Инструкция на Battery Optimization Services
A guide to optimize your battery maintenance
Загружаем документ…
Текст инструкции
-
A guide to optimize your battery maintenance
by Peter Shore 1, Emerson Network Power and Geoffrey May 2, FOCUS Consulting Executive Summary All telecommunications nodes, from highly critical core sites to remote access sites, rely on standby batteries to keep systems up and running when utility power is disrupted or fails. As batteries are…
-
Introduction
It is essential that batteries are maintained to ensure reliability. Traditional maintenance techniques can be labor-intensive and expensive, limiting the application of preventive maintenance (PM) to only the most critical sites. However, with a clear understanding of the key failure modes of…
-
Condition-Based Maintenance
Battery Testing For VRLA batteries, annual discharge testing initially became the preferred method for measuring battery capacity and assessing condition. This remains the most accurate but also the most costly way of verifying battery condition—and is valid only at the time of the test. It cannot…
-
End-of-Life Zone Battery replacement required >50% increase Internal Resistance (%) 150 Alert Zone Between 35-50% increase in internal resistance Recommend battery replacement 140 130 Between 25-35% increase in internal resistance Battery capacity approaching end-of-life 120 Up to 25% increase in…
-
Internal Resistance (µΩ) 1400 1200 90% Internal Resistance Values Per Cell 80% Depth of Discharge Per Cell 70% 1000 60% 800 50% 40% 600 30% 400 Depth of Discharge 1600 20% 200 10% 0 0% Internal Resistance Base Line Start of Amber Internal Resistance Warning Zone Start of Red Internal Resistance…
-
Optimized Battery Maintenance
A dynamic, battery maintenance program will provide optimum information on overall battery health and improved battery reliability for each testing dollar spent. Such a program should combine preventive, predictive and corrective maintenance and dynamically perform both state-of-health and…
-
Example 1
On-Site Discharge – Full Capacity Testing with an External Load Battery discharge testing is acknowledged in the industry as the most effective method of determining a battery’s actual capacity and ability to provide a reliable source of power. Discharge/load testing also verifies the integrity of…
-
Selecting the Best Program to Suit Particular Battery Maintenance Requirements
By defining parameters and values for features of various battery maintenance techniques, it becomes clear that no single technique can deliver optimum battery health information and score high on all desirable features. To gain maximum benefit from battery maintenance, a holistic, dynamic life…
-
Proposed Solution for High Critical Nodes
Remote Testing with Dedicated Hardware: Partial Discharge and Internal Resistance Combined with Annual Site Visits For the most critical sites where downtime is not an option, the solution that offers highest confidence in battery condition and reliability is a combination of remote tests with…
-
Optimized Corrective
Maintenance The predictive and preventive elements of an optimized battery maintenance program are an essential part of a complete package but for maximum effectiveness, corrective maintenance elements should be added to form part of the overall maintenance program. A single faulty cell/monobloc can…
-
Conclusions
Most networks rely on large numbers of batteries of various types, age, capacity and condition—often assigned to applications of varying criticality and operating under different temperature and cycling conditions. These batteries need regular maintenance and inspection; however, all of the…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.