Контроллеры PC-2H2 для управления кондиционерами Hitachi. Инструкция по монтажу.
Загружаем документ…
Текст инструкции
-
ENGLISH
Read and understand this manual before using this air conditioner. Keep this manual for future reference. Lea cuidadosamente este manual antes de poner en marcha el equipo de aire acondicionado. Guarde este manual en un lugar seguro por si necesita consultarlo en el futuro. Diese Bedienungsanleitung…
-
DANGER: § DO NOT pour water into the remote controller (hereafter called “controller”). These products are equipped with electrical parts. If poured, it will cause a serious electrical shock. § DO NOT operate switches by wet hand. It may cause an electrical shock. § In case that the protective…
-
INSTALLATION OF REMOTE CONTROL SWITCH <PC-2H2> 1.1. BEFORE INSTALLATION Check the contents and the number of the accessories in the packing. 1 Remote Control Switch, for Operation Control 2 screws ø4x16L For fixing the Holding Bracket onto the wall 1 Remote Control Cable (8 m) for connection Holding…
-
Ë Connect the cable to the PCB connector (yellow) of
the controller, run the cable through the groove at the backside of the casing and draw out the cable from the casing. Ë Mounting procedures. Step 1: Insert the hooks of the controller to the holes on the top of the holding bracket. Step 2: Push the lower part toward the holding bracket. Step 3…
-
INSTALLATION OF REMOTE CONTROL SWITCH <PC-2H2> 1.4.3. ONE REMOTE CONTROL SWITCH FOR MULTIPLE UNITS In case that a longer cable is required, the additional fieldsupplied cable shall be connected as following procedure. A. Prepare the cable with two wires. B. After checking the color of the wires…
-
1.5. TEST RUN PROCEDURE BY REMOTE CONTROL SWITCH
É Turn ON the power source of the Indoor and Outdoor Units Set the TEST RUN mode by remote control switch. Ê Depress the "MODE" and the "CHECK" switches Operation Lamp 05 simultaneously for more than 3 seconds. a) If "TEST RUN" and the counting number of the connected units to the remote control…
-
INSTALLATION OF REMOTE CONTROL SWITCH <PC-2H2> 2. CHECK FUNCTION USING THE REMOTE CONTROL 2.1. ALARM CODES Indication RUN lamp Flashes for 2 Seconds RUN lamp flashes 5 times (5 seconds) with unit number and alarm code displayed Trouble Possible Causes Action Failure in Transmission Between Indoor…
-
2.2. OPTIONAL FUNCTION SETTING
The remote control switch is changed to the optional setting mode by the following procedures. n Field Setting Mode Check to ensure that the unit is stopped, press the "CHECK" switch and the "RESET" switch on the remote control switch simultaneously more than 3 seconds, and the remote control switch…
-
INSTALLATION OF REMOTE CONTROL SWITCH <PC-2H2> n Selection of Other Indoor Unit At the optional setting mode, press the "TIME ∇" switch or the "TIME ∆" switch, the condition of the remote control switch is changed so that the indoor unit can be selected to set the optional function described in the…
-