PMML0077/0 A - 11/03 - Printed in Spain
INSTALLATION AND OPERATION MANUAL MANUAL DE INSTALACIÓN Y FUNCIONAMIENTO INSTALLATIONS- UND BETRIEBSHANDBUCH MANUEL D’INSTALLATION ET DE FUNCTIONNEMENT MANUALE D’INSTALLAZIONE E D’USO HARC-BX E MANUAL DE INSTALAÇÄO E DE FUNCIONAMENTO BRUGER- OG MONTERINGSVEJLEDNING INSTALLATIE- EN…
-
CONTENTS
Page 1 INTRODUCTION_______________________________________ 2 1.1. Preface 2 1.2. Safety Summary 2 2 SYSTEM CONSTITUTION 4 2.1. System Constitution 4 2.2. Name of parts 4 2.3. Name of Parts (Control Board) 5 2.4. Specifications of HARC-BX E 6 3 INSTALLATION WORK 7 3.1. Selection of Installation Place…
-
1/2 INTRODUCTION
1 INTRODUCTION 1.1. Preface ■ This BMS connection adapter is applied to the packaged air conditioners. ■ Do not place the adapter in a place where flammable gas, or oil mist may stay exit, it will cause a fire, a fire disaster, deformation of machines, corrosion or breakage. - Places where oil mists…
-
Explanation of signs Õ DANGER: This sign indicates where user mishandles or misapply its operation, which could result in severe personal injury or death. CAUTION: This sign indicates general users or non-specific users are forced to act. Ô ATTENTION: This sign indicates restriction. Installation…
-
2/4 SYSTEM CONSTITUTION
2 SYSTEM CONSTITUTION 2.1. System Constitution The Internal Constitution of BMS connection using HARC-BX E is displayed in the Figure below. The description of HARC-BX E is written on this manual. As for the other equipment to setup the system, read the attached installation manual respectively.…
-
2.3. Name of Parts (Control Board) o PSW No. 1 (M.CLR): Push Switch for checking connected unit quantity p 7-Segment (*): Present state of HARC-BX E q PSW No.2 (LON-SERV): Push Switch for transmission neuron ID. (Service Pin) r 8P DSW No. 1 (S201) (**): Dip Switch System Setting of HARC-BX E s 8P…
-
2/6 SYSTEM CONSTITUTION
2.4. Specifications of HARC-BX E ■ Hardware Specification Item Specification Power Source AC240V±10%(50/60Hz) Power Consumption Mass 30W(max) Width:240 mm, Height:285 mm, Depth:128.5 mm (When installed inside box) 2.3kg Installation Condition Indoor Outer Dim Temperature Condition 0~45 °C Humidity…
-
3 INSTALLATION WORK This manual provides operational instructions for HARC-BX E from installation to turning on the power source. The procedure of the instruction is described in the table below. Handling Procedure No. Items Contents 1 Selection of Installation Position The precautions on the…
-
3/8 INSTALLATION WORK
2. Fixing Method by Screw(M4) (Screws: Field-supplied) By using screw (M4 Screw, 4Position), fix HARC-BX E on the wall.
-
4 WIRING CONNECTION Read and understand SAFETY SAMMARY as described in the beginning of this manual before starting up wiring work. ■ Wiring work should perform according to”the local regulations” and the instruction of utility company beforehand. ■ Wiring work should be perfomed by qualified…
-
4/10 WIRING CONNECTION
(*1) Ensure to apply Twisted cable Recommended Cable Types: Japan Cable Industrial Associations - Hitachi Cable Co., Ltd. Japan Cable Co., Ltd. Integral power consumption Non-shielded JKEV KPEV KNPEV KPEV Shielded (Copper Foil) Shielded(Twisted) JKEV-S KPEV-S KNPEV-S KPEV-S JKEV-SB KPEV-SB KNPEV-SB…
-
4.2. Electrical Wiring 1. Turn OFF the main power switch connected to the wire of HARC-BX E and the surrounding equipment to connect wire. 2. Wiring work should be conducted according to the table described below. The “No.” showing in the table indicates the wire of “Wiring Method”. ■ Electrical…
-
4/12 WIRING CONNECTION
4.3. Arrangement of the Installation of PCB and H-LINK Terminals As described in the figure below, 8 PCBs which are built into HARC-BX E and H-LINK and Terminals correspond to the both sides of the same numbers, 1 to 8 within respectively. In order that PCB would be able to communicate with unit it…
-
5 TEST RUN 5.1. Setting of Dip Switch 1. Setting Dip Switch before power supply. 2. Remove the front board to set Dip Switch. 3. Dip Switch setting for each PCB is different. 4. Setting for 8 Pins Dip Switch (S201) Setting of 8 Pins DipSwitch (S201) are determined by the system numbers and the unit…
-
5/14 TEST RUN
Next, setting for the required unit numbers are described below. System No. Setting Pin No.5 to No.8 System No. ON 1 System No. ON Setting Pin No.5 to No.8 Setting Pin No.5 to No.8 ON System No. 13 Setting Pin No.5 to No.8 ON 5. Setting of 8 Pins Dip Switch (S202) Setting of 8 Pins DipSwitch (S202)…
-
4. Check how many numbers of identified Indoor unit
The amounts of Indoor unit, which HARC-BX E has identified will display on the 7-Segment after pressing the PUSH SWITCH (PSW [M.CLR]) on HARC-BX E with indicating ” ” on the 7-Segment display. (Check if the amounts of actual Indoor Units are identical to these). 5. After the quantity of recognizable…
-
5/16 TEST RUN
5.3. Abnormal Indication 1. Abnormality will be identified with 7-Segment Display of HARC-BX E . 7-Segment Display Phenomenon Content of Abnormality Abnormality in Initial Connection at No Remote Control Switch Group were found (failure to conform the connection). Transmission Abnormality in Entire…
-
6 MAINTENANCE AND SERVICE
6.1. Self-Inspection for HARC-BX E Self-Inspection to identify the abnormality of HARC-BX E can be conducted by the following procedures. 1. Turn ON the power supply with leaving 8 Pins DSW [S202] OFF. (The 7-Segment shows “” and is lit OFF). ON Pins DSW (S202) 2. Turn ON only No. 1 pin of 8-pin DSW…
-
6/18 MAINTENANCE AND SERVICE
6.2. Troubleshooting The following table indicates possible trouble-shooting upon the abnormal operation in the unit. Ensure that power supply is switched OFF before starting the check. No. Phenomenon Items to be checked Check if power cable is connected. Check if power is supplied. Check if Power…
-
No
Phenomenon Items to be checked 6/19 Action Check if the Dip Switches on HARC-BX E are set correctly. HARC-BX E does not identify the air conditioner even though power supply is ON. (“ ” displayed on the 7-Segment). 2 After the indication of “ ” on the 7-Segment with check mode, the quantity of…
-
6/20 MAINTENANCE AND SERVICE
6.3. Periodical Inspection The unit should be periodically inspected in order to ensure dependable performance and long life operation. 1. Ambient Conditions: - Inspect that the internal temperature of cabinet panel is not abnormally too high. - Inspect that the temperature of unit case is not…