure cut) Activation of PSH, locked motor, abnormal operation in the power supply…
-
8.2.3 Troubleshooting by alarm code for the outdoor and indoor units
Alarm code 01 Activation of the safety device in the indoor unit • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. • The unit number and the alarm code are…
-
Activation of the safety device (high pressure switch) in the outdoor unit (Except Alarm codes 41 and 42) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The…
-
Cause
Remove the dust or the clogging Remove the dust Remove the obstacles Check the service area Secure service area Check the speed (Outdoor Fan: Cooling / Indoor Fan: Heating) Replace the fan motor if faulty Calculate the heat load Reduce the heat load or use a bigger unit Check for hot air near the…
-
Abnormal transmission between the indoor units and the outdoor unit for RAS-(2-2.5)HVNP / RAS-3HVNC • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. • The unit…
-
SMGB0079 rev.0 - 01/2013
-
Cause
Blown out fuse for control circuit or activation of outdoor unit breaker Supply the power Short-circuit between the wires Check the insulation material for breaks Remove the short-circuit and replace the fuse Short-circuited wire to ground Measure the insulation resistance Remove short-circuit to…
-
Abnormal transmission between the indoor units and the outdoor unit for RAS-(3-12)H(V)N(P/C)(E) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. • The unit…
-
201 SMGB0079 rev.0 - 01/2013
-
Disconnected Wire
Insufficient Contacting Check continuity and looseness of connection screws. Replacing Wires, Repairing and Tightening Screws Incorrect Wiring Check terminal Nos. Correctly connect wires. Incorrect Wiring 202 SMGB0079 rev.0 - 01/2013
-
NOTE
• *1) In the case that the end terminal resistance (DSW5-1) is set to OFF for H-LINK connection, set the end terminal resistance to ON when CN8 is disconnected. Set the end terminal resistance to OFF when CN8 is reconnected. • *2) Transmission Setting (SW1) • Item Setting Position SW1 Left Side (for…
-
Abnormal transmission between Inverter PCB and Outdoor PCB1 • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed on…
-
8 NOTE • *1): Surely perform the troubleshooting of the resistance for inrush current prevention (R115/R116) on inverter PCB. If the resistance for inrush current prevention (R115/R116) fails, the abnormal transmitting occurs. • *2): Surely perform the troubleshooting of DC fan motor according to…
-
NOTE Surely perform the troubleshooting of DC fan motor according to section Procedure of checking other main parts. If the DC fan motor fails, the normal inverter PCB may be damaged. 206 SMGB0079 rev.0 - 01/2013
-
Alarm code Code abnormal operation of picking up phase signal • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed…
-
Excessively low voltage or excessively high voltage for the inverter • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. • The unit number and the alarm code are…
-
8 NOTE • The indicated voltage is for three phase models. The power supply voltage for single phase models is 220V and 187V during operation. • *1): If capacitor has high voltage, perform the high voltage discharge work refer to the item Procedure of checking other main parts. • *2): Regarding…
-
Decrease of Discharge Gas Superheat • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed on the display of the…
-
Cause
Check item Action (Turn OFF the main switch) Ref. cycle is different from the electrical system Check ref. cycle and the electrical system Repair wiring Overcharged Refrigerant Measure pressure Correctly charge refrigerant Faulty Expansion Valve Check expansion valve *1) Replace expansion valve if…
-
Excessively High Discharge Gas Temperature at the Top of Compressor • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are…
-
Abnormal operation of thermistor for the indoor unit air inlet temperature (air inlet thermistor) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit…
-
Abnormal operation of the thermistor for the indoor discharge air temperature (air outlet thermistor) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit…
-
Abnormal operation of the thermistor for the indoor unit heat exchanger liquid pipe temperature (freeze protection thermistor) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set…
-
Abnormal operation of the thermistor for the indoor unit heat exchanger gas pipe temperature (gas piping thermistor) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature…
-
Activation of the protection device for the indoor fan motor (except RCI, RCIM and RPK) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the…
-
Activation of the protection device for the indoor fan motor (RCI, RCIM) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. • The unit number and the alarm code…
-
Activation of the protection device for the indoor fan motor (RPK) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are…
-
Abnormality of Thermistor for Discharge Gas Temperature (Compressor Thermistor) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm…
-
Abnormality of High pressure sensor for RAS-(3-12)H(V)NP(E) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed on…
-
Abnormal operation of the thermistor for the outdoor temperature (outdoor unit ambient thermistor) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit…
-
Abnormal operation of the thermistor for the evaporating temperature during the heating process (outdoor unit) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.…
-
Alarm code Incorrect Capacity Setting or Combined Capacity between Indoor Units and Outdoor Unit • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number…
-
Incorrect Indoor number setting • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, alarm code and unit model code appear alternately on the Set Temperature display of the remote control switch. The alarm code also appears on the outdoor unit PCB display.…
-
• 38 Abnormality of Protective Circuit for Protection (Outdoor Unit) The RUN LED flickers and “ALARM” is displayed on the remote control switch. The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are…
-
Alarm code Cooling Overload (High pressure switch will be activated) for RAS-(2-2.5)HVNP and RAS-3HVNC • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit…
-
Cause
Insufficient Air Flow to Heat Exchanger of Outdoor Unit Check item Action (Turn OFF main switch) Clogging of Heat Exchanger? Remover clogging Check for dust on air filter Remove dust Check the service space Check for outdoor fan speed Excessively High Temp. Air to Outdoor Unit Heat Exchanger Faulty…
-
Alarm code • • Heating Overload (High pressure switch will be activated) for RAS-(2-2.5)HVNP and RAS-3HVNC The RUN LED flickers and “ALARM” is displayed on the remote control switch. The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit…
-
Cause
Check item Action (Turn OFF Main Switch) Clogging of Heat Exchanger Activation of High Pressure Switch due to Excessively High Discharge Pressure during Heating Operation Check for dust on air filter Insufficient Air Flow to Heat Exchanger of Indoor Unit Check the service space Excessively High…
-
Activation of high pressure increase protection device • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed on the…
-
Activation to Protect System from Excessively Low Suction Pressure (Protection from Vacuum Operation) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit…
-
Overcurrent protection activation for RAS-(2-2.5)HVNP and RAS-3HVNC 8 233 SMGB0079 rev.0 - 01/2013
-
Restart operation. Does it trip soon? Yes It trips immediately It trips after a certain period Overcurrent protection activation for RAS-(3-12)H(V)N(P/C)(E) Turn OFF power and disconnect U, V, W from compressor terminals. Turn ON #1 of DSW1 on PCB2 (IPM or dipIPM) and restart. Does it trip? *1) No…
-
Abnormal operation of the current sensor (RAS-(2-2.5)HVNP / RAS-3HVNC) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are…
-
Abnormal operation of the current sensor (RAS-(3-6)H(V)N(P/C)E) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed…
-
Abnormal operation of the current sensor (RAS-(8-12)HN(P/C)(E)) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed…
-
Activation of transistor module (RAS-(2-2.5)HVNP / RAS-3HVNC) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed…
-
Alarm code Activation of transistor module (RAS-3HVNPE / RAS-(4-6)H(V)NCE) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code…
-
Activation of transistor module (RAS-(4-6)H(V)NPE) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed on the…
-
Compressor
stops immediately. (Itc=1, 12)* Turn OFF power, disconnect U, V, W from compressor Restart operation. terminals and restart. Does the protecting Compressor function activate? *3) stops after few minutes. Yes It trips. (Itc=1) (Itc=21)* Is heat exchanger clogged? No Normal Check the compressor.…
-
Activation of transistor module (RAS-(8-12)HN(P/C)(E)) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed on the…
-
Are the power wires
passed through CT(inverter element)? Check transistor module (*1) (*2) Pass the power wires through CT Check inverter PCB Replace transistor and inverter Replace transistor module Is the space between the transistor module and radiation fins entirely covered by silicon? Apply silicon to cover…
-
Abnormality of inverter fin temperature (RAS-3HVNPE / RAS-(4-6)H(V)N(P/C)E) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code…
-
Alarm code Abnormality of inverter fin temperature (RAS-(8-12)HN(P/C)(E)) • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are…
-
Abnormality of Inverter Module • The RUN LED flickers and “ALARM” is displayed on the remote control switch. • The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed on the display of the outdoor…
-
• 57 Abnormality of fan motor protection (DC fan motor) for RAS-(2-2.5)HVNP and RAS-3HVNC The RUN LED flickers and “ALARM” is displayed on the remote control switch. The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the…
-
Alarm code • • Abnormality of fan motor protection (DC fan motor) for RAS-(3-6)H(V)NPE and RAS-(8-12)HN(P/C)(E) The RUN LED flickers and “ALARM” is displayed on the remote control switch. The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The…
-
Alarm code • • Abnormality of fan motor protection (DC fan motor) for RAS-(4-6)H(V)NCE The RUN LED flickers and “ALARM” is displayed on the remote control switch. The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm…
-
EE Compressor protection This alarm code is displayed when one of the following alarms occurs three times within six hours. If the outdoor unit operates continuously without removing the cause of the alarm, the compressor may be seriously damaged Alarm code Content of abnormality 02 Tripping of…
-
• b1 Incorrect Setting of Unit and Refrigerant Cycle No. The RUN LED flickers and “ALARM” is displayed on the remote control switch. The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit number and the alarm code are displayed on the…
-
8.2.4 Alarm codes for the KPI (E/H/X)3E Series and DX Interface
Code No. DXKIT2 KPIS3 KPIActive Category 01 o - o Indoor 03 o - o Transmission Type of Abnormality Main cause Activation of protection device Float switch activation (high water level in drain hose or abnormality in drain pipe, float switch or drain pan). Transmission Error Outdoor fuse meltdown…
-
8.3 Troubleshooting in check mode
8.3.1 Troubleshooting using the remote controller PC-ART Use the “OK” switch of the remote control in the following cases: 1 When the RUN LED is flickering. 2 To trace back the cause of the malfunction after restarting from the stoppage while the RUN LED is flickering. 3 To check during the normal…
-
Although the wireless controller is used for the wall type indoor unit with the built-in receiver part, you can check the alarm code by connecting the PC-P2HTE. Suction grille Connector for check NOTE • The unit does not operate by pressing the operation switch. • The above function is available…
-
Indication of micro-computer input/output
12 Micro-computer input/output in indoor unit C1 Heating Thermo-ON Alarm Cooling Thermo-ON Dark 13 Micro-computer input/output in outdoor unit H2 C2 - 52H Dark Y52C2 Y212 Y211 Y52C1 Y20B Y20A Outdoor fan Indication of unit stoppage cause d1 01 14 Cause of stoppage 00 Operation OFF, power OFF 01…
-
Abnormal operation occurrence counter
15 16 Abnormal operation occurrence counter E1 01 Instantaneous power failure occurrence counter in indoor unit E2 00 Transmission error occurrence 17 counter between remote control switch and indoor unit E3 00 Abnormal operation occurrence counter on inverter E4 00 18 Countable up to 99. Over 99…
-
Expansion opening indication
28 Indoor unit expansion valve opening (%) L 20 29 Outdoor unit expansion valve MV1 opening (%) L2 gg 30 Outdoor unit expansion valve MV2 opening (%) L3 gg In case of models without the expansion valve (MV2), the same figure is displayed L4 00 31 Control information Estimated electric current…
-
Contents of the check mode 2
When more than three indoor units are connected to one remote control switch, the latest data of only the first three indoor units that are connected serially are displayed. If you press the part “” of the TEMP switch, the next display appears. If you press the part “” of the TEMP switch, the…
-
Self-checking procedure of PCB by means of the Remote Control Switch
Use the following troubleshooting procedure for testing the PCB in the indoor unit and the outdoor unit: Press (ex.) Indication of unit No. “0” Indication of unit number After 7 seconds Operating PCB check automatic Indication Contents Normal Abnormality (open-circuit, short-circuit, etc.) in…
-
If you are using a wireless remote control switch with the built-in receiver part of the wall-type indoor unit and you need to perform the above checking, perform the following procedure: Turn OFF the power supply. Disconnect the connector (CN25) on PWB(M). Connect the PC-ART. Turn ON the power…
-
Self-checking procedure of the remote control switch
Cases where the OK switch is used: 1 2 If the remote control switch displays a malfunction. For the regular maintenance check. Turn ON the power source No. Simultaneously press the following three switches. (During the operation, you can press the switches.) LCD indication 1 1 The LCD changes as…
-
The LCD changes as shown below
The detected temperature of the remote control thermostat is displayed at the (A) part in the figure below. 7 The LCD changes as shown below. If the indicators “--” or “FF” are displayed at the “A” part, the remote control thermostat is abnormal. If you press the RESET switch or you leave the…
-
8.3.2 Troubleshooting using the remote controller PC-ARF
Each “Check Menu” item and its function are explained in the following table. Check Menu Item Function Check 1 Sensor condition of air conditioner will be monitored and indicated. Check 2 Sensor data of air conditioner prior to alarm occurrence will be indicated. Alarm History Display Previous alarm…
-
Check mode 1 items
No. Item 1 b1 2 Data Name No. Item Data Name Set Temp. 18 E3 Times of Abnormal Transmitting b2 Inlet Air Temp. 19 E4 Times of Inverter Tripping 3 b3 Discharge Air Temp. 20 F1 Louver Sensor State 4 b4 Liquid Pipe Temp. 21 H1 Discharge Pressure 5 b5 Remote Thermistor Temp. 22 H2 Suction Pressure 6 b6…
-
Checking procedure of PCB by means of the Remote Control Switch
(1) Press and hold “ ” (menu) and “?” (help) simultaneously for 3 seconds during the normal mode. The check menu is displayed. Check Menu I. U./O. U. PCB Check Self Checking 02 / 02 (2) Select “I.U./O.U. PCB Check” from the check menu and press “OK”. SEL. OK ENT. RTN. I.U./O.U. PCB Check (3)…
-
Self-checking procedure of PCB by means of the Remote Control Switch
The self checking performs to check the remote control switch and to clear EEPROM (storage cell inside of the remote control switch). (1) Press and hold “ ” (menu) and “?” (help) simultaneously for 3 seconds during the normal mode (when unit is not operated). Check Menu I. U./O. U. PCB Check Self…
-
(9) No Function
This function is not used. Press “OK” to proceed. Self Checking 07:000 (10) Transmission Circuit Test The remote control switch automatically starts to check the transmission circuit. Self Checking (11) Remote Control Switch Thermistor Test The temperature detected by remote control switch…
-
8.3.3 Troubleshooting using the 7 segment display
Simple checking by 7-segment display 1 Turn ON indoor unit connected to the outdoor unit During auto-addressing, the following items can be checked using the outdoor unit’s on-board 7-segment LED display: 2 Turn ON the outdoor unit Auto-addressing starts Disconnection of power supply to the…
-
Check mode items
RAS-(2-2.5)HVNP / RAS-3HVNP Item Item Indication data Check No. Indic. Indic. Input/output state of outdoor microcomputer 01 SC Capacity of operating indoor unit 02 oP 11 Inverter order frequency to compressor 03 HI 74 Indoor order frequency to compressor 04 H2 74 Air flow ratio 05 Fo 80…
-
Item Item Indication data Check No. Indic. Indic. Input/output state of outdoor microcomputer 01 SC Capacity of operating indoor unit 02 oP 11 Control software No. 03 SP 11 Inverter software No. 04 iP 11 Inverter order frequency to compressor 05 HI 74 Air flow ratio 06 Fo 80 00~15 Outdoor unit…
-
Item Item Indication data Check No. Indic. Indic. Input/output state of outdoor microcomputer 01 SC Capacity of operating indoor unit 02 oP 11 Control software No. 03 SP 11 Inverter software No. 04 iP 11 Inverter order frequency to compressor 05 HI 74 Air flow ratio 06 Fo 80 00~15 Outdoor unit…
-
Cause of indoor unit stoppage (dA)
Contents 00 Operation OFF, Power OFF 01 Thermo-OFF 02 Alarm 03 Freeze protection overheating protection 05 Instantaneous power failure at outdoor unit 06 Instantaneous power failure at indoor unit 07 Stoppage of heating operation due to high outdoor air temperature 10 Demand thermo OFF 13 Retry…
-
Cancellation of Forced Thermo OFF (21)
Turn ON the power source and wait for more than 30 seconds. Then press PSW1 and PSW3 simultaneously for more than 3 seconds. Forced thermo-OFF (indoor unit error code 21) will be cancelled. However, this function may damage the compressor, use only on inevitable occasion. • In case of using the…
-
Protection control code on 7-segment display
Protection control code is displayed on 7-segment when a protection control is activated. Protection control code is displayed while function is working, and goes out when released. When several protection control are activated, code number with higher priority will be indicated (see below for…
-
Activating condition of protection control code
To monitor the conditions such as the temperature change and others, the control of the frequency and other controls are performed by the protection control in order to prevent the abnormal operations. The activating conditions of protection control are shown in the table below: RAS-(2-2.5)HVNP /…
-
Code Protection control Activating condition Remarks Compression ratio ε ≥ 7.5 => frequency decrease Compression ratio ε ≤ 1.6 => frequency increase P01 Pressure ratio control ε = (Pd+0.1)/(Ps+0.1) High Pressure Switch for Control is activated P02 High-pressure increase protection => Frequency…
-
8.4 Checking procedure for main parts
8.4.1 Procedure for checking the DIP-IPM inverter for indoor and outdoor units RAS-(3-6)H(V)N(P/C)E High voltage discharge work for replacing parts C aution Electrical hazard. Risk of electrical shock. Perform this high voltage discharge work to avoid an electric shock. Turn OFF the main switches…
-
Touch [+] side of the tester to DIP-IPM 52C terminal, and [-] side to DIP-IPM R, S and T terminals to measure the resistance. Normal if all three terminals have 1 kΩ or greater. Contrary to [1], touch [-] side of the tester to DIP-IPM 52C terminal, and [+] side to DIP-IPM R, S terminals to measure…
-
ACT circuit of inverter PCB Internal circuit of ACT part of inverter module Non-faulty if [9] – [13] are checked and satisfied. (Measure with 1 kΩ range of a tester.) External Appearance and Internal Circuit of Transistor Module N ote DO NOT use a digital tester. 9 Check items [1] – [8]. 10 Touch…
-
Checking Method of Fuse for fan motor protection (EF1) (Measure the resistance under 1 kΩ range of a circuit tester.) N ote DO NOT use a digital tester. By placing the + and - side of tester to EF1 on inverter PCB, measure the resistance. EF1 If the resistance is 0Ω, it is normal. + - Contact…
-
Transistor module checking procedure
1 1 Outer Appearance and Internal Circuit of Transistor Module 1 1 1. Drive circuit. 2. Overheating protection circuit. 3. Sensor. Procedure: Remove all the terminals of the transistor module before check. If items [1] – [4] are performed and the results are satisfactory, the transistor module is…
-
Diode module checking procedure
Outer appearance and internal circuit of diode module: If items [1] – [4] are performed and the results are satisfactory, the diode module is normal. Measure it under 1kΩ range of a tester. N ote DO NOT use a digital tester. 1 By touching the + side of the tester to the + terminal of diode module…
-
danger : • Electrical hazard. Risk of serious injuries or death. • Before installing the electrical wiring or before performing a periodical check, turn OFF the main switch of the unit. For safety reasons, be sure that the fan is stopped. • Prevent from touching the capacitors’ terminals. High…
-
8.4.3 Fault diagnosis of DC fan motor
When ISPM/DIP-IPM is faulty and Alarm 03, 04 or 53 appears, the fan motor may also be damaged. To prevent ISPM/DIPIPM damage which may result from operation combined with a faulty fan motor, check also if the fan motor is not damaged when ISPM/DIP-IPM is replaced caution • Turn OFF main power before…
-
8.4.4 Checking procedure for the electronic expansion valve for indoor and outdoor units
Indoor unit electronic expansion valve Locked with fully closed Outdoor unit electronic expansion valve Check the liquid pipe temperature during the hea-It is abnormal if the liquid pipe pressure ting process. It is abnormal if the temperaturedoes not increase during the pump down process. does not…
-
8.4.6 Checking procedure for other parts
-
Checking procedure for the compressor
CHECK LIST ON COMPRESSOR Client: Model: Date: Serie No. Production Date: Checker: No. Check item Check method 1 Is THM9 correctly connected? 1. Is wire of thermistor correctly connected by viewing? THM9: Discharge Gas Thermistor 2 Is thermistor THM9 disconnected? Result Remarks 2. Check to ensure…
-
Additional Information for “CHECK LIST ON COMPRESSOR”
Check item Additional information (mechanism of the compressor failure) 1&2 The liquid refrigerant return volume to the compressor is controlled by the discharge gas temperature Td when compressor is operating. If Td thermistor is disconnected, the liquid refrigerant return volume will become small…
-
9.1 RAS-(2-2.5)HVNP
-
9.1.2 Parts table
-
9.2 RAS-3HVNC
-
9.2.2 Parts table
-
RAS-3HVNPE New issue of Spare Parts List for HITACHI New DC Inverter UTOPIA PARTS Outdoor Units IVX Premium and IVX Standard Series NEWS 9.3.1 Cycle and structural parts DATE: Dec’12 PAGE: 4/21 LOCATION OF SPARE PART IN THE UNIT CABINET AND CYCLE RAS-3HVNPE Spare Parts Document: EPN-201211A Hitachi…
-
SERVICE 9. Spare parts
DATE: Dec’12 New issue of Spare Parts List for HITACHI New DC Inverter UTOPIA PAGE: 15/21 PARTS Outdoor Units IVX Premium and IVX Standard Series NEWS 9.3.2 Electrical parts LOCATION OF SPARE PART IN THE UNIT ELECTRICAL PARTS RAS-(3/4/5/6)HVNPE A View from A 9 Spare Parts Document: EPN-201211A…
-
9.3.3 Parts name
Cycle and structural parts No. Part name Remarks No. Part name Remarks 18 EXPV Coil Handle 19 Stay 1-2 H Cover 20 End P Unit 1-3 Pipe Cover B 21 Partition S Assy 2 Upper Cover Assy Assembly 22 Accumulator 3 Service Cover S Assy Assembly 23 Strainer 4 S Cover B Lower Service Cover 24 Pressure SW…
-
9.4SERVICE
RAS-(4-6)H(V)NPE SUBJECT New issue of Spare Parts List for HITACHI New DC Inverter UTOPIA PARTS Outdoor Units IVX Premium and IVX Standard Series NEWS 9.4.1 Cycle and structural parts DATE: Dec’12 PAGE: 8/21 LOCATION OF SPARE PART IN THE UNIT CABINET AND CYCLE RAS-(4/5/6)H(V)NPE 9 Spare Parts…
-
SERVICE 9. Spare parts
DATE: Dec’12 New issue of Spare Parts List for HITACHI New DC Inverter UTOPIA PAGE: 15/21 PARTS Outdoor Units IVX Premium and IVX Standard Series NEWS 9.4.2 Electrical parts LOCATION OF SPARE PART IN THE UNIT ELECTRICAL PARTS RAS-(3/4/5/6)HVNPE A View from A Spare Parts Document: EPN-201211A…
-
DATE: Dec’12
New issue of Spare Parts List for HITACHI New DC Inverter UTOPIA PAGE: 17/21 PARTS Outdoor Units IVX Premium and IVX Standard Series NEWS 9. Spare parts LOCATION OF SPARE PART IN THE UNIT ELECTRICAL PARTS RAS-(4/5/6)HNPE A View from A 9 Spare Parts Document: EPN-201211A Hitachi Air Conditioning…
-
9.4.3 Parts name
Cycle and structural parts No. Part name Remarks No. Part name Remarks 21-1-1-1 Expansion Valve Handle 21-1-1-2 Strainer H Cover 21-2 Header G Unit Assembly 1-3 Pipe Cover B 22 EXPV Coil Coil for Expansion Valve 2 Upper Cover Assy Assembly 23 Stay End P Unit 1 Rear Cover L Assy 1-1 1-2 Assembly 3…
-
RAS-(4-6)HVNPE No. RAS-(4-6)HNPE Part name Remarks 1 Electrical Wiring Diagram Assembly (2+3+Harness) No. Part name Remarks 1 Electrical Wiring Diagram Assembly (2+3+Harness) 2 P Plate Unit Assembly (2-1~2-11) 2 P Plate Unit Assembly (2-1~2-11) 2-1 P Plate Assy Assembly 2-1 P Plate Assy Assembly 2-2…
-
DATE: Dec’12
9.5 RAS-(4-6)H(V)NCE New issue of Spare Parts List for HITACHI New DC Inverter UTOPIA PARTS Outdoor Units IVX Premium and IVX Standard Series NEWS PAGE: 12/21 9.5.1 Cycle and structural parts LOCATION OF SPARE PART IN THE UNIT CABINET AND CYCLE RAS-4H(V)NCE Spare Parts Document: EPN-201211A Hitachi…
-
PARTS
NEWS SUBJECT DATE: Dec’12 New issue of Spare Parts List for HITACHI New DC Inverter UTOPIA PAGE: 13/21 Outdoor Units IVX Premium and IVX Standard Series 9. Spare parts LOCATION OF SPARE PART IN THE UNIT CABINET AND CYCLE RAS-(5/6)H(V)NCE 9 Spare Parts Document: EPN-201211A Hitachi Air Conditioning…
-
DATE: Dec’12
9. Spare parts New issue of Spare Parts List for HITACHI New DC Inverter UTOPIA PAGE: 19/21 PARTS Outdoor Units IVX Premium and IVX Standard Series NEWS 9.5.2 Electrical parts LOCATION OF SPARE PART IN THE UNIT ELECTRICAL PARTS RAS-(4/5/6)HVNCE A View from A Spare Parts Document: EPN-201211A…
-
DATE: Dec’12
New issue of Spare Parts List for HITACHI New DC Inverter UTOPIA PAGE: 21/21 PARTS 9. Spare parts Outdoor Units IVX Premium and IVX Standard Series NEWS LOCATION OF SPARE PART IN THE UNIT ELECTRICAL PARTS RAS-(4/5/6)HNCE A View from A 9 Spare Parts Document: EPN-201211A Hitachi Air Conditioning…
-
9.5.3 Parts name
Cycle and structural parts No. Part name Remarks No. Part name Remarks 21-1-1-2 Strainer Handle 21-2 Header G Unit Assembly H Cover 22 EXPV Coil Coil for Expansion Valve 1-3 Pipe Cover B 23 Stay 2 Upper Cover Assy Assembly 24 End P Unit Partition S Assy 1 Rear Cover Assy 1-1 1-2 Assembly 3…
-
RAS-(4-6)HVNCE No. RAS-(4-6)HNCE Part name Remarks 1 Electrical Wiring Diagram Assembly (2+3+Harness) No. Part name Remarks 1 Electrical Wiring Diagram Assembly (2+3+Harness) 2 P Plate Unit Assembly (2-1~2-11) 2 P Plate Unit Assembly (2-1~2-11) 2-1 P Plate Assy Assembly 2-1 P Plate Assy Assembly 2-2…
-
9.6.1 Cycle and structural parts RAS-(8-10)HNPE Spare Parts Document: EPN-201211B 308 SMGB0079 rev.0 - 01/2013
-
RAS-(8-10)HNCE
9 Spare Parts Document: EPN-201211B 309 SMGB0079 rev.0 - 01/2013
-
9.6.2 Electrical parts
Spare Parts Document: EPN-201211B 310 SMGB0079 rev.0 - 01/2013
-
9.6.3 Parts name
Cycle and structural parts RAS-(8-10)HNPE No. Part name Remarks No. Part name Remarks 26 Strainer Handle 27 Pressure SW H Cover 28 Coil 20 Coil for Solenoid Valve 1-3 Pipe Cover B 29 Coil Coil for 4 Way Valve 2 Upper Cover Assy Assembly 30 4-Way Valve Assy Assembly 4-Way Valve Assy Assembly 1…