Инструкция на Контроллеры Hitachi серии CSC-5S
Контроллеры CSC-5S для управления кондиционерами Hitachi. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
HANDBOK FÖR INSTALLATION OCH ANVÄNDING
ÅÃ×ÅÉÑÉÄÉÏÅÃÊÁÔÁÓÔÁÓÇÓÊÁÉËÅÉÔÏÕÑÃÉÁÓ ENGLISH ESPAÑOL MANUAL DE INSTALAÇÄO E DE FUNCIONAMENTO BRUGER- OG MONTERINGSVEJLEDNING INSTALLATIE- EN BEDIENINGSHANDLEIDING SVENSKA Do not perform installation work, without referring to our installation manual. No realice la instalación de este equipo, sin…
-
– Hazards or unsafe practices which COULD result in minor personal injury or
CAUTION product or property damage. PRECAUCIÓN – Riesgos o prácticas poco seguras que PODRÍAN provocar lesiones personales de menor importancia o daños en el producto u otros bienes. VORSICHT – Gefährliche oder unsichere Anwendung, die geringfügigen Personen-, Produkt- oder Sachschaden verursachen…
-
120 mm
UNIT SELECTION 120 mm 2
-
1. SAFETY SUMMARY DANGER: DO NOT pour water into the central station. This product is equipped with electrical parts. If poured, it will cause a serious electrical shock. WARNING: DO NOT perform installation work and electrical wiring connection by yourself. Contact your distributor or dealer of…
-
INSTALLATION WORK 2.3. INSTALLATION SPACE In case of installing the controllers in vertical line keep a distance more than 50mm between the controllers vertically. If the distance is insufficient, the front cover of the controller can not open wide enough More than 50mm 1.Insert the edge of the…
-
3. ELECTRICAL WIRING 3.1. ELECTRICAL WIRING Max.8 Chiller Units CSC-5S Control Timer Chiller Units (Option) Chiller Units Connector Terminal TB2 CN1 TB1 F Control Timer's Accessory H-LINK Power Supply AC220~240V Cable(1m) To TB2 of Other Controller Twist Pair Cable 1P-0.75mm2 3.1.1. RECOMMENDABLE…
-
ELECTRICAL WIRING Dip Switch Setting Pin No. DSW Setting Contents of Setting ON OFF 1 2 DSW1 DSW2 3 For Address Setting Remarks Refer to the table below. It is necessary to set these switches in case of connecting more than 2 units. H-Link (Chiller~CSC-5S) 4 For Checking Connection Not Available…
-
4. GROUP REGISTRATION Indication after turning ON power switch If group registration is not performed, the indication is changed as follows. After COOL UNIT No. Checking Connection UNIT No. INDVDL A/C SET TEMP. ℃ UNIT No. INDVDL INDVDL In case that the address of the controller is not set at “1” and…
-
GROUP REGISTRATION CAUTION: - If “RESET” switch is pressed or any switch is not pressed for more than 30 seconds, group registration mode is changed to the normal mode automatically. In this case, group registration is not available. - Check to ensure that the same unit No. setting is not…
-
5. NAME OF EACH PART Liquid Crystal Display Section The figure below shows all the indications for reference.The actual display during operation is different. Indication of Operating Unit (Page 10) Indication of Individual Control (indicated during individual control) (Page 8) Timer Indication…
-
CONTROLS Operation Switch Section The above figure shows the central station with the cover opened. When opening the cover, pull the cover toward the arrow direction. 6. CONTROLS Individual Control Multiple-unit Control - “INDVDL” is indicated at the display panel during this control. There are…
-
7. OPERATION PROCEDURE 7.1. GROUP REGISTRATION PROCEDURE COOL UNIT No. HEAT H.RCV. A/C MULTI TIMER EMG.STOP INDVDL NO FUNC. DEMAND INLET SET TEMP. ℃ OUTLET TEMP. PR. MPa H.STRG LOCAL ABNML CHECK UNIT SELECTION RUN/STOP MODE CHANGE A/C/H.STRG TIMER OPTION DISP.MODE RESET 2, 4 CHECK GROUP TEMP. 1, 3…
-
OPERATION PROCEDURE 3. Press the “GROUP” switch again. The first digit is flickered (the maximum unit No. is indicated at first). UNIT No. INDVDL 4. By pressing the “UNIT SELECTION” switch, the unit confirmed to connect No. bigger than minimum unit No. is indicated sequentially. (Set the maximum…
-
1. Press “UNIT SELECTION” switch.By pressing, the target
units are changed as follows. In case of indicating “AA”, all units are operated simultaneously. 11 Unit No. is changed. The figure below shows the case of selecting unit No.4. COOL UNIT No. SET TEMP. ℃ INDVDL AA NOTE: This procedure is not performed in multiple unit control. 2. If the unit is…
-
OPERATION PROCEDURE 7.3. OPERATION MODE SETTING PROCEDURE Operation and Function COOL UNIT No. HEAT H.RCV. A/C MULTI TIMER EMG.STOP INDVDL NO FUNC. DEMAND ℃ OUTLET TEMP. PR. MPa INLET SET TEMP. H.STRG LOCAL ABNML CHECK UNIT SELECTION RUN/STOP MODE CHANGE A/C/H.STRG TIMER OPTION DISP.MODE - COOL…
-
7.4. TEMPERATURE SETTING PROCEDURE COOL UNIT No. HEAT H.RCV. A/C MULTI TIMER EMG.STOP INDVDL NO FUNC. DEMAND INLET SET TEMP. ℃ OUTLET TEMP. PR. MPa H.STRG LOCAL ABNML CHECK UNIT SELECTION RUN/STOP MODE CHANGE A/C/H.STRG DISP.MODE RESET 1 TIMER OPTION CHECK GROUP TEMP. CHECK 2 CAUTION: - Do not…
-
OPERATION PROCEDURE 7.5. CHANGING DISPLAY MODE PROCEDURE COOL UNIT No. HEAT H.RCV. A/C MULTI TIMER EMG.STOP INDVDL NO FUNC. DEMAND INLET SET TEMP. ℃ OUTLET TEMP. PR. MPa H.STRG LOCAL ABNML CHECK UNIT SELECTION RUN/STOP MODE CHANGE A/C/H.STRG 2 TIMER OPTION DISP.MODE RESET CHECK GROUP TEMP. 1 Select…
-
ENGLISH OPERATION PROCEDURE 7.6. OPERATION PROCEDURE COOL UNIT No. RUN Lamp HEAT H.RCV. A/C MULTI TIMER EMG.STOP INDVDL NO FUNC. DEMAND INLET SET TEMP. ℃ OUTLET TEMP. PR. MPa H.STRG LOCAL ABNML CHECK UNIT SELECTION RUN/STOP 2 MODE CHANGE A/C/H.STRG TIMER OPTION DISP.MODE RESET 1 CHECK GROUP TEMP. 1.…
-
OPERATION PROCEDURE 7.7. TIMER OPERATION PROCEDURE Operation and Function: COOL UNIT No. HEAT H.RCV. A/C MULTI TIMER EMG.STOP INDVDL NO FUNC. DEMAND INLET SET TEMP. ℃ OUTLET TEMP. PR. MPa H.STRG LOCAL ABNML CHECK UNIT SELECTION RUN/STOP MODE CHANGE A/C/H.STRG TIMER OPTION This is the function to set…
-
7.8. OTHER INDICATIONS Normal Indications LOCAL: “LOCAL” is indicated when setting local at the chiller unit. Setting is not available to change from controller during this indication. Contact to installer for details. DEMAND: This function is not available. EMG.(Emergency) STOP: “EMG. STOP” is…
-
OPERATION PROCEDURE 7.9. OPTION SETTING PROCEDURE COOL UNIT No. HEAT H.RCV. A/C MULTI TIMER EMG.STOP INDVDL NO FUNC. DEMAND INLET SET TEMP. ℃ OUTLET TEMP. PR. MPa H.STRG LOCAL ABNML CHECK UNIT SELECTION RUN/STOP MODE CHANGE A/C/H.STRG 1 TIMER OPTION DISP.MODE RESET CHECK GROUP TEMP. Option 1. Select…
-
NOTE: - In case of individual control, option No.1 only is available. - If “RESET” switch is pressed or any switch is not pressed for more than 30 seconds during option setting procedure, option setting mode is changed to the normal mode without option setting. (A setting is not registered in this…
-
CHILLER CONTROLLER CHECKING PROCEDURE 9. CHILLER CONTROLLER CHECKING PROCEDURE Checking mode indicates 3 kinds of contents as follows. - Operating condition data, Chiller unit ROM No. and controller ROM No. etc. are indicated. Refer to the table below in detail. - The content of abnormal stoppage…
-
Alarm History Indication Previous alarm occurrence data is indicated. The data is indicated up to 10 data by pressing the “UNIT SELECTION” switch. Capacity Control State Indication Capacity control state is indicated. Individual Control: Capacity of each unit is indicted by each pressing the…
-
SELF-CHECKING MODE NOTE: In case of the “UNIT SELECTION ∧”, ”UNIT SELECTION ∨” and “MODE CHANGE” switches are not simultaneously pressed again, self-checking continues. If the self-checking mode is required, refer to the self-checking procedure of page 23. 2. EEPROM Initialization If the EEPROM…
-
Indication on the liquid crystal display is changed as follows. I. Checking for Liquid Crystal ℃ PR. V Checking for External Output COOL UNIT No. HEAT H.RCV. A/C H.STRG LOCAL H.STRG MULTI TIMER EMG.STOP INDVDL NO FUNC. DEMAND INLET SET TEMP. ℃ OUTLET TEMP. PR. MPa LOCAL ABNML CHECK II Checking for…
-
SELF-CHECKING MODE VI. Checking for External Input Prepare the cable assembly as shown in the right figure and connect this cable to CN2. Checking proceeding is as follows. By turning switch 1 ON, LED1 is turning ON → By turning switch 1 OFF and switch 2 ON, LED2 is turned ON → By turning switch 1…
-
HITACHI is participating in the EUROVENT Certification
Programme. Products are as specified in the EUROVENT Directory of Certified Products. Hitachi Air Conditioning Products Europe, S.A. Ronda Shimizu, 1 - Políg. Ind. Can Torrella 08233 Vacarisses (Barcelona) España ISO 9002 certified by AENOR, Spain Hitachi Air Conditioning Products (M) Sdn. Bnd. Lot…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.