Инструкции на Контроллеры Hitachi серии PSC-A64S
Контроллеры Hitachi серии PSC-A64S (центральный пульт управления). Инструкция по установке и эксплуатации.
Смотрите также: Инструкция по монтажу и эксплуатации →
Загружаем документ…
Текст инструкции
-
FUNCIONAMENTO BRUGER- OG MONTERINGSVEJLEDNING INSTALLATIE- EN BEDIENINGSHANDLEIDING HANDBOK FÖR INSTALLATION OCH ANVÄNDING ΕΓΧΕΙΡΙΔΙΟΕΓΚΑΤΑΣΤΑΣΗΣΚΑΙΛΕΙΤΟΥΡΓΙΑΣ ENGLISH SVENSKA Do not perform installation work, without referring to our installation manual. No realice la instalación de este equipo…
-
1. SAFETY SUMMARY DANGER: DO NOT pour water into the central station. This product is equipped with electrical parts. If poured, it will cause a serious electrical shock. WARNING: DO NOT perform installation work and electrical wiring connection by yourself. Contact your distributor or dealer of…
-
INSTALLATION WORK 2.3. INSTALLATION SPACE In case of installing the central stations in the vertical direction, keep a distance more than 50mm between the central stations vertically. If the distance is insufficient, the front cover of the central station can not open wide enough. More than 50 mm…
-
ENGLISH ELECTRICAL WIRING 3. ELECTRICAL WIRING 3.1. ELECTRICAL WIRING Up to 8 Central Stations can be connected to the H-LINK (Control line). 2 Use the 2-core cable of 0.75-1.25 mm or the 2-core twist pair cable (Max. 1.000 m) for the transmission cable for the central station, for the outdoor unit…
-
ELECTRICAL WIRING DSW1 (Address Setting) Address 0 Address 1 Address 2 Address 3 ON ON ON ON Address 4 Address 5 Address 6 Address 7 ON ON ON ON NOTE: When using the central station PSC-5S and PSC-A64S together in the same HLINK (control line) system, set the DSW1 not to be overlapped. Divide the…
-
Judgment of H-LINKII Adaptive START NO Other central controller is connected in the same H-LINK (control line) system (*1) NO YES All models of other connected central controllers are PSCA*** or HC-A*** (*1) NO H-LINKII adaptive DSW2-4 Pin OFF YES The setting of other connected central controllers…
-
GROUP SETTING Central station Outdoor unit Indoor unit Remote Control Switch Group Group Group Group Group Group Zone One remote control switch group is considered as one group The remote control switch group with one indoor unit is also considered as one group As for the indoor unit without remote…
-
4.1. GROUP SETTING PROCEDURE - The group setting consists of the master unit setting and the slave unit setting. The indoor unit, which is connected directly to the remote control switch, is set as the master unit, and the indoor unit connected with the transmission line is set as the slave unit.…
-
GROUP SETTING 4.1.2. SYSTEM OF MORE THAN 17 INDOOR UNIT CONNECTED In this case, the group setting by central station is required. Group setting is for master unit (directly connected to remote control switch) and slave unit (connected by extension cable). In case that the remote control switch is…
-
4.2.2. PROCEDURE OF MASTER UNIT SETTING a. Screen change for Master Unit Setting keep depressing the "CHECK" switch for 3 seconds during all the indoor unit is stopped (with "RUN" indicator OFF). The "CHECK" indicator turns ON, and it shows the state is changed to the CHECK mode. In addition, "1"…
-
GROUP SETTING • ATTENTION: - When the indication of Ref. Nº is “- -”, the indication of I.U. Add. is also “- -”. In such a case, I.U. Add. can not be changed although the “Å” (TEMP) switch is depressed. - Ref. Nº with no indoor unit connected and I.U. Add. not connected are not indicated. - The…
-
4.3. SETTING OF SLAVE UNIT When using the remote control switch (PC-AR(T)), the half-size remote control switch (PC-ARH) or receiver kit (PC-ALH∗), after the setting of master unit, the central station automatically set the slave unit. Check for the setting state by the slave unit setting mode.…
-
GROUP SETTING b. Select the refrigerant system address and indoor unit address to set. The refrigerant system address is changed by depressing "∇" (TEMP) switch and the indoor unit address is changed by depressing "Δ" (TEMP) switch in order as shown below. In this case, the switch is kept…
-
4.3.3. CANCELLATION OF SLAVE UNIT SETTING a. Screen Change for Cancellation of Slave Unit Setting. Keep depressing the "CHECK" switch for 3 seconds during all the indoor unit is stopped (with "RUN" indicator OFF). The "CHECK" indicator turns ON, and it shows the state is changed to the CHECK mode.…
-
INPUT/OUTPUT FUNCTION 5. INPUT/OUTPUT FUNCTION The central station has two input functions and two output functions as shown below. 1. Simultaneous Operation/Stoppage. This function is for operating / stopping all the indoor units of the group, which is set by the central station, by the external…
-
7. Simultaneous Alarm Output. This function is for outputting signal outward in the case where there is any air conditioner in abnormal condition in the group set by the central station. The input function is set by DSW2 as shown in the table below: DSW Pin Nº Function Simultaneous…
-
INPUT/OUTPUT FUNCTION 2. Changing to Demand Setting Mode. Depress the “CHECK” switch and change the 7-segment indication for check to “5” (Demand Setting Mode). The LCD indication of the central station is as shown below. “5” shows the demand setting mode. Ref. Nº. of Indoor Unit Set as Master Unit…
-
5. Setting Procedure Depress the “RUN/STOP” switch and the selected group is set with demand control, and the “°” and “DEMAND” indications appear. In the case where there is one or more group with demand setting in the zone, the "°" indication of zone turns ON. (Every time the “RUN/STOP” switch is…
-
OPTION SETTING Indication of Option Setting Mode When the central station is changed to the slave unit setting mode, the LCD indication on the central station is as shown below. The indication of the group to be set is flickered. The Ref. Nº and I.U. Add. indicates the address of the indoor unit…
-
7. INITIALIZATION OF CENTRAL STATION The procedure for initialization of the group setting and the optional setting is as follows. 7.1. CHANGiNG TO SELF CHECK MODE Depress the “GROUP ()” and ”MODE” switches simultaneously, the central station is changed to the self check mode. In case that there is…
-
INITIALIZATION OF CENTRAL STATION
20 7.3. ZONE AND GROUP SETTING TABLE OF CENTRAL STATION (1) Indoor Unit Address Refrigerant number Fill the group number (1-4) and the group number (1-16) in the above table. Circle the unit number of the master unit. 15
-
7.4. ZONE AND GROUP SETTING TABLE OF CENTRAL STATION (2) Zone Group Remarks (ex. Room name) Zone Group Remarks (ex. Room name) ENGLISH INITIALIZATION OF CENTRAL STATION
-
SWITCH NAMES AND FUNCTIONS 8. SWITCH NAMES AND FUNCTIONS Liquid Crystal Display Selection The figure below shows all the indications for reference.The actual display during operation is different. Indication of Setting Target (Page 24, 25) Indication of Fan speed (Page 25,26) Indication of Timer…
-
About Zone and Group The central station controls plural indoor units as a unit (one indoor unit is also available). The operation unit is as follows; Group Minimum operation unit for central station One remote control switch group is considered as one group under the same control. The central…
-
OPERATION PROCEDURE 9. OPERATION PROCEDURE 9.1. SETTING TARGET SELECTION AND MONITORING OPERATION STATUS The central station can control up to 64 groups by each group, each zone or simultaneously . (The selected setting target can be operated and the unit operation status can be monitored.) •…
-
3. When selecting the group, the setting conditions of each
group are indicated. By operating by the remote control switch, the content of the setting is indicated. Zone show the operating conditions of each zone as follows; - OFF Stoppage of All Groups in Zone - ° ON Operation of One or More Group in Zone - ° Flickering Failure in One or More Group in Zone…
-
9.3. SETTING OF TEMPERATURE, FAN SPEED AND LOUVER ANGLE • ATTENTION: - Do not touch the “CHECK” switch. The “CHECK” switch is only for service use. - When the “CHECK” switch is depressed by a mistake and the central station is changed to the check mode, depress the “RESET” switch to cancel. 1.…
-
In Case of 4-Way Cassette Type (Example) LCD Indication Air Louver Angle Cooling Dry Heat Approx. Approx. Approx. Approx. Approx. Approx. Approx. 25° 30° 35° 40° 50° 55° 60° Angle Range Angle Range :Recommended Angle NOTES: - The fixing angle of the louver shown above is the case of 4-way cassette…
-
OPERATION PROCEDURE Prohibiting Operation by Remote Control Switch <Function> To prohibit the operation by the remote control switch. When this function is available, the “CENTRAL” indication appears on the LCD on the remote control switch and the operation by the remote control switch is not…
-
Timer Operation <Function> To set the schedule operation “available” or “not available” by the signal from the control timer in case of connection with the control timer (PSC-A1T; Option). The schedule operation can be set “available” or “not available” individually for each unit, however, the…
-
OPERATION PROCEDURE <DEMAND> The “DEMAND” is indicated when the demand input is set by the outside input function. The indication is indicated for the group with demand setting and the “DEMAND” indication flickers when the demand signal is input. Contact your distributor or dealer of HITACHI for…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.