Инструкция на Преобразователь частоты Danfoss серии VLT Decentral Drive FCD 302
Преобразователь частоты Danfoss серии VLT Decentral Drive FCD 302. Инструкция по эксплуатации.
Загружаем документ…
Текст инструкции
-
MAKING MODERN LIVING POSSIBLE
Operating Instructions VLT® Decentral Drive FCD 302
-
1 Introduction
5 1.1 Introduction 5 1.2 Safety 5 1.3 Purpose of the Manual 5 1.4 Additional Resources 6 1.5 Product Overview 6 1.6 Internal Frequency Converter Controller Functions 6 1.7 Type Code Description 7 2 Installation 9 2.1 Check List 9 2.2 Exploded View of the FCD 302 10 2.3 Mechanical Installation 12…
-
3.1.1 Safety Inspection
29 3.1.2 Start Up Check List 29 3.2 Applying Power to the Frequency Converter 30 3.3 Quick Setup 30 3.4 Automatic Motor Adaptation 31 3.5 Local-control Test 32 3.6 System Start Up 32 4 User Interface 33 4.1 Local Control Panel 33 4.1.1 LCP Layout 33 4.1.2 Setting LCP Display Values 34 4.1.3 Display…
-
Contents | Illustration
Illustration 1.1: Frequency Converter Block Diagram 6 Illustration 2.1: Exploded View Small Unit 10 Illustration 2.2: Exploded View Large Unit 11 Illustration 2.3: Cable Entries and Hole Sizes (Small Unit) 12 Illustration 2.4: Cable Entries and Hole Sizes (Large Unit) 12 Illustration 2.5: Top and…
-
Contents | Table
Table 1.1: Frequency Converter Internal Components 7 Table 1.2: Type Code Description 8 Table 2.1: 4xM12 Connection Input 21 Table 2.2: 2xM12 Connection Output 21 Table 3.1: Start Up Check List 30 Table 6.1: LED Status 64 Table 7.1: Alarm/Warning Code List 69 Table 7.2: Description of Alarm Word…
-
Introduction
Introduction WARNING 1.1 Introduction UNINTENDED START 1.1.1 Approvals When the frequency converter is connected to the AC mains, start the motor using an external switch, a serial bus command, an input reference signal, or a cleared fault condition. Use appropriate precautions to guard against an…
-
1.4 Additional Resources Other resources are available to understand advanced frequency controller functions and programming. • • • • • The FCD 302 Programming Guide, MG04GXYY, provides greater detail in how to work with parameters and many application examples. The FCD 302 Design Guide, MG04HXYY…
-
Introduction
Area Title Functions Area Title Functions 7 By controlling the voltage and frequency, the frequency converter provides regulated motor control from 0-50/60 Hz at 100% supply voltage. 8 • Output to motor Control circuitry 1 1 Input power, internal processing, output, and motor current are monitored…
-
VLT® Decentral Drive FCD 302 Operating Instructions Introduction Position Description 24 Choices/options X No sensor plugs E Direct mount 4xM12: 4 digital inputs F Direct mount 6xM12: 4 digital inputs, 2 relay outputs Sensor plugs 25 Motor plug X No motor plug 26 Mains plug X No mains plug X No…
-
2 Installation
2 2 2.1 Check List The packaging contains: • Accessories bag, supplied only with order of installation box. Contents: 2 cable clamps bracket for motor/loads cables elevation bracket for cable clamp screw 4 mm 20 mm thread forming 3.5 mm 8 mm • • Documentation Frequency converter Depending on options…
-
2.2 Exploded View of the FCD 302
130BC379.10 Illustration 2.1 Exploded View Small Unit 1 Inverter part 6 Installation box 2 Fastening screws (4 x, one in each corner) 7 Display connection 3 Sealing gasket 8 Access to USB port 4 Inverter part plastic cover 9 Service switch-motor side (alternatively, switch located on mains side, or…
-
Illustration 2.2 Exploded View Large Unit
1 Inverter part 7 Display connection 2 Fastening screws (4 x, one in each corner) 8 Access to USB port 3 Sealing gasket 9 Service switch*-motor side (alternatively, switch located on mains side, or not mounted) 4 Inverter part plastic cover 10 Flat mounting brackets 5 Ground connection pin 11…
-
2.3 Mechanical Installation
2.3.1 Recommended Tools and Equipment Equipment Size Description Socket (Hex) 8 For fastening inverter screws/mounting of brackets Slotted 0.4x2.5 For spring loaded power and control terminals Slotted/Torx 1.0x5.5/TX20 For cable clamps inside the installation box Spanner 19, 24, 28 Screwdrivers For…
-
195NA261.10
100 (4) 130BB701.10 VLT® Decentral Drive FCD 302 Operating Instructions Installation 100 (4) 100 (4) Illustration 2.6 FCD 302 Stand Alone Mounted with Mounting Brackets 100 (4) Permitted mounting positions 130BC382.10 Illustration 2.5 Top and Bottom Cooling Clearance 2.3.4 Mounting The FCD 302…
-
2.3.4.1 Hygienic Installation
2.3.4.2 Cleaning The FCD 302 is designed according to the EHEDG guidelines, suitable for installation in environments with high focus on cleanability. The enclosure (IP66/NEMA type 4x indoor) provides protection against dirt and water ingress. The enclosure is suitable for cleaning methods and…
-
3 phase
-
130BC286.10
Installation L1 1 L1 T1 2 L2 3 L2 T2 4 L3 5 L3 T3 6 PE 33 NO NO 34 L1 91 L2 92 L3 NC NC 42 27 U 96 V 97 W 98 Illustration 2.10 Large Unit only: Circuit Breaker and Mains Disconnect 1 Looping terminals 130BC287.10 2 Circuit breaker 1 L1 L2 L3 PE L1 91 L2 92 L3 93 12 U 96 V 97 W 98 • Overload and…
-
2.4.2 Location of Terminals
2 2 Illustration 2.12 Location of Terminals (Small Unit) Illustration 2.13 Location of Terminals (Large Unit) 1 Digital and analog inputs/outputs 8 USB port 2 Safe stop, LCP connection, B-option 9 Standard bus/RS-485 3 Relay 1 10 Profibus 4 Relay 2 11 Ethernet port 5 Motor, mechanical brake, brake…
-
For both small and large unit, the service switch is
optional. The switch is shown mounted on the motor side. Alternatively, the switch can be located on the mains side, or omitted. For the large unit, the circuit breaker is optional. The large unit can be configured with either service switch or circuit breaker, not both. The illustration shown is…
-
NOTE
• Installations with cables connected in a common • • It is recommended that control wiring is rated for 600 V. joint as in Illustration 2.15, is only recommended for short cable lengths (max. 10 m). • Isolate control wiring from high-power components in the frequency converter. When motors are…
-
2.4.7 Motor and Mains Connection with
Service Switch Terminal No. Function 62 RxD/TxD –P (red cable) for Profibus. See dedicated literature (MCA 101) for details. 63 RxD/TxD –N (green cable) for Profibus. 66 0 V for Profibus. 67 +5 V for Profibus. B01-B12 B-option. See dedicated literature for details. G, R, V, N, P Connection of LCP.…
-
2 2 When the frequency converter enters alarm mode or is exposed to an over-voltage situation, the mechanical brake immediately cuts in. For more detailed information, refer to the FCD 302 Programming Guide, MG04GXYY. NOTE When the Mechanical Brake Control/Supply terminals 122 and 123 are set…
-
CAUTION
PE CONNECTION The metal pins in the corners of the electronic part and the holes on the corner of the installation box are essential for the protective earth connection. Make sure that they are not loosened, removed, or violated in any way. Tightening torque requirement is 3 Nm. See Illustration…
-
Grounding shielded cable
Earthing (grounding) clamps are provided for motor and control wiring (see Illustration 2.17). 2 2 130BC390.10 Illustration 2.17 Earthing (Grounding) Clamp for Motor and Control Wiring (Small Unit) Illustration 2.18 Earthing (Grounding) Clamp for Motor and Control Wiring (Large Unit) MG04F302 - VLT®…
-
Use a wire stripper to remove the insulation for
proper grounding. 2. Secure the grounding clamp to the stripped portion of the wire with the screws provided. 3. Secure the grounding wire to the grounding clamp provided. PE PE Follow national and local codes regarding protective earthing of equipment with a leakage current > 3.5 mA. The frequency…
-
130BB708.10
Installation 2 1 • • 3 4 Selecting a specific communication protocol changes various default parameter settings to match that specifications of the protocol along with making additional protocol-specific parameters available Control card options are available to provide additional communication…
-
activated, the frequency converter issues an alarm, trips
the unit, and coasts the motor to a stop. Manual restart is required. The safe stop function can be used for stopping the frequency converter in emergency stop situations. In the normal operating mode when safe stop is not required, use the regular stop function of the frequency converter instead.…
-
Illustration 2.21 Jumper between Terminal 13 and 37
-
M Illustration 2.22 Installation to Achieve a Stopping Category 0 (EN 60204-1) with Safety Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1). 1 Safety device Cat. 3 (circuit interrupt device, possibly with release input) 7 Inverter module 2 Door contact 8 Motor 3 Contactor (Coast) 9 5 V DC 4 Frequency…
-
Start Up and Functional Tes
VLT® Decentral Drive FCD 302 Operating Instructions 3 Start Up and Functional Testing 3.1.2 Start Up Check List 3.1 Pre-start 3.1.1 Safety Inspection Before applying power to the unit, inspect the entire installation as detailed in Table 3.1. WARNING HIGH VOLTAGE If input and output connections have…
-
Inspect for
Description Input and output power wiring • • Check for proper fusing or circuit Switches Ensure that all switch and disconnect settings are in the proper position. Grounding The equipment requires a dedicated ground wire from its chassis to the plant ground. Check for good ground connections that…
-
Start Up and Functional Tes
1-22 Motor Voltage 1-23 Motor Frequency 1-24 Motor Current 1-25 Motor Nominal Speed 4. Continue set-up of Quick Menu parameters: 5-12 Terminal 27 Digital Input. If terminal default is Coast inverse it is possible to change this setting to No function. 1-29 Automatic Motor Adaptation (AMA). Set…
-
VLT® Decentral Drive FCD 302 Operating Instructions Start Up and Functional Tes... 3.6 System Start Up 3.5 Local-control Test WARNING MOTOR START Ensure that the motor, system, and any attached equipment are ready for start. Failure to ensure that the motor, system, and any attached equipment are…
-
130BC362.10
4 User Interface 4.1 Local Control Panel The LCP is the combined display and keypad. The LCP can be attached to the display connector outside the unit (without opening the enclosure) via the LCP cable/plug. The LCP is the user interface to the frequency converter. Status 1234rpm 1(1) 43,5Hz 1.0 A 4…
-
4.1.3 Display Menu Keys
The display area is activated when the frequency converter receives power from mains voltage, or an external 24 V supply. Menu keys are used for menu access for parameter set-up, toggling through status display modes during normal operation, and viewing fault log data. The information displayed on…
-
4.1.5 Operation Keys
Navigation keys are used for programming functions and moving the display cursor. The navigation keys also provide speed control in local (hand) operation. Three frequency converter status indicator lights are also located in this area. Operation keys are found at the bottom of the LCP. Ba l ce ck n…
-
4.2.1 Uploading Data to the LCP
4 4 1. Press [Off] to stop the motor before uploading or downloading data. 2. Go to 0-50 LCP Copy. 3. Press [OK]. 4. Select All to LCP. 5. Press [OK]. A progress bar shows the uploading process. 6. Press [Hand On] or [Auto On] to return to normal operation. 4.2.2 Downloading Data from the LCP 1.…
-
5 Programming
0-01 Language Option: 5.1 Introduction The frequency converter is programmed for its application functions using parameters. Parameters are accessed by pressing either [Quick Menu] or [Main Menu] on the LCP. (See 4 User Interface for details on using the LCP function keys.) Parameters may also be…
-
1-23 Motor Frequency
5-12 Terminal 27 Digital Input Range: Option: Function: Size related* Function: [20 1000 Hz] Min - Max motor frequency: 20-1000 Hz. Select the motor frequency value from the motor nameplate data. If a value different from 50 Hz or 60 Hz is selected, it is necessary to adapt the load independent…
-
Note
• For the best adaptation of the frequency converter, run AMA on a cold motor. • AMA cannot be performed while the motor is running. • AMA cannot be performed on permanent magnet motors. NOTE It is important to set motor parameter group 1-2* correctly, since these parameters form part of the AMA…
-
5.3 Parameter Lists
Changes during operation ”TRUE” means that the parameter can be changed while the frequency converter is in operation and “FALSE” means that it must be stopped before a change can be made. 0-** Operation and Display parameters for basic frequency converter settings 4-Set-up 'All set-up': the…
-
5.3.1 0-** Operation/Display
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 0-0* Basic Settings 0-01 Language [0] English 1 set-up TRUE - Uint8 0-02 Motor Speed Unit [0] RPM 2 set-ups FALSE - Uint8 0-03 Regional Settings [0] International 2 set-ups FALSE - Uint8 0-04…
-
5.3.2 1-** Load/Motor
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 1-0* General Settings 1-00 Configuration Mode null All set-ups TRUE - Uint8 1-01 Motor Control Principle null All set-ups FALSE - Uint8 1-02 Flux Motor Feedback Source [1] 24 V encoder All set-ups…
-
Par
No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 1-6* Load Depen. Setting 1-60 Low Speed Load Compensation 100% All set-ups TRUE 0 Int16 1-61 High Speed Load Compensation 100% All set-ups TRUE 0 Int16 1-62 Slip Compensation App.Dependent All set-ups…
-
5.3.3 2-** Brakes
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 2-0* DC-Brake 2-00 DC Hold Current 50% All set-ups TRUE 0 Uint8 2-01 DC Brake Current 50% All set-ups TRUE 0 Uint16 2-02 DC Braking Time 10.0 s All set-ups TRUE -1 Uint16 2-03 DC Brake Cut In Speed…
-
5.3.4 3-** Reference/Ramps
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 3-0* Reference Limits 3-00 Reference Range null All set-ups TRUE - Uint8 3-01 Reference/Feedback Unit null All set-ups TRUE - Uint8 3-02 Minimum Reference App.Dependent All set-ups TRUE -3 Int32…
-
Par
No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 3-8* Other Ramps 3-80 Jog Ramp Time App.Dependent All set-ups TRUE -2 Uint32 3-81 Quick Stop Ramp Time App.Dependent 2 set-ups TRUE -2 Uint32 3-82 Quick Stop Ramp Type [0] Linear All set-ups TRUE - Uint8…
-
5.3.5 4-** Limits / Warnings
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 4-1* Motor Limits 4-10 Motor Speed Direction null All set-ups FALSE - Uint8 4-11 Motor Speed Low Limit [RPM] App.Dependent All set-ups TRUE 67 Uint16 4-12 Motor Speed Low Limit [Hz] App.Dependent…
-
5.3.6 5-** Digital In/Out
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 5-0* Digital I/O mode 5-00 Digital I/O Mode [0] PNP All set-ups FALSE - Uint8 5-01 Terminal 27 Mode [0] Input All set-ups TRUE - Uint8 5-02 Terminal 29 Mode [0] Input All set-ups TRUE - Uint8 5-1*…
-
Par
No. # Parameter description VLT® Decentral Drive FCD 302 Operating Instructions Default value 4-set-up Change during operation Conversion index Type 5-6* Pulse Output 5-60 Terminal 27 Pulse Output Variable 5-62 Pulse Output Max Freq #27 5-63 Terminal 29 Pulse Output Variable 5-65 Pulse Output Max…
-
5.3.7 6-** Analog In/Out
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 6-0* Analog I/O Mode 6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint8 6-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8 6-1* Analog Input 1 6-10 Terminal 53 Low Voltage 0.07…
-
5.3.8 7-** Controllers
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 7-0* Speed PID Ctrl. 7-00 Speed PID Feedback Source null All set-ups FALSE - Uint8 7-02 Speed PID Proportional Gain App.Dependent All set-ups TRUE -3 Uint16 7-03 Speed PID Integral Time…
-
5.3.9 8-** Comm. and Options
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type Uint8 8-0* General Settings 8-01 Control Site [0] Digital and ctrl.word All set-ups TRUE - 8-02 Control Word Source null All set-ups TRUE - Uint8 8-03 Control Word Timeout Time 1.0 s 1 set-up TRUE…
-
5.3.10 9-** Profibus
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 9-00 9-07 Setpoint 0 N/A Actual Value 0 N/A All set-ups TRUE 0 Uint16 All set-ups FALSE 0 9-15 PCD Write Configuration Uint16 App.Dependent 1 set-up TRUE - 9-16 PCD Read Configuration Uint16…
-
5.3.11 13-** Smart Logic
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 13-0* SLC Settings 13-00 SL Controller Mode null 2 set-ups TRUE - Uint8 13-01 Start Event null 2 set-ups TRUE - Uint8 13-02 Stop Event null 2 set-ups TRUE - Uint8 13-03 Reset SLC [0] Do not reset…
-
5.3.12 14-** Special Functions
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 14-0* Inverter Switching 14-00 Switching Pattern null All set-ups TRUE - Uint8 14-01 Switching Frequency null All set-ups TRUE - Uint8 14-03 Overmodulation [1] On All set-ups FALSE - Uint8 14-04 PWM…
-
Par
No. # Parameter description VLT® Decentral Drive FCD 302 Operating Instructions Default value 4-set-up Change during operation Conversion index Type 14-7* Compatibility 14-72 Legacy Alarm Word 0 N/A All set-ups FALSE 0 Uint32 14-73 Legacy Warning Word 0 N/A All set-ups FALSE 0 Uint32 14-74 Leg. Ext.…
-
5.3.13 15-** Drive Information
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 15-0* Operating Data 15-00 Operating Hours 0h All set-ups FALSE 74 Uint32 15-01 Running Hours 0h All set-ups FALSE 74 Uint32 15-02 kWh Counter 0 kWh All set-ups FALSE 75 Uint32 15-03 Power Up's 0…
-
Par
No. # Parameter description VLT® Decentral Drive FCD 302 Operating Instructions Default value 4-set-up Change during operation Conversion index Type 15-6* Option Ident 15-60 Option Mounted 0 N/A All set-ups FALSE 0 VisStr[30] 15-61 Option SW Version 0 N/A All set-ups FALSE 0 VisStr[20] 15-62 Option…
-
5.3.14 16-** Data Readouts
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 16-0* General Status 16-00 Control Word 0 N/A All set-ups FALSE 0 V2 16-01 Reference [Unit] 0.000 ReferenceFeedbackUnit All set-ups FALSE -3 Int32 16-02 Reference % 0.0% All set-ups FALSE -1 Int16…
-
Par
No. # Parameter description VLT® Decentral Drive FCD 302 Operating Instructions Default value 4-set-up Change during operation Conversion index Type 16-6* Inputs & Outputs 16-60 Digital Input 0 N/A All set-ups FALSE 0 Uint16 16-61 Terminal 53 Switch Setting [0] Current All set-ups FALSE - Uint8…
-
5.3.15 17-** Motor Feedb.Option
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type [1] RS422 (5V TTL) All set-ups FALSE - Uint8 1024 N/A All set-ups FALSE 0 Uint16 17-1* Inc. Enc. Interface 17-10 Signal Type 17-11 Resolution (PPR) 17-2* Abs. Enc. Interface 17-20 Protocol Selection…
-
5.3.16 30-** Special Features
Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type 30-0* Wobbler 30-00 Wobble Mode [0] Abs. Freq., Abs. Time All set-ups FALSE - Uint8 30-01 Wobble Delta Frequency [Hz] 5.0 Hz All set-ups TRUE -1 Uint8 30-02 Wobble Delta Frequency [%] 25% All…
-
5.4 Remote Programming with MCT 10 Setup Software
Danfoss offers a software program available for developing, storing, and transferring frequency converter programming. The MCT 10 Set-up Software allows the user to connect a PC to the frequency converter and perform live programming rather than using the LCP. Also, all frequency converter…
-
6.1 Frontal LEDs
The actual status can be read on the outside of the FCD products. Six LEDs signal the actual status of the unit with the meaning described in Table 6.1. ON Warning Alarm Bus MS NS1 Status 1(1) 799RPM NS2 130BC281.10 6 Status Indication 0.75kW 0.98A 0.000 53.2% 130BB710.10 6 6 VLT® Decentral Drive…
-
Status Indication
Operation Status Operation Mode Hand On The navigation keys on the LCP control the frequency converter. Stop commands, reset, reversing, DC brake, and other signals applied to the control terminals can override local control. DC Stop Brake Current) for a specified time (2-02 DC Braking Time). • DC…
-
Status Indication
Operation Status Operation Status Motor check OVC control In 1-80 Function at Stop, Motor Check was selected. A stop command is active. To ensure that a motor is connected to the frequency converter, a permanent test current is applied to the motor. Speed high Motor speed is above the value set in…
-
7 Troubleshooting
7.1.1 Warnings/Alarm Messages Alarms that are trip-locked offer additional protection, meaning that the mains supply must be switched off before the alarm can be reset. After being switched back on, the frequency converter is no longer blocked. Reset the frequency converter as described above, once…
-
No. Description
Warning Alarm/Trip 27 Brake chopper short-circuited X X Alarm/Trip Lock Parameter Reference 28 Brake check (X) (X) 29 Heatsink temp X X X 30 Motor phase U missing (X) (X) (X) 4-58 Missing Motor Phase Function 31 Motor phase V missing (X) (X) (X) 4-58 Missing Motor Phase Function 32 Motor phase W…
-
No. Description
Warning 250 New spare part 251 New Type Code Alarm/Trip X Alarm/Trip Lock Parameter Reference X 14-23 Typecode Setting X Table 7.1 Alarm/Warning Code List (X) Dependent on parameter 1) Can not be Auto reset via 14-20 Reset Mode A trip is the action performed when an alarm arises. The trip causes the…
-
Alarm Word Extended Status Word
Bit Hex Dec Alarm Word Alarm Word 2 Warning Word Warning Word 2 Extended Status Word 0 00000001 1 Brake Check (A28) ServiceTrip, Read/ Write Brake Check (W28) reserved Ramping 1 00000002 2 Heatsink temp. (A29) ServiceTrip, (reserved) Heatsink temp. (W29) reserved AMA Running 2 00000004 4 Earth Fault…
-
The alarm words, warning words and extended status
words can be read out via serial bus or optional fieldbus for diagnosis. See also 16-94 Ext. Status Word. WARNING 1, 10 Volts low: The 10 V voltage from terminal 50 on the control card is below 10 V. Remove some of the load from terminal 50, as the 10 V supply is overloaded. Max. 15 mA or minimum…
-
If 8-04 Control Word Timeout Function is set to [Stop] and
[Trip], a warning appears and the frequency converter ramps down until it trips, while giving an alarm. 8-03 Control Word Timeout Time could possibly be increased. WARNING/ALARM 22, Hoist Mechanical Brake: The report value shows what kind it is. 0=The torque ref. was not reached before timeout.…
-
1283 Power EEPROM data version mismatch
1284 Cannot read Digital Signal Processor software version 1299 Option SW in slot A is too old 1300 Option SW in slot B is too old 1315 Option SW in slot A is not supported (not allowed) 1316 Option SW in slot B is not supported (not allowed) 1536 An exception in the Application Orientated Control…
-
4-32 Motor Feedback Loss Timeout. During a commissioning
procedure the function may be effective. WARNING 62, Output Frequency at Maximum Limit: The output frequency is higher than the value set in 4-19 Max Output Frequency. This is a warning in VVCplus mode and an alarm (trip) in Flux mode. ALARM 63, Mechanical Brake Low: The actual motor current has not…
-
8 Specifications
-
VLT® Decentral Drive FCD 302 Operating Instructions Specifications DC voltage level 380-480 V units (V DC) Inverter undervoltage disable 373 Undervoltage warning 410 Inverter undervoltage reenable (warning reset) 398 Overvoltage warning (without brake) 778 Dynamic brake turn on 778 Inverter…
-
8.2 General Specifications
Mains supply (L1, L2, L3) Supply voltage 380-480 V ±10% Mains voltage low / mains drop-out: During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops below the minimum stop level, which corresponds typically to 15% below the FC's…
-
Digital inputs
Programmable digital inputs Terminal number Logic Voltage level Voltage level, logic'0' PNP Voltage level, logic'1' PNP Voltage level, logic '0' NPN2) Voltage level, logic '1' NPN2) Maximum voltage on input Pulse frequency range (Duty cycle) Min. pulse width Input resistance, Ri 4 (6)1) 18, 19…
-
Max. frequency at terminal 29, 32, 33
Min. frequency at terminal 29, 32, 33 Voltage level Maximum voltage on input Input resistance, Ri Pulse input accuracy (0.1 - 1 kHz) Encoder input accuracy (1 - 110 kHz) 5 kHz (open collector) 4 Hz see 8.2.1 Digital Inputs 28 V DC approx. 4 kΩ Max. error: 0.1% of full scale Max. error: 0.05% of full…
-
Specifications VLT® Decentral Drive FCD 302 Operating Instructions Max. terminal load (DC-1)1) on 4-5 (NO) (Resistive load) Max. terminal load (DC-13)1) on 4-5 (NO) (Inductive load) Max. terminal load (AC-1)1) on 4-6 (NC) (Resistive load) Max. terminal load (AC-15)1) (Inductive load @ cosφ 0.4) Max.…
-
www.danfoss.com/drives