Инструкция на Преобразователь частоты Danfoss серии VLT Soft Starter MCD 600
Преобразователь частоты Danfoss серии VLT Soft Starter MCD 600. Руководство по эксплуатации.
Загружаем документ…
Текст инструкции
-
Operating Guide
VLT® Soft Starter MCD 600
-
1 Introduction
8 1.1 Product Description 8 1.2 Document Version 8 1.3 Additional Resources 8 1.4 Approvals and Certifications 8 2 Safety 9 2.1 Safety Symbols 9 2.2 Qualified Personnel 9 2.3 Safety Precautions 9 3 System Design 12 3.1 Feature List 12 3.2 Type Code 13 3.3 Selection of Soft Starter Size 14 3.4…
-
Electromagnetic Capability (Compliant with EU Directive 2014/35/EU) 25 4.4 Inputs 25 4.5 Outputs 25 4.6 Environmental 26 4.7 Heat Dissipation 26 4.8 Motor Overload Protection 26 4.9 Certification 26 4.10 Operational Life (Internal Bypass Contacts) 26 5 Installation 27 5.1 Safety Instructions 27 5.2…
-
Load/Save Settings 40 6.7 USB Save & Load 41 6.7.1 Save and Load Procedure 42 6.7.2 File Locations and Formats 42 6.8 Auto-start/Stop 43 6.9 Network Address 43 6.9.1 44 Setting a Network Address 6.10 Digital I/O State 44 6.11 Analog I/O State 45 6.12 Serial Number & Rating 45 6.13 Software Versions…
-
Constant Current with Current Ramp 58 9.8.3 Adaptive Control for Starting 59 9.8.3.1 60 9.8.4 9.9 Contents Fine-tuning Adaptive Control Constant Current with Kickstart 60 Stop Methods 61 9.9.1 Coast to Stop 61 9.9.2 Timed Voltage Ramp 61 9.9.3 Adaptive Control for Stopping 61 9.9.4 DC Brake 62 9.9.5…
-
11 Application Examples
Contents 121 11.1 Smart Card - Pump Control and Protection 121 11.2 Smart Card - Level-controlled Pump Activation 122 12 Troubleshooting 124 12.1 Protection Responses 124 12.2 Trip Messages 124 12.3 General Faults 138 13 Appendix 141 13.1 Symbols and Abbreviations 141 13.2 Conventions 141 Danfoss…
-
Introduction
1 Introduction 1.1 Product Description The VLT® Soft Starter MCD 600 is an advanced digital soft start solution for 11–315 kW motors. The soft starters provide a complete range of motor and system protection features and are designed for reliable performance in the most demanding installation…
-
2 Safety
2.1 Safety Symbols The following symbols are used in this manual: DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a…
-
WARNING
PROPER GROUNDING It is the responsibility of the installer of the soft starter to provide proper grounding and branch circuit protection according to local electrical safety codes. Not providing proper grounding and branch circuit protection may lead to death, personal injury, or equipment damage.…
-
WARNING
SAFETY OF PERSONNEL The soft starter is not a safety device and does not provide electrical isolation or disconnection from the supply. - If isolation is required, the soft starter must be installed with a main contactor. - Do not rely on the start and stop functions for safety of personnel. Faults…
-
3 System Design
3.1 Feature List Streamlined set-up process • Configuration profiles for common applications. • Built-in metering and inputs/outputs. Easy-to-understand interface • Multi-language menus and displays. • Descriptive option names and feedback messages. • Real-time performance graphs. Supports energy…
-
Customizable protection
• Motor overload. • Excess start time. • Undercurrent/overcurrent. • Underpower/overpower. • Current imbalance. • Input trip. • Motor thermistor. Optional features for advanced applications • Smart cards. • Communication options: - DeviceNet. - EtherNet/IP. - Modbus RTU. - Modbus TCP. - PROFIBUS.…
-
3.3 Selection of Soft Starter Size
The size of the soft starter must match the motor and the application. Select a soft starter that has a current rating at least equal to the motor's full load current rating (see motor nameplate) at the start duty. The soft starter's current rating determines the maximum motor size it can be used…
-
A
-
1/L1
2/T1 3/L2 4/T2 177HA714.10 3.6 Physical Installation/Cooling Clearances 5/L3 6/T3 B A READY RUN TRIP Exit Reset LOCAL READY Menu Store TRIP LOCAL READY Menu Store RUN TRIP Exit Reset LOCAL READY Menu Store RUN TRIP Exit Reset D LOCAL READY Menu Store RUN TRIP Exit Reset VLT VLT VLT VLT VLT Soft…
-
3.7.1.2 Communication Expansion Cards
The VLT® Soft Starter MCD 600 supports network communication via easy-to-install communication expansion cards. Each communication card includes a remote LCP 601 connector port. Table 7: Fieldbus Expansion Cards with Ordering Numbers Option Card Ordering Number VLT® Soft Starter MCD 600 Modbus RTU…
-
Use the main contactor output (13, 14) to control the contactor
For wiring of the main contactor, see illustration 12 in 5.8 Typical Installation. WARNING SHOCK HAZARD When the soft starter is wired in inside delta configuration, it results in a portion of the motor windings being connected to line power at all times (even when the soft starter is switched off).…
-
3.11 Short-circuit Protection Devices
When designing motor circuit protection schemes, the IEC 60947-4-1 standard on soft starters and contactors defines 2 types of coordination regarding soft starters: • Type 1 coordination. • Type 2 coordination. 3.11.1 Type 1 Coordination Type 1 coordination requires that, if there is a short circuit…
-
Nominal rating [A]
-
Model Nominal rating [A] 3 cycle short cct rating @600 V AC (1) MCD6-0144B 184 18 kA MCD6-0171B 225 MCD6-0194B 229 MCD6-0244B 250 MCD6-0287B 352 MCD6-0323B 397 MCD6-0410B 410 MCD6-0527B 550 MCD6-0579B 580 30 kA Suitable for use in a circuit with the prospective current noted, when protected by any…
-
Table 11: Circuit Breakers - High Fault Short-circuit Current
-
Model
-
Specifications
-
Specifications
4.6 Environmental Operating temperature Storage temperature Operating altitude Humidity Pollution degree Vibration -10 to +60 °C (14–140 °F), above 40 °C (104 °F) with derating -25 to +60 °C (-13 to +140 °F) 0–1000 m (0–3280 ft), above 1000 m (3280 ft) with derating 5–95% relative humidity Pollution…
-
5 Installation
5.1 Safety Instructions See 2.3 Safety Precautions for general safety instructions. WARNING INDUCED VOLTAGE Induced voltage from output motor cables that run together can charge equipment capacitors, even with the equipment turned off and locked out. Failure to run output motor cables separately or…
-
5.3 Setting up the Soft Starter
Procedure 1. Mount the soft starter, see 3.6 Physical Installation/Cooling Clearances. 2. Connect control wiring, see 5.4.1 Input Terminals. 3. Apply control voltage to the soft starter. 4. Configure the application (listed in the Quick Set-up): A Press [Menu]. B Press [Menu/Store] to open the Quick…
-
AO-07
Exit Reset AO-08 TRIP DI-B DI-A COM+ START COM+ RUN RESET TER-06 TER-05 READY e77ha718.10 5.4.1 Input Terminals LOCAL Menu Store VLT ® Soft Starter 2/T1 1/L1 4/T2 3/L2 6/T3 5/L3 TER-05, TER-06 Motor thermistor input RESET, COM+ Reset input START, COM+ Start/stop input DI-A, COM+ Programmable input A…
-
RESET
A e77ha721.10 Operating Guide | VLT® Soft Starter MCD 600 COM+ B START A Reset Illustration 7: B Start/stop Start/Stop Control Wiring CAUTION ATTEMPTED START If the start input is closed when control voltage is applied, the soft starter attempts to start. - Check that the start/stop input is open…
-
5.5 Outputs
AO-08 AO-07 21 14 DI-B DI-A COM+ START COM+ RESET Exit Reset 13 TRIP TER-06 RUN TER-05 READY e77ha719.10 5.5.1 Output Terminals LOCAL Menu Store VLT ® Soft Starter 2/T1 1/L1 4/T2 3/L2 6/T3 5/L3 AO-07, AO-08 Analog output 13, 14 Main contactor output 21, 22, 23 Relay output A (default = Run) 33, 34…
-
5.5.4 Programmable Outputs
-
5.7 Power Terminations
-
NOTICE
If the installation requires large diameter cables, it is possible to complete each termination with 2 smaller cables, 1 on each side of the busbar. 5.7.1 Wiring Connectors Select a connector according to the wire size, material, and application requirements. For models MCD6-0144B to MCD6-0579B, a…
-
F1
-
13, 14 Main contactor output
-
5 Motor thermistor input
6 Relay outputs 7 Analog output 8 Control voltage (external equipment) 9 Pilot lamps 10 Communications/smart card expansion port K1 Main contactor F1 Semiconductor fuses RESET, COM+ (S1) Reset START, COM+ (S2) Start/stop DI-A, COM+ Programmable input A (default = Input trip (N/O)) DI-B, COM+…
-
Application
Start mode Start ramp time [s] Initial current [%] Current limit [%] Adaptive start profile Stop mode Stop time [s] Adaptive stop profile Bow thruster Constant current n/a Coast to stop n/a n/a Bandsaw Constant current n/a Coast to stop n/a n/a NOTICE The adaptive start and stop profile settings…
-
6 Set-up Tools
6.1 Introduction Set-up Tools includes options to load or save parameters to a backup file, set the soft starter's network address, check the status of the inputs and outputs, reset the thermal models, or test operation using the Run Simulation. To access Set-up Tools, press [Menu] to open the Main…
-
The simulation is only available when the soft starter is in ready state
Procedure 1. Press [Menu] and select Set-up Tools. Run Simulation Ready e77ha731.10 2. Scroll to Run Simulation and press [Menu/Store]. Apply Start Signal 3. Apply a start command from the selected command source. The soft starter simulates its prestart checks and closes the main contactor relay.…
-
Procedure
1. Press [Menu] and select Set-up Tools. Load/Save Settings Load Defaults e77ha732.10 2. Scroll to Load/Save Settings and press [Menu/Store]. Load User Set Save User Set 3. Scroll to the required function and press [Menu/Store]. 4. At the confirmation prompt, select Yes to confirm or No to cancel.…
-
6.7.1 Save and Load Procedure
Procedure 1. Connect the external drive to the USB port. 2. Press [Menu] and select Set-up Tools. USB Save & Load Save Params and Logs e77ha733.10 3. Scroll to USB Save & Load and press [Menu/Store]. Save Master Params Load Master Params 4. Scroll to the required function and press [Menu/Store]. 5.…
-
e77ha730.10
Operating Guide | VLT® Soft Starter MCD 600 Illustration 13: USB Directory 6.8 Auto-start/Stop Context: The soft starter can be configured to automatically start and/or stop the motor at a particular time, or run it in cycles of a specified duration. The Auto-Start/Stop function in Set-up Tools…
-
IP address. • Gateway address. • Subnet mask. 6.9.1 Setting a Network Address Procedure 1. Press [Menu] and select Set-up Tools. 2. Scroll to Network Address and press [Menu/Store]. e77ha735.10 3. Scroll to the required function and press [Menu/Store]. Set IP Address 192.168.000.002 4. The 1st digit…
-
e77ha717.10 Operating Guide | VLT® Soft Starter MCD AO-08 AO-07 DI-B DI-A COM+ START COM+ RESET TER-06 TER-05 1 RESET, COM+: Reset input 2 START, COM+: Start/stop input 3 DI-A, COM+: Programmable input A 4 DI-B, COM+: Programmable input B 5 13, 14: Main contactor output 6 21, 22, 23: Relay output A…
-
Serial Number & Rating
MCD 600 e77ha789.10 The bottom line of the screen shows the model number. 123456-123 0410-T5-S1-CV2 Illustration 17: Serial Number & Rating Screen 6.13 Software Versions The software version screen reports the version of each software component of the soft starter: • User interface. • Motor control.…
-
Logs
Operating Guide | VLT® Soft Starter MCD 600 7 Logs 7.1 Introduction The Logs Menu provides information on events, trips, and soft starter performance. To access the Logs Menu on the local LCP, press [Menu] and select Logs. On the remote LCP, press [Logs]. 7.2 Event Log The Event Log stores details…
-
8 LCP and Feedback
e77ha715.10 8.1 Local LCP and Feedback 1 READY RUN TRIP LOCAL 2 3 Back Reset Menu Store 1 Four-line display for status and programming details. 3 Menu navigation keys: Illustration 18: Back: Exit the menu or parameter, or cancel a parameter change. This key also resets a trip. Menu/Store: Enter a…
-
If the remote LCP is not selected as the command source, [Start], [Stop], and [Reset] have no effect. • The menu navigation keys and display on the remote LCP are always active. • If a key is pressed on the remote LCP, the display on the remote LCP updates to match. NOTICE The remote LCP can be…
-
3 Menu
navigation keys: Back: Exit the menu or parameter, or cancel a parameter change. Menu/Store: Enter a menu or parameter, or save a parameter change. Arrow keys: Scroll to the next or previous menu or parameter, change the setting of the current parameter, or scroll through the status screens. 5 Local…
-
LED name
On Flashing Trip The soft starter has tripped. The soft starter is in warning state. Local The soft starter is controlled via a remote LCP. – If all LEDs are off, the soft starter is not receiving control voltage. 8.5 Displays 8.5.1 Soft Starter Information e77ha790.10 At power-up, the soft starter…
-
1 Mains Frequency
59.7 Hz 1.01 2 Motor pf 3 Motor power 37.0 kW 4 Motor Temp 85% e77ha792.10 Operating Guide | VLT® Soft Starter MCD 600 1 Parameter 10-10 User Parameter 3 (default: Mains frequency) 2 Parameter 10-11 User Parameter 4 (default: Power factor) 3 Parameter 10-12 User Parameter 5 (default: Motor running…
-
000.0 A
0-400% LCP and Feedback e77ha757.10 Operating Guide | VLT® Soft Starter MCD 600 If a remote LCP is connected, press [Graph] to change the graph data. The graph can show: • Motor current. • Motor temperature. • Motor power factor. • Analog input data from the smart card (if installed). Danfoss A/S ©…
-
9 Operation
9.1 Start, Stop, and Reset Commands The VLT® Soft Starter MCD 600 can be started and stopped via the digital inputs, remote LCP, communication network, smart card, or scheduled auto-start/stop. The command source can be set via the Set-up Tools, or using parameter 1-1 Command Source. • The MCD 600…
-
Parameter 4-1 Auto-Start/Stop Mode must be set to Enable. • Parameter 1-1 Command Source must be set to Timer. • The reset input must be closed. • The first start must be commanded by a start signal. Timer mode operation is controlled by parameters 4-2 to 4-3. 9.4 PowerThrough PowerThrough allows…
-
NOTICE
REDUCED EQUIPMENT LIFETIME Continued use of emergency mode is not recommended. Emergency mode may compromise the soft starter and/or motor life as all protections and trips are disabled. Using the soft starter in emergency mode voids the product warranty. - Do not run the soft starter in emergency…
-
Application
Start mode Start ramp time [s] Initial current (%FLC) Current limit (%FLC) Stop mode Stop time [s] Crusher - cone Constant current Coast to stop n/a Crusher - jaw Constant current Coast to stop n/a Crusher - rotary Constant current Coast to stop n/a Debarker Constant current Coast to stop n/a Fan…
-
e77ha505.10
Operating Guide | VLT® Soft Starter MCD 600 % 3 Current (% motor full load current) Rotor speed (% full speed) 80 1 Initial current (set in parameter 2-3 Initial Current) 90 % 100 2 Current limit (set in parameter 2-4 Current Limit) 3 Full voltage current Illustration 26: Example of Constant Current…
-
e77ha506.10
Operating Guide | VLT® Soft Starter MCD 600 Current (% motor full load current) % % Time Parameter 2-3 Initial Current 2 Parameter 2-2 Start Ramp Time 3 Parameter 2-4 Current Limit 4 Full voltage current Illustration 27: Example of Current Ramp Soft Starting 9.8.3 Adaptive Control for Starting In an…
-
9.8.3.1 Fine-tuning Adaptive Control
If the motor does not start or stop smoothly, adjust parameter 2-12 Adaptive Control Gain. The gain setting determines how much the soft starter adjusts future adaptive control starts and stops, based on information from the previous start. The gain setting affects both starting and stopping…
-
9.9 Stop Methods
9.9.1 Coast to Stop Coast to stop lets the motor slow at its natural rate with no control from the soft starter. The time required to stop depends on the type of load. 9.9.2 Timed Voltage Ramp Timed voltage ramp (TVR) reduces the voltage to the motor gradually over a defined time. This can extend…
-
NOTICE
Adaptive control controls the motor's speed profile, within the programmed time limit. This may result in a higher level of current than traditional control methods. 4 Speed e77ha510.10 If replacing a motor connected to a soft starter programmed for adaptive control starting or stopping, the soft…
-
NOTICE
MOTOR DAMAGE If the brake torque setting is too high, the motor stops before the end of the brake time and the motor suffers unnecessary heating, which could result in damage. A high brake torque setting can also result in peak currents up to motor DOL being drawn while the motor is stopping.…
-
9.9.5 DC Brake with External Zero-speed Sensor
For loads which may vary between braking cycles, install an external zero-speed sensor to ensure that the soft starter ends DC braking at motor standstill. Using a sensor prevents unnecessary motor heating. Configure DC brake for the longest braking time required, and also set parameter 7-1 Input A…
-
e77ha729.10
Operating Guide | VLT® Soft Starter MCD 600 A2 1 1/L1 3/L2 2/T1 4/T2 5/L3 A7 A8 A9 COM+ DI-A 5 2 6/T3 23 K2 K2 K1 4 K1 M1 1 Three-phase supply 2 Motor terminals 3 Relay A output 4 K1/K2 coil supply 5 Programmable input A K1 Line contactor (Run) K2 Line contactor (Brake) A2 Zero-speed sensor…
-
Reverse torque/
Forward current (%FLC) Current 7 e77ha787.10 Operating Guide | VLT® Soft Starter MCD Torque Time 1 Parameter 11-1 Reverse Torque 2 Parameter 11-2 Reverse Time 3 Parameter 11-3 Forward Current Limit 4 Parameter 11-4 Forward Time 5 Parameter 11-6 Pump Stop Time 6 Cleaning cycle 7 Parameter 11-7 Pump…
-
e77ha795.10
Operating Guide | VLT® Soft Starter MCD 600 1 1/L1 3/L2 2/T1 4/T2 5/L3 A1 A2 A3 COM+ DI-A 3 2 6/T3 23 K2 K2 K1 5 K1 M 1 Three-phase supply 2 Motor terminals 3 Programmable input A (set=Reverse direction) 4 Relay output A (set=Reversing contactor) 5 K1/K2 coil supply K1 Forward run contactor K2…
-
The maximum available torque for jog forward is approximately 50–75% of motor FLT depending on the motor. When the motor is jogged in reverse, the torque is approximately 25–50% of FLT. Parameter 2-8 Jog Torque and parameter 3-10 Jog Torque-2 control how much of the maximum available jog torque the…
-
Adaptive control start
The soft starter performs a constant current start. Adaptive control stop The soft starter performs a TVR soft stop if parameter 2-10 Stop Times is >0 s. If parameter 2-10 Stop Times is set to 0 s, the soft starter performs a coast to stop. Jog The soft starter issues a warning with the error…
-
10 Programmable Parameters
10.1 Main Menu Use the Main Menu to view and change programmable parameters that control how the soft starter operates. To open the Main Menu, press [Main Menu] while viewing the monitoring screens. 10.2 Changing Parameter Values Procedure 1. Scroll to the parameter in the Main Menu. 2. Press…
-
Parameter group number
Parameter group name Default setting 2-3 Initial Current 200% 2-4 Current Limit 350% 2-5 Adaptive Start Profile Constant Acceleration 2-6 Kickstart Time 000 ms 2-7 Kickstart Level 500% 2-8 Jog Torque 50% 2-9 Stop Mode TVR Soft Stop 2-10 Stop Time 00:00 (mm:ss) 2-11 Adaptive Stop Profile Constant…
-
Parameter group number
Parameter group name Default setting 3-19 Brake Current Limit-2 250% 3-20 Soft Brake Delay-2 400 s 4 Auto-Start/Stop 4-1 Auto-Start/Stop Mode Disable 4-2 Run Time 00:00 (hh:mm) 4-3 Stopped Time 00:00 (hh:mm) 4-4 Sunday Mode Start/Stop Disable 4-5 Sunday Start Time 00:00 (hh:mm) 4-6 Sunday Stop Time…
-
Parameter group number
Parameter group name Default setting 5-8 Undervoltage Delay 00:01 (mm:ss) 5-9 Overvoltage 500 V 5-10 Overvoltage Delay 00:01 (mm:ss) 5-11 Underpower 10% 5-12 Underpower Delay 00:01 (mm:ss) 5-13 Overpower 150% 5-14 Overpower Delay 00:01 (mm:ss) 5-15 Excess Start Time 00:20 (mm:ss) 5-16 Restart Delay…
-
Parameter group number
Parameter group name Default setting 7-3 Input A Trip Delay 00:00 (mm:ss) 7-4 Input A Initial Delay 00:00 (mm:ss) 7-5 Input B Function Input Trip (N/O) 7-6 Input B Trip Operating Only 7-7 Input B Trip Delay 00:00 (mm:ss) 7-8 Input B Initial Delay 00:00 (mm:ss) 7-9 Reset/Enable Logic Normally Closed…
-
Parameter group number
Parameter group name Default setting 10-10 User Parameter 3 Mains Frequency 10-11 User Parameter 4 Motor pf 10-12 User Parameter 5 Motor Power 10-13 User Parameter 6 Motor Temp (%) 11 Pump Clean 11-1 Reverse Torque 20% 11-2 Reverse Time 00:10 (mm:ss) 11-3 Forward Current Limit 100% 11-4 Forward Time…
-
Parameter group number
Parameter group name Default setting 20-1 Tracking Gain 50% 20-2 Pedestal Detect 80% 20-3 Bypass Contactor Delay 150 ms 20-4 Model Rating Model dependent 20-5 Screen Timeout 1 minute 20-6 Motor Connection Auto-detect 30 Pump Input Configuration 30-1 Pressure Sensor Type None 30-2 Pressure Units kPa…
-
Parameter group number
Parameter group name Default setting 33-1 Pressure Control Mode Off 33-2 Start Pressure Level 5 33-3 Start Response Delay 00:00:500 (mm:ss:ms) 33-4 Stop Pressure Level 10 33-5 Stop Response Delay 00:00:500 (mm:ss:ms) 34 Depth Protection 34-1 Depth Trip Level 5 34-2 Depth Reset Level 10 34-3 Depth…
-
Function
Smart card + clock The soft starter accepts start commands from the smart card if they are within the operating schedule set in parameters 4-1 to 4-24. A stop command from the smart card is accepted regardless of the schedule. Timer After a start signal is received, the soft starter starts and stops…
-
10.6 Parameter Group 2-** Motor Start/Stop
Table 27: 2-1 - Start Mode Option Function Selects the soft start mode. NOTICE The VLT® Soft Starter MCD 600 applies the current limit on all soft starts, including adaptive control. If the current limit is too low or the start ramp time (parameter 2-2 Start Ramp Time) is too short, the motor may…
-
Table 32: 2-6 - Kickstart Time
Range Function *0000 ms 0–2000 ms Sets the kickstart duration. A setting of 0 disables kickstart. Table 33: 2G - Kickstart Level Range * 500% Function 100–700% FLC Sets the level of the kickstart current. NOTICE Kickstart subjects the mechanical equipment to increased torque levels. Ensure that the…
-
Function
Late Deceleration Table 38: 2-12 - Adaptive Control Gain Range Function * 75% 1–200% Adjusts the performance of adaptive control. This setting affects both starting and stopping control. Table 39: 2-13 - Multi Pump Option Function Adjusts the performance of adaptive control to suit installations…
-
See 9.14 Secondary Motor Set for more details
Table 45: 3-1 - Motor Full Load Current-2 Range Function Model dependent Sets the secondary motor's full load current. Table 46: 3-2 - Motor kW-2 Range *0 Function 0–9999 kW Sets the running power of the secondary motor in kW. Table 47: 3-3 - Start Mode-2 Option Function Selects the soft start mode.…
-
Table 51: 3-7 - Adaptive Start Profile-2
Option Function Selects which profile the VLT® Soft Starter MCD 600 uses for an adaptive control soft start. Early Acceleration * Constant Acceleration Late Acceleration Table 52: 3-8 - Kickstart Time-2 Range Function * 0000 ms 0–2000 ms Sets the kickstart duration. A setting of 0 disables…
-
Table 57: 3-13 - Adaptive Stop Profile-2
Option Function Selects which profile the soft starter uses for an adaptive control soft stop. Early Deceleration * Constant Deceleration Late Deceleration Table 58: 3-14 - Adaptive Control Gain-2 Range *75% Function 1–200% Adjusts the performance of adaptive control. This setting affects both…
-
Table 64: 3-20 - Soft Brake Delay-2
Range Function *400 ms 400–2000 ms Sets the time which the soft starter waits after a stop signal is received, before it begins to supply braking current to the motor. Set to allow time for K1 and K2 to switch. 10.8 Parameter Group 4-** Auto-Start/Stop Table 65: 4-1 - Auto-Start/Stop Mode Option…
-
Table 71: 4-7 - Monday Mode
Option Function Enables or disables auto-start/stop for Monday. * Start/Stop Disable Stop Only Enable Start Only Enable Start/Stop Enable Table 72: 4-8 - Monday Start Time Range Function *00:00 00:00–23:59 Sets the auto-start time for Monday (24-hour format). Table 73: 4-9 - Monday Stop Time Range…
-
Table 78: 4-15 - Wednesday Stop Time
Range *00:00 Function 00:00–23:59 Sets the auto-stop time for Wednesday (24-hour format). Table 79: 4-16 - Thursday Mode Option Function Enables or disables auto-start/stop for Thursday. * Start/Stop Disable Start Only Enable Stop Only Enable Start/Stop Enable Table 80: 4-17 - Thursday Start Time…
-
Table 85: 4-22 - Saturday Mode
Option Function Enables or disables auto-start/stop for Saturday. * Start/Stop Disable Start Only Enable Stop Only Enable Start/Stop Enable Table 86: 4-23 - Saturday Start Time Range *00:00 Function 00:00–23:59 Sets the auto-start time for Saturday (24-hour format). Table 87: 4-24 - Saturday Stop…
-
Table 92: 5-5 - Overcurrent
Range *400% Function 80–600% Sets the trip point for overcurrent protection as a percentage of motor full load current. Table 93: 5-6 - Overcurrent Delay Range *0s Function 0:00–1:00 (minutes:seconds) Slows the soft starter's response to overcurrent, avoiding trips due to momentary overcurrent…
-
Table 100: 5-13 - Overpower
Range Function *150% 80–200% Sets the trip point for overpower protection. Set as required. Table 101: 5-14 - Overpower Delay Range *1s Function 0:00–1:00 (minutes:seconds) Slows the soft starter's response to overpower, avoiding trips due to momentary fluctuations. Table 102: 5-15 - Excess Start…
-
10.10 Parameter Group 6-** Protection Action
Table 106: 6-1 - Auto-Reset Count Range Function *0 Sets how many times the soft starter auto-resets if it continues to trip. 0–5 The reset counter increases by 1 each time the soft starter auto-resets, and resets after a successful start. Setting this parameter to 0 disables auto-reset. Table 107…
-
Table 110: 6-5 - Overcurrent
Option Function Selects the soft starter's response to the protection event. * Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Table 111: 6-6 - Undervoltage Option Function Selects the soft starter's response to the protection event. * Soft Trip and Log Soft…
-
Function
Trip and Reset Warn and Log * Log Only Table 114: 6-9 - Overpower Option Function Selects the soft starter's response to the protection event. Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log * Log Only Table 115: 6-10 - Excess Start Time Option Function Selects the…
-
Table 117: 6-12 - Input B Trip
Option Function Selects the soft starter's response to the protection event. * Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Table 118: 6-13 - Network Communications Option Function Selects the soft starter's response to the protection event. If set to Stop…
-
Function
Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Table 121: 6-16 - Phase Sequence Option Function Selects the soft starter's response to the protection event. * Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Table 122: 6-17 - Motor…
-
Table 124: 6-19 - Shorted SCR Action
Option Function Selects whether the soft starter allows PowerThrough operation, if the soft starter is damaged on 1 phase. The soft starter uses 2-phase control, allowing the motor to continue operating in critical applications. * 3-phase Control Only PowerThrough For more details on PowerThrough…
-
Function
Motor Set Select A closed circuit across DI-A, COM+ instructs the soft starter to use the secondary motor configuration for the next start/stop cycle. Reverse Direction A closed circuit across DI-A, COM+ instructs the soft starter to reverse the phase sequence for the next start. Pump Clean…
-
Table 131: 7-6 - Input B Trip
Option Function Selects when an input trip can occur. Always Active * Operating Only Run Only Table 132: 7-7 - Input B Trip Delay Range *0s Function 0:00–4:00 (minutes:seconds) Sets a delay between the input activating and the soft starter tripping. Table 133: 7-8 - Input B Initial Delay Range *0s…
-
Function
Starter Disable Controller PLC Vibration Alarm Field Trip Interlock Trip Motor Temp Motor Prot Feeder Prot Custom Message Table 136: 7-11 - Input B Name Option Function Selects a message for the LCP to show when Input B is active. * Input B Trip Low Pressure High Pressure Pump Fault Low Level High…
-
10.12 Parameter Group 8-** Relay Outputs
Table 137: 8-1 - Relay A Function Option Function Selects the function of Relay A. Relay A is a changeover relay. * Off Relay A is not used. Ready The relay is closed when the soft starter is in Ready state. Run The Run output closes when the soft start is complete (when the starting current drops…
-
Function
Trip Low Current Flag High Current Flag Motor Temperature Flag Soft Brake Relay Reversing Contactor Table 141: 8-5 - Relay B On Delay Range *0s Function 0:00–5:00 (minutes:seconds) Sets the delay for closing Relay B. Table 142: 8-6 - Relay B Off Delay Range *0s Function 0:00–5:00 (minutes:seconds)…
-
Table 146: 8-10 - Main Contactor Time
Range Function *400 ms 100–2000 ms Sets the delay period between the soft starter switching the main contactor output (terminals 13, 14) and beginning the pre-start checks (before a start), or entering the not-ready state (after a stop). Set according to the specifications of the main contactor…
-
Programmable Parameters Function English Chinese Español Deutsch Português Français Italiano Russian Table 152: 10-2 - Temperature Scale Option Function Selects whether the soft starter shows temperatures in degrees Celsius or Fahrenheit. * Celsius Fahrenheit Table 153: 10-3 - Graph Timebase Option…
-
Table 156: 10-6 - Current Calibration
Range *100% Function 85– 115% Calibrates the soft starter's current monitoring circuits to match an external current metering device. Use the following formula to determine the necessary adjustment: Calibration ( % ) = Table 157: 10-7 - Adjustment Lock Option Current shown on soft starter display…
-
Function
Heat Sink Temperature The soft starter's temperature measured at the heat sink. Bypass Model (%) The percentage of thermal capacity remaining in the bypass contactor. SCR Temperature The temperature of the SCRs calculated by the thermal model. Rating Capacity (%) The thermal capacity available in…
-
10.15 Parameter Group 11-** Pump Clean
Table 164: 11-1 - Reverse Torque Range Function * 20% 20–100% Sets the torque level for reverse jog operation during pump clean. Table 165: 11-2 - Reverse Time Range * 10 s Function 0:00–1:00 (minutes:seconds) Sets the time for the starter to operate in reverse jog during a pump clean cycle. Table…
-
Table 172: 12-2 - Modbus Baud Rate
Option Function Selects the baud rate for Modbus RTU communications. 4800 * 9600 19200 38400 Table 173: 12-3 - Modbus Parity Option Function Selects the parity for Modbus RTU communications. * None Odd Even 10-bit Table 174: 12-4 - Modbus Timeout Option Function Selects the timeout for Modbus RTU…
-
Table 177: 12-7 - PROFIBUS Address
Range *1 Function 1–125 Sets the PROFIBUS network address for the soft starter. Table 178: 12-8 - Gateway Address Range *192 Function 0–255 Sets the 1st component of the network gateway address. The gateway address is set using parameters 12-8 to 12-11 and the default address is 192.168.0.100. Table…
-
Table 185: 12-15 - IP Address 4
Range Function *2 Sets the 4th component of the soft starter's IP address for Ethernet communications. 0–255 NOTICE The network address can also be set via the Network Address options in the Set-up Tools. Table 186: 12-16 - Subnet Mask Range *255 Function 0–255 Sets the 1st component of the network…
-
Table 191: 12-21 - Location ID
Range *0 Function 0–65535 Sets the soft starter's unique location ID. 10.17 Parameter Group 20-** Advanced Table 192: 20-1 - Tracking Gain Range *50% Function 1–200% Fine-tunes the behavior of the adaptive control algorithm. Table 193: 20-2 - Pedestal Detect Range * 80% Function 0–200% Adjusts the…
-
Function
2 minutes 3 minutes 4 minutes 5 minutes Table 197: 20-6 - Motor Connection Option Function Selects whether the soft starter automatically detects the format of the connection to the motor. * Auto-detect In-line Inside delta 10.18 Parameter Group 30-** Pump Input Configuration Table 198: 30-1…
-
Table 202: 30-5 - Flow Sensor Type
Option Function Selects which type of sensor is associated with the flow sensor input on the smart card. * None Switch Analog Pulses per minute Pulses per unit Table 203: 30-6 - Flow Units Option Function Selects which units the sensor uses to report the measured flow. * liters/second liters/minute…
-
Table 209: 30-12 - Depth Sensor Type
Option Function Selects which type of sensor is associated with the depth sensor input on the smart card. * None Switch Analog Table 210: 30-13 - Depth Units Option Function Selects which units the sensor uses to report the measured depth. * meters feet Table 211: 30-14 - Depth at 4 mA Range *0…
-
Table 215: 31-3 - Flow Start Delay
Range Function *00:00:500 ms 00:00:100– 30:00:000 mm:ss:ms Sets a delay before a flow protection trip can occur. The delay is counted from the time a start signal is received. The flow level is ignored until the start delay has elapsed. Table 216: 31-4 - Flow Response Delay Range Function *…
-
Table 221: 32-5 - Low Pressure Start Delay
Range * 0.5 s Function 00:00:100– 30:00:000 mm:ss:ms Sets a delay before a low-pressure protection trip can occur. The delay is counted from the time a start signal is received. The pressure is ignored until the start delay has elapsed. Table 222: 32-6 - Low Pressure Response Delay Range * 0.5 s…
-
Table 227: 33-5 - Stop Response Delay
Range * 0.5 s Function 00:00:100–30:00:000 mm:ss:ms Sets a delay between the pressure passing the pressure control stop level and the soft starter stopping the motor. 10.22 Parameter Group 34-** Depth Protection NOTICE The parameters in this group are only active if a smart card is installed. Depth…
-
Table 232: 35-1 - Temperature Sensor Type
Option Function Selects which type of sensor is associated with the temperature sensor input on the smart card. * None PT100 Table 233: 35-2 - Temperature Trip Level Range * 40 ° Function 0–240 ° Sets the trip point for temperature protection. Use parameter 10-2 Temperature Scale to configure the…
-
Function
Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Table 237: 36-4 - High Pressure Option Function Selects the soft starter's response if the pressure exceeds the high-pressure trip level (parameter 32-1 High Pressure Trip Level) or the high-pressure switch sensor closes. * Soft…
-
Function
Log Only Table 240: 36-7 - Low Flow Option Function Selects the soft starter's response if the flow drops below the low flow trip level (set in parameter 31-2 Low Flow Trip Level). * Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Table 241: 36-8 - Flow Switch…
-
Option Function Selects the soft starter's response to the protection event. * Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only 120 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174
-
11 Application Examples
11.1 Smart Card - Pump Control and Protection The VLT® Soft Starter MCD 600 smart card is ideal for applications with extensive external inputs, such as pumping situations where external sensors provide extra protection to the pump and motor. 1 READY RUN TRIP RESET RESET 4 LOGS DI-A DI-B A B C K1 14…
-
B Manual stop
C Automatic operation (scheduled start/stop) K1 Main contactor RESET, COM+ Reset input START, COM+ Start/stop input DI-A, COM+ Programmable input A (set = Command Override: Digital) 13, 14 Main contactor output B33, B34 Flow protection B13, B14 Depth protection Illustration 37: R1, R2, R3 Motor…
-
RESET DI-A DI-B A B C K1 14 13 A9 A7 A8 2 3 F1 C44 C43 C34 C33 C24 C23 C14 C13 R3 R2 R1 4/20mA INPUTS START RTD A B C 4 DIGITAL INPUTS COM+ e77ha744.10 Operating Guide | VLT® Soft Starter MCD 600 B34 B33 B24 B23 B14 B13 1/L1 2/T1 3/L2 4/T2 5/L3 6/T3 K1 1 Digital inputs 2 Control voltage 3…
-
12 Troubleshooting
12.1 Protection Responses When a protection condition is detected, the soft starter writes this to the event log and may also trip or issue a warning. The soft starter's response depends on the settings in parameter group 6-** Protection Action. Some protection responses cannot be adjusted by the…
-
12.2.4 Current Imbalance
Cause • An imbalance in the incoming mains voltage. • A problem with the motor windings. • A light load on the motor. • A phase loss on mains terminals L1, L2, or L3 during Run mode. • An SCR that has failed open circuit. A failed SCR can only be diagnosed accurately by replacing the SCR and…
-
12.2.8 Excess Start Time
Cause • Parameter 1-2 Motor Full Load Current is not appropriate for the motor. • Parameter 2-4 Current Limit has been set too low. • Parameter 2-2 Start Ramp Time has been set greater than the setting for parameter 5-15 Excess Start Time. • Parameter 2-2 Start Ramp Time is set too short for a high…
-
12.2.12 Flow Switch
Cause The flow switch sensor (smart card terminals C23, C24) has closed. Troubleshooting • Check the following parameters: - Parameter 30-5 Flow Sensor Type. - Parameter 36-8 Flow Switch. 12.2.13 Frequency Cause This trip is not adjustable. The mains frequency is outside of the specified range.…
-
Check the following parameters: - Parameter 30-5 Flow Sensor Type. - Parameter 30-7 Flow at 4 mA. - Parameter 30-8 Flow at 20 mA. - Parameter 31-1 High Flow Trip Level. - Parameter 31-3 Flow Start Delay. - Parameter 31-4 Flow Response Delay. - Parameter 36-6 High Flow. 12.2.16 High Pressure Cause…
-
12.2.18 Instant Overcurrent
Cause This trip is not adjustable. The current on all 3 phases has exceeded 7.2 times the value of parameter 1-2 Motor Full Load Current. Causes can include a locked rotor condition or an electrical fault in the motor or cabling. Troubleshooting • Check for jammed loads. • Check for faults in the…
-
• For the soft starter and the motor, check - The supply connections. - The input connections. - The output connections. There are no parameters related to this trip message. 12.2.23 L1-T1/L2-T2/L3-T3 Shorted Cause During pre-start checks, the soft starter has detected a short-circuited SCR or a…
-
12.2.26 Low Pressure
Cause The pressure sensor connected to the smart card has activated low-pressure protection. Troubleshooting • Check the following parameters: - Parameter 30-1 Pressure Sensor Type. - Parameter 30-3 Pressure at 4 mA. - Parameter 30-4 Pressure at 20 mA. - Parameter 32-4 Low Pressure Trip Level.…
-
12.2.29 Motor Overload
Cause The motor has reached its maximum thermal capacity. The following can cause overload: • The soft starter protection settings do not match the motor thermal capacity. • Excessive starts per hour or start duration. • Excessive current. • Damage to the motor windings. Troubleshooting • • Resolve…
-
12.2.31 Network Communication
Cause The network master has sent a trip command to the soft starter, or there could be a network communication problem. Check the network for causes of communication inactivity. Troubleshooting • Check the following parameter: - Parameter 6-13 Network Communications. 12.2.32 Not Ready Cause • The…
-
12.2.35 Overvoltage
Cause There has been a voltage surge on the mains. Causes can include problems with a transformer tap regulator of off-loading of a large transformer load. Troubleshooting • Check the following parameters: - Parameter 5-9 Overvoltage. - Parameter 5-10 Overvoltage Delay. - Parameter 6-7 Overvoltage.…
-
Check that the main contactor closes when a start command is given and remains closed until the end of a soft stop. • Check the fuses. If testing the soft starter with a small motor, it must draw at least 10% of the programmed FLC setting on each phase. • There are no parameters related to this trip…
-
12.2.43 SCR Overtemperature
Cause The temperature of the SCRs, calculated by the thermal model, is too high to allow further operation. Troubleshooting • Wait for the soft starter to cool. • There are no parameters related to this trip message. 12.2.44 Starter Communication Cause There is a problem with the connection between…
-
12.2.47 Time - Overcurrent
Cause The soft starter is internally bypassed and has drawn high current during running. (The 10 A protection curve trip has been reached, or the motor current has risen to 600% of the motor FLC setting.) Related parameters: None. 12.2.48 Undercurrent Cause The motor has experienced a sharp drop in…
-
12.2.52 VZC Fail Px
Cause Where X is 1, 2, or 3. Internal fault (PCB fault). Contact the local Danfoss supplier for advice. Related parameters: None. 12.2.53 Zero Speed Detect Cause The zero-speed detect input has not closed within the expected duration of a soft stop. Troubleshooting • Check that the zero-speed sensor…
-
Symptom
Probable cause/suggested solution The soft starter does not respond to a start command from either the LCP or the digital inputs. • The soft starter may be waiting for the restart delay to elapse. Parameter 5-16 Restart Delay controls the length of the restart delay. • The motor may be too hot to…
-
Symptom
Probable cause/suggested solution USB full • The USB drive may not have enough free space available for the selected function. • The file system on the USB drive may not be compatible with the soft starter. The VLT® Soft Starter MCD 600 supports FAT32 file systems. The USB functions of the MCD 600…
-
Appendix
Operating Guide | VLT® Soft Starter MCD 600 13 Appendix 13.1 Symbols and Abbreviations °C Degrees Celsius °F Degress Fahrenheit AC Alternating current CT Current transformer DC Direct current DOL Direct on-line EMC Electromagnetic campatibility FLA Full load amperage FLC Full load current FLT Full…
-
144 | Danfoss A/S © 2018.10
AQ262141844215en-000202 / 175R1174
-
Danfoss A/S © 2018.10
AQ262141844215en-000202 / 175R1174 | 145
-
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being…