Operating Instructions VLT® AQUA Drive FC 202 315-1400 kW www.danfoss.com/drives
-
1 Introduction
4 1.1 Purpose of the Manual 4 1.2 Additional Resources 4 1.3 Document and Software Version 4 1.4 Approvals and Certifications 4 1.5 Disposal 5 1.6 Abbreviations and Conventions 5 2 Safety 7 2.1 Qualified Personnel 7 2.2 Safety Regulations 7 2.2.1 Discharge Time 7 2.2.2 Safe Torque Off (STO) 8 3…
-
4.1 Electrical Installation
2 28 4.1.1 Power Connections 28 4.1.2 Grounding 35 4.1.3 Extra Protection (RCD) 35 4.1.4 RFI Switch 35 4.1.5 Torque 35 4.1.6 Screened Cables 36 4.1.7 Motor Cable 36 4.1.8 Brake Cable for Frequency Converters with Factory-installed Brake Chopper Option 37 4.1.9 Shielding against Electrical Noise 37…
-
5.1.9 Quick Transfer of Parameter Settings when Using GLCP
57 5.1.10 Initialisation to Default Settings 57 5.1.11 RS-485 Bus Connection 58 5.1.12 How to Connect a PC to the Frequency Converter 58 5.1.13 PC Software Tools 59 6 How to programme the frequency converter 6.1 How to programme 60 6.1.7 Main Menu Mode 64 6.1.8 Parameter Selection 64 6.2 Commonly…
-
Introduction Operating Instructions 1 Introduction 1.1 Purpose of the Manual The frequency converter is designed to provide high shaft performance on electrical motors. Read these operating instructions carefully for proper use. Incorrect handling of the frequency converter may cause improper…
-
The frequency converter complies with UL508C thermal
memory retention requirements. For more information, refer to the section Motor Thermal Protection in the product specific design guide. hp Horsepower HTL HTL encoder (10-30 V) pulses - High-voltage transistor logic Hz Hertz NOTICE IINV Rated inverter output current Imposed limitations on the output…
-
Introduction Operating Instructions SFAVM Stator flux-oriented asynchronous vector modulation STW Status word SMPS Switch mode power supply THD Total harmonic distortion TLIM Torque limit TTL TTL encoder (5 V) pulses - transistor transistor logic UM,N Nominal motor voltage V Volts VT Variable torque…
-
Safety
Operating Instructions 2 Safety The following symbols are used in this document: WARNING UNINTENDED START WARNING Indicates a potentially hazardous situation which could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which could result in minor or moderate…
-
Safety Operating Instructions WARNING EQUIPMENT HAZARD Contact with rotating shafts and electrical equipment can result in death or serious injury. • Ensure that only trained and qualified personnel perform installation, start up, and maintenance. • Ensure that electrical work conforms to national…
-
3 Mechanical Installation
3.1.4 Lifting 3.1 Pre-installation 3.1.1 Planning the Installation Site NOTICE 130BB753.10 Always lift the frequency converter via the dedicated lifting eyes. Plan the installation of the frequency converter before commencing the installation. Neglecting this may result in extra work during and…
-
130BB689.10
Mechanical Installation 3 3 Illustration 3.3 Recommended Lifting Method, Enclosure Size F11/F12/F13/F14. NOTICE The plinth is provided in the same packaging as the frequency converter, but is not attached during shipment. The plinth is required to allow airflow cooling to the frequency converter.…
-
F8
-
3.2 Mechanical Installation
3.2.1 Preparation for Installation 776 (30.6) Provide a suitable mounting arrangement. The mounting arrangement depends on the design, weight, and torque of the frequency converter. • Examine the mechanical drawings to ensure that the space requirements are met. • Ensure that all wiring is done in…
-
3.2.4.2 Inverter, Enclosure Sizes F10 and F11
3 2 130BA849.13 1 4 308.3 [12.1] 253.1 [10.0] 180.3 [7.1] 5 6 .0 [.0] 44.40 [1.75] .0 [.0] 339.4 [13.4] 287.4 [11.3] 4 465.6 [18.3] 465.6 [18.3] 287.4 [11.3] 339.4 [13.4] .0 [.0] 635.0 [25.0] 637.3 [25.1] 671.0 [26.4] 551.0 [21.7] 522.3 [20.6] 572.1 [22.5] 587.0 [23.1] 497.1 [19.6] 198.1[7.8] 169.4…
-
3.2.4.3 Inverter, Enclosure Sizes F12 and F13
-
R1/L11 91
S2/L22 S1/L21 92 92-1 T2/L32 93-1 [ 24.79 ] [ 25.09 ] 91-1 629.7 637.3 R2/L12 [ 16.04 ] [ 18.28 ] [ 20.56 ] [ 20.65 ] 1 407.3 464.4 522.3 524.4 0.0 [ 0.00 ] 57.6 [ 2.27 ] 74.0 [ 2.91 ] 100.4 [ 3.95 ] 139.4 [ 5.49 ] 172.6 [ 6.80 ] 189.0 [ 7.44 ] 199.4 [ 7.85 ] 287.6 [ 11.32 ] 304.0 [ 11.97 ] 91.8 […
-
130BC146.10
3.2.4.6 Rectifier, Enclosure Size F14 3 3 629.7 [24.8] 100.4 [4.0] 139.4 [5.5] 199.4 [7.9] 464.4 [18.3] 524.4 [20.6] EARTH GROUND 308.3 [12.1] 253.1 [10.0] 273.1 [10.8] 253.1 [10.0] 203.1 [8.0] [7.1] EARTH GROUND 56.6 [2.2] .0 [.0] MOTOR SIDE EARTH GROUND 308.7 [12.2] 172.6 [6.8] 224.6 [8.8] .0 [.0]…
-
3 2 130BB756.11 3.2.4.7 Options Cabinet, Enclosure Size F9 887.4 830.3 628.8 443.8 386.7 151.3 .0 425.0 448.0 493.0 314.0 307.3 369.5 128.5 129.3 184.0 218.3 249.0 .0 73.0 .0 142.0 92.0 336.4 291.2 244.4 Illustration 3.17 Terminal Locations - Left, Front and Right Views MG20Y202 Danfoss A/S © Rev.…
-
2 130BB757.11 3.2.4.8 Options Cabinet, Enclosure Sizes F11/F13 547.8 440.4 4 151.3 .0 437.0 438.6 480.4 497.0 531.2 557.0 573.0 602.3 625.8 .0 73.0 88.1 112.0 138.9 172.0 180.7 232.0 231.5 273.3 324.1 338.9 387.8 179.2 135.2 80.4 36.4 .0 316.4 244.4 Illustration 3.18 Terminal Locations - Left, Front…
-
130BB190.10
(%) Fit the gland plate to the frequency converter to ensure the specified protection degree, as well as ensuring proper cooling of the unit. If the gland plate is not mounted, the frequency converter may trip on Alarm 69, Pwr. Card Temp 30 130BB073.10 Drive Derating 70 NOTICE Pressure Change…
-
130BB533.11
Enclosure Size F8 3 3 70.0 [ 2.756 ] 593.0 [ 23.326 ] 1 199.5 [ 7.854 ] 535.0 21.063 ] 258.5 [10.177 ] 35.5 [ 1 ] 36.5 [ 1.437 ] 733.0 [ 28.858 ] 460.0 [18.11] 673.0 [26.50] 593.0 [23.35] 130BB698.10 Enclosure Size F9 1 37.2 [1.47] 199.5 [7.85] 535.0 [21.06] 258.5 [10.18] 37.2 [1.47] 533.0 [20.98]…
-
[23.346] 1670.0 [65.748] 70.0 [ 2.756 ] 593.0 [23.346] 870.7 [34.252] 593.0 [23.346] 130BB695.10 Enclosure Size F11 199.5 [7.854] 535.0 [21.0631] 258.5 [10.177] 37.2 [1.466] 733.0 [28.858] 36.5 [1.437] 800.0 [31.496] 1533.0 [60.354] 1600.0 [62.992] 2333.0 [91.850] 857.7 [33.768] 593.0 [23.346] 70.0…
-
Operating Instructions Mechanical Installation 3.3 Frame size F Panel Options 3.3.1 Panel Options Space heaters and thermostat Space heaters are mounted on the cabinet interior of enclosure size F10-F14 frequency converters. They are controlled via an automatic thermostat, and help control humidity…
-
30 Amp, fuse-protected terminals
• 3-phase power matching incoming mains voltage for powering auxiliary customer equipment. • Not available if 2 manual motor starters are selected. • Terminals are off when the incoming power to the frequency converter is off. • Power for the fused protected terminals is provided from the load side…
-
4 How to Install
4.1 Electrical Installation 4.1.1 Power Connections Cabling and Fusing NOTICE Cables General All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. UL applications require 75 °C copper conductors. 75 °C and 90 °C copper conductors are thermally…
-
NOTICE
If an unscreened/unarmoured cable is used, some EMC requirements are not complied with. Use a screened/armoured motor cable to comply with EMC emission specifications. For more information, see EMC Specifications in the product relevant design guide. Inverter4 F14 Inverter4 F14 92-2 Inverter3…
-
Screening of cables
Avoid installation with twisted screen ends (pigtails). They spoil the screening effect at higher frequencies. If it is necessary to break the screen to install a motor isolator or motor contactor, the screen must be continued at the lowest possible HF impedance. Connect the motor cable screen to…
-
130BB699.11
1 130BB700.10 1 6 CFD30J3 R/L1 91 3 S/L2 92 T/L3 R/L1 91 S/L2 92 6 T/L3 Pilz relay terminal 2 RCD or IRM terminal 3 Mains/6-phase 4 R1 S1 T1 R2 S2 T2 91-1 92-1 93-1 91-2 92-2 93-2 L1-1 L2-1 L3-1 L1-2 L2-2 L3-2 Safety relay coil fuse with Pilz relay See chapter 4.1.13 Fuse Tables for part numbers. 5…
-
4.1.2 Grounding
For further reference, see IEC 364-3. Set 14-50 RFI Filter to [ON] if: To obtain electromagnetic compatibility (EMC), consider the following basic issues when installing a frequency converter. • Safety grounding: The frequency converter has a high leakage current (> 3.5 mA) and must be grounded…
-
4.1.6 Screened Cables
Motor U2 V2 W2 U1 V1 W1 Motor U2 V2 W2 U1 V1 W1 175HA036.11 Operating Instructions How to Install WARNING Danfoss recommends using screened cables between the LCL filter and the frequency converter. Unshielded cables can be used between transformer and LCL filter input side. FC It is important that…
-
module terminals and the first common point of a phase
The recommended common point is the motor terminals. 4.1.9 Shielding against Electrical Noise F14 requirements: Motor phase cable quantities must be multiples of 4, resulting in 4, 8, 12, or 16 (1, 2, or 3 cables are not allowed) to obtain an equal amount of wires attached to each inverter module…
-
4.1.11 External Fan Supply
In case the frequency converter is supplied by DC, or if the fan must run independently of the power supply, an external power supply can be applied. The connection is made on the power card. Terminal number Function 100, 101 Auxiliary supply S, T 102, 103 Internal supply S, T Table 4.6 External Fan…
-
Power size
-
Supplementary fuses
-
4.1.13 Motor Insulation
5. Install a shaft grounding system or use an isolating coupling For motor cable lengths ≤ the maximum cable length listed in , the motor insulation ratings in Table 4.19 are recommended. Peak voltage can be up to twice the DClink voltage, and 2.8 times the mains voltage, due to transmission line…
-
130BT312.10
frequency converter and tie it down with other control wires. Installation of 24 V external DC supply • • Torque: 0.5 - 0.6 Nm (5 in-lbs) Screw size: M3 Terminal number Function 35 (-), 36 (+) 24 V external DC supply Table 4.21 Terminals for 24 V External DC Supply Illustration 4.17 Inserting Cable…
-
+24V
P 5 - 10[9] 4.2 Connection Examples 4.2.1 Start/Stop 130BA156.12 Operating Instructions P 5 - 12 [6] How to Install 130BA155.12 P 5-12 [0] P 5-10 [8] +24V Terminal 18 = 5-10 Terminal 18 Digital Input [8] Start Terminal 27 = 5-12 Terminal 27 Digital Input [0] No operation (Default coast inverse)…
-
Voltage reference via a potentiometer
Reference Source 1 = [1] Analog input 53 (default) Speed RPM P 6-15 +10V/30mA 4.2.4 Potentiometer Reference 130BA154.11 How to Install Terminal 53, Low Voltage = 0 V Terminal 53, High Voltage = 10 V Ref. voltage P 6-11 10V Terminal 53, Low Ref./Feedback = 0 RPM 4 4 Terminal 53, High Ref./Feedback =…
-
4.3 Electrical Installation - additional
-
CUSTOMER
SUPPLIED 24V RET. REGEN TERMINALS 1 CUSTOMER SUPPLIED 24V 117 + CONTROL CARD PIN 20 (TERMINAL JUMPERED TOGETHER) CUSTOMER SUPPLIED (TERMINAL JUMPERED TOGETHER) MCB 113 PIN X46/1 5 11 MCB 113 PIN X46/3 TB8 12 MCB 113 PIN X46/5 13 MCB 113 PIN X46/7 14 MCB 113 PIN X46/9 15 MCB 113 PIN X46/11 C14 MCB…
-
NOTICE
Very long control cables and analog signals may in rare cases and depending on installation result in 50/60 Hz ground loops due to noise from mains supply cables. 130BT340.10 Control cables must be screened/armoured. If this occurs, it may be necessary to break the screen or insert a 100 nF…
-
130BA767.10
NOTICE 130BT310.11 When changing the function of S201, S202, or S801 do not to use force during the switch over. Remove the LCP fixture (cradle) when operating the switches. Do not operate the switches when the frequency converter is powered. 4 4 THREE PHASE INDUCTION MOTOR MOD MCV 315E Nr. 135189…
-
Press [OK]. The display shows Press [Hand On] to start. 6. Press [Hand On]. A progress bar indicates if the AMA is in progress. Stop the AMA during operation 1. Press [Off] - the frequency converter enters into alarm mode and the display shows that the user terminated the AMA. Successful AMA 1. The…
-
NOTICE
4.5.3 Motor Thermal Protection Installations with cables connected in a common joint as in Illustration 4.31, are only recommended for short cable lengths. NOTICE When motors are connected in parallel, 1-29 Automatic Motor Adaptation (AMA) cannot be used. NOTICE The electronic thermal relay (ETR) of…
-
5 How to operate the frequency converter
2. Numeric Local Control Panel (NLCP), see 6.1.3 3. RS-485 serial communication or USB, both for PC connection, see 6.1.4 If the frequency converter is fitted with fieldbus option, refer to relevant documentation. 130BA018.13 The frequency converter can be operated in 3 ways: 1. Graphical Local…
-
799 RPM
1.1 0.000 1.2 2 7.83 A 1 (1) 36.4 kw 53.2 % 1.3 Illustration 5.2 Status display II See the operating variables (1.1, 1.2, 1.3, and 2) shown in the display in Illustration 5.3. In the example, Speed, Motor current, Motor power and Frequency are selected as variables in the first and second lines.…
-
Status
Quick Menu Main Menu Alarm Log 130BP045.10 GLCP keys Menu keys The menu keys are divided into functions. The keys below the display and indicator lamps are used for parameter setup, including choice of display indication during normal operation. Illustration 5.7 [Status] Indicates the status of the…
-
NOTICE
Info OK On [Auto on] enables the frequency converter to be controlled via the control terminals and/or serial communication. When a start signal is applied on the control terminals and/or the bus, the frequency converter will start. The key can be Enabled [1] or Disabled [0] via 0-42 [Auto on] Key…
-
130BA191.10
How to operate the frequenc... Quick Setup Status Main Menu Ba ck Menu OK On 3 Alarm Hand on Main Menu Navigation keys [Back] for stepping backwards Warn. 4 Quick Setup Off Auto on [▲] [▼] keys are used for manoeuvring between parameter groups, parameters and within parameters Reset [OK] is used for…
-
Auto
on Reset Illustration 5.14 Operation keys of the numerical LCP (NLCP) [Hand on] enables control of the frequency converter via the LCP. [Hand on] also starts the motor and it is now possible to enter the motor speed data by means of the navigation keys. The key can be [1] Enabled or[0] Disabled via…
-
729RPM
6.21A 1(1) Load depen. setting 1- 6* 1 - 60 Low speed load compensation 130BP070.10 Press [▲] and [▼] to change the data value. [▲] increases the data value, and [▼] decreases the data value. Place the cursor on the value to be saved and press [OK]. • Under [Quick Menu] and [Changes Made] all…
-
Recommended initialisation (via 14-22 Operation Mode)
1. Select 14-22 Operation Mode. 5 5 2. Press [OK]. 3. Select [2] Initialisation (for NLCP select “2”). 4. Press [OK]. 5. Remove power to unit and wait for display to turn off. 6. Reconnect power and the frequency converter is reset. Note that first start-up takes a few more seconds. 7. Press [Reset]…
-
130BT308.10
How to operate the frequenc... mains, with the USB port. Failure to do so may damage equipment.). 2. Open MCT 10 Set-up Software. 3. Select Read from drive. 4. Select Save as. All parameters are now stored in the PC. Load frequency converter settings: Illustration 5.19 USB Connection to Frequency…
-
6 How to programme the frequency converter
6.1 How to programme The parameters are grouped into various parameter groups for easy selection of the correct parameter for optimised frequency converter operation. Overview of parameter groups Group Title Function 0-** Operation/Display Parameters related to the fundamental functions of the…
-
All digital input/output and analog input/output terminals
are multifunctional. All terminals have factory default functions suitable for the majority of water applications, but if other special functions are required, they must be programmed in parameter groups 5-** Digital In/out or 6-** Analog In/out. 6.1.1 Quick Menu Mode Par. Designation 0-01 Language…
-
Unit
69.3% 0-01 Language 5.20A 1(1) Quick Menus Parameter 1-20 Motor Power [kW] kW Parameter 1-22 Motor Voltage V Parameter 1-23 Motor Frequency Hz Parameter 1-24 Motor Current A Parameter 1-25 Motor Nominal Speed RPM Parameter 3-41 Ramp 1 Ramp Up Time s Parameter 3-42 Ramp 1 Ramp Down Time s Parameter…
-
The Function Setup parameters are grouped in the following way
Q3-10 Clock Settings Q3-11 Display Settings Q3-12 Analog Output 0-70 Date and Time 0-20 Display Line 1.1 Small Parameter 6-50 Terminal 42 Output Relay 1 ⇒ 5-40 Function Relay Q3-13 Relays 0-71 Date Format 0-21 Display Line 1.2 Small Parameter 6-51 Terminal 42 Output Relay 2 ⇒ 5-40 Function Relay Min…
-
6.1.5 Q5 Changes Made
Lines 2 to 5 on the display show a list of parameter groups which can be selected by toggling [▲] and [▼]. 1107 RPM Select Changes made to get information about: • the last 10 changes. Use the up/down navigation keys to scroll between the last 10 changed parameters. • Note that the parameters listed…
-
Group no
Parameter group 0-01 Language 23-** Time Actions 25-** Cascade Controller Option: 26-** Analog I/O Option MCB 109 27-** Cascade CTL Option 29-** Water Application Functions 31-** Bypass Option Defines the language to be used in the display. The frequency converter can be delivered with 4 different…
-
0-20 Display Line 1.1 Small
0-20 Display Line 1.1 Small Option: Function: Option: Function: [953] Profibus Warning Word Displays Profibus communication warnings. [1613] Frequency [1005] Readout Transmit Error Counter View the number of CAN control transmission errors since the last power-up. Motor frequency, i.e. the output…
-
0-20 Display Line 1.1 Small
0-20 Display Line 1.1 Small Option: Function: Option: Function: [1650] External Reference Sum of the external reference as a percentage, i.e. the sum of analog/ pulse/bus. [1672] Counter A View the present value of counter A. [1673] Counter B View the present value of counter B. [1652]…
-
0-20 Display Line 1.1 Small
0-20 Display Line 1.1 Small Option: Function: Option: Function: [1830] Analog Input X42/1 Shows the value of the signal applied to terminal X42/1 on the analog I/O card. [2230] The calculated no-flow power for the actual operating speed. [2316] Maintenance Text [1831] Analog Input X42/3 Shows the…
-
0-21 Display Line 1.2 Small
0-39 Display Text 3 Option: Function: Range: Function: Select a variable for display in line 1, middle position. 0* In this parameter it is possible to write an individual text string for display in the LCP or to be read via serial communication. If to be displayed [1662] * Analog input 53 [0 25 ]…
-
0-77 DST/Summertime End
1-22 Motor Voltage Range: Range: Function: Size related* Function: the nominal rated output of the frequency converter. [ 0 - 0 ] Sets the date and time when DST/ summertime ends. The date is programmed in the format selected in 1-23 Motor Frequency 0-71 Date Format. Range: 6.2.3 1-0* General…
-
NOTICE
3-04 Reference Function Parameter 1-29 Automatic Motor Adaptation (AMA) have no effect when 1-10 Motor Construction = [1] PM, nonsalient SPM. Activate the AMA function by pressing [Hand On] after selecting [1] or [2]. See also the section Automatic Motor Adaptation in the Design Guide. After a…
-
12 (+24V)
Preset 76543210 10101010 29 [P 5-13=Preset ref. bit 0] 11001100 32 [P 5-14=Preset ref. bit 1] 11110000 33 [P 5-15=Preset ref. bit 2] Speed 130BA962.10 130BA149.10 Operating Instructions Motor Speed High Normal Ramps Motor Speed Low Initial Ramp Final Ramp Time Illustration 6.12 Preset Reference…
-
130BA961.10
Speed Motor Speed High Normal Ramp Motor Speed Low 4-11 Motor Speed Low Limit [RPM] Range: Function: Size related* [ 0 - par. Enter the minimum limit for motor speed 4-13 in RPM. The motor speed low limit can be RPM] set to correspond to the manufacturer’s recommended minimum motor speed. The motor…
-
6.2.5 5-1* Digital Inputs
Digital input function Parameters for configuring the input functions for the input terminals. The digital inputs are used for selecting various functions in the frequency converter. All digital inputs can be set to the following functions: Options [120] - [138] are related to the cascade controller…
-
External Interlock Operating Instructions Same function as Coasting stop, inverse, but External Interlock generates the alarm Preset ref. bit Preset ref. message external fault in the display when the terminal which is programmed for Coast Inverse is logic ‘0’. The alarm message is also active via…
-
[34] Ramp bit 0
Select which ramp to use. Logic ‘0’ selects ramp 1 while logic ‘1’ selects ramp 2. [60] Counter A (up) (Terminal 29 or 33 only) Input for increment counting in the SLC counter. [36] Mains failure inverse Activates 14-10 Mains Failure. Mains failure inverse is active in the Logic ‘0’ situation. [61]…
-
Setting in
parameter group 5-1* Setting in 25-06 Number of Pumps [0] No [1] Yes [130] Pump1 Interlock Controlled by RELAY1 (only if not lead pump) Frequency converter controlled (cannot be interlocked) [131] Pump2 Interlock Controlled by RELAY2 Controlled by RELAY1 [132] Pump3 Interlock Controlled by RELAY3…
-
5-30 Terminal 27 Digital Output
5-40 Function Relay Option: Option: Function: [180] Clock Fault [21] Thermal warning [181] Prev. Maintenance [25] Reverse [182] Deragging [26] Bus OK [183] Pre/Post Lube [27] Torque limit & stop [188] AHF Capacitor Connect [28] Brake, no brake war [189] External Fan Control [29] Brake ready, no…
-
6-01 Live Zero Timeout Function
5-40 Function Relay Option: Option: Function: Function: 6-12 Terminal 53 Low Current, [193] Sleep Mode [194] Broken Belt parameter 6-20 Terminal 54 Low Voltage or [195] Bypass Valve Control 6-22 Terminal 54 Low Current for a time period [198] Drive Bypass defined in parameter 6-00 Live Zero Timeout…
-
6-10 Terminal 53 Low Voltage
6-24 Terminal 54 Low Ref./Feedb. Value Range: Range: 0.07 V* Function: [ 0 - par. 6-11 V] Function: parameter 6-20 Terminal 54 Low Voltage and 6-22 Terminal 54 Low Current. Enter the low-voltage value. This analog input scaling value should correspond to the low reference/feedback value set in…
-
6-50 Terminal 42 Output
[134] 6-52 Terminal 42 Output Max Scale Function: Range: Torq.0-lim 4-20 mA 0 - Torque limit (4-16 Torque Limit Function: Current (mA) Motor Mode) 130BA075.12 Option: 20 [135] Torq.0-nom 4-20mA 0 - Motor rated torque [136] Power 4-20mA 0 - Motor rated power [137] Speed 4-20mA 0 - Speed High Limit…
-
130BA856.10
Operating Instructions 20 mA 0/4 mA 0% 50% -200% 0% 75% +100% 100% +200% Illustration 6.21 Example 2 Example 3: Variable value=REFERENCE, range=Minimum ref maximum ref. Range needed for output=Minimum ref (0%) - Maximum ref (100%), 0-10 mA Output signal 0 mA or 4 mA is needed at minimum ref set…
-
20-21 Setpoint 1
Range: Function: 0 ProcessCtrlUnit* [-999999.999 999999.999 ProcessCtrlUnit] Setpoint 1 is used in closed loop mode to enter a setpoint reference that is used by the frequency converter’s PID controller. See the description of 20-20 Feedback Function. NOTICE The setpoint reference entered here is…
-
22-20 Low Power Auto Set-up
22-23 No-Flow Function Start of auto set-up of power data for no-flow power tuning. Common actions for low-power detection and low-speed detection (Individual selections not possible). Option: Function: [0] * Off Option: [1] [0] * Off Enabled An auto set-up sequence is activated, automatically…
-
22-26 Dry Pump Function
22-27 Dry Pump Delay Select desired action for dry pump operation. Range: Option: Function: expire before the timer for the dry pump delay starts. Function: [0] * Off [1] [2] Warning Trip The frequency converter continues to run, but activates a dry pump warning [W93]. A frequency converter digital…
-
22-35 Low Speed Power [HP]
22-41 Minimum Sleep Time Range: Function: Range: To be used if 0-03 Regional Settings has been set for North America (parameter not visible if International selected). Set power consumption at 50% speed level. This function is used for storing values needed to tune no-flow detection. 30 s* Size…
-
NOTICE
22-45 Setpoint Boost Range: Function: 0 %* Only to be used if parameter 1-00 Configuration [-100 - 100 %] Mode, is set for [3] Closed Loop and the integrated PI controller is used. In systems with e.g. constant pressure control, it is advantageous to increase the system pressure before the motor is…
-
130BA388.11
H (head) -81 P22 22-82 Work Point Calculation Option: Function: with HMIN as described above, allows the frequency converter to calculate the reference point B and thus to plot the control curve which also includes the system design working point A. 0% 100 % Control Curve HRATED Par. 22-88 H DESIGN…
-
22-85 Speed at Design Point [RPM]
22-83 Speed at No-Flow [RPM] Range: Range: Size related* Function: [0 60000 RPM] Only visible when parameter 22-82 Work entered in parameter 22-86 Speed at Design Range: Resolution 0.033 Hz. Only visible when parameter 22-82 Work Point Calculation is set to [0] Disabled. Enter the motor speed in Hz…
-
NOTICE
23-01 ON Action The clock (parameter group 0-7* Clock Settings) must be correctly programmed for timed actions to function correctly. Arra [10] Option: Function: [19] Select ramp 2 [22] Run NOTICE [23] Run reverse When mounting an analog I/O MCB 109 option card, a battery back-up of the date and…
-
23-02 OFF Time
23-03 OFF Action Array [10] Array [10] Range: Size related* Option: Function: [ 0 - 0 ] Sets the OFF time for the timed action. NOTICE Function: [37] Set digital out F low [38] Set digital out A high The frequency converter has no back-up of the clock function and the set date/time is reset to…
-
29-01 Pipe Fill Speed [RPM]
Range: Function: made in parameter 4-11 Motor Speed Low Limit [RPM]/parameter 4-13 Motor Speed High Limit [RPM] or in 4-12 Motor Speed Low Limit [Hz]/4-14 Motor Speed High Limit [Hz]. 29-02 Pipe Fill Speed [Hz] Range: Size related* 6 6 Function: [ par. 4-12 - Set the filling speed for filling…
-
6.3 Parameter Options
6.3.1 Default Settings Changes during operation ”TRUE” means that the parameter can be changed while the frequency converter is in operation and “FALSE” means that the frequency converter must be stopped before a change can be made. 4-Set-up 'All set-up': the parameter can be set individually in…
-
Danfoss A/S © Rev. 06/2014 All rights reserved. 0-67 0-7* 0-70 0-71 0-72 0-74 0-76 0-77 0-79 0-81 0-82 0-83 0-89 1-** 1-0* 1-00 0-** 0-0* 0-01 0-02 0-03 0-04 0-05 0-1* 0-10 0-11 0-12 0-13 0-14 0-2* 0-20 0-21 0-22 0-23 0-24 0-25 0-3* 0-30 0-31 0-32 0-37 0-38 0-39 0-4* 0-40 0-41 0-42 0-43 0-44 0-45…
-
6-44 6-45 6-46 6-47 6-5* 6-50 6-51 6-52 6-53 6-54 6-55 6-6* 6-60 6-61 6-62 6-63 6-64 6-7* 6-70 6-71 6-72 6-73 6-74 6-8* 6-80 6-81 6-82 6-83 6-84 8-** 8-0* 8-01 8-02 8-03 8-04 8-05 8-06 8-07 8-08 8-1* 8-10 8-13 8-14 8-3* 8-30 8-31 8-32 8-33 8-35 8-36 8-37 8-4* 8-40 8-42 8-43 8-5* 8-50 8-52 8-53…
-
15-33 Alarm Log: Date and Time
15-34 Alarm Log: Setpoint 15-35 Alarm Log: Feedback 15-36 Alarm Log: Current Demand 15-37 Alarm Log: Process Ctrl Unit 15-4* Drive Identification 15-40 FC Type 15-41 Power Section 15-42 Voltage 15-43 Software Version 15-44 Ordered Typecode String 15-45 Actual Typecode String 15-46 Frequency…
-
23-01 ON Action
23-02 OFF Time 23-03 OFF Action 23-04 Occurrence 23-1* Maintenance 23-10 Maintenance Item 23-11 Maintenance Action 23-12 Maintenance Time Base 23-13 Maintenance Time Interval 23-14 Maintenance Date and Time 23-1* Maintenance Reset 23-15 Reset Maintenance Word 23-16 Maintenance Text 23-5* Energy Log…
-
7 General Specifications
Mains Supply (L1-1, L2-1, L3-1, L1-2, L2-2, L3-2) Supply voltage Supply voltage 380-500 V ±10% 525-690 V ±10% Mains voltage low/mains drop-out: During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops below the minimum stop level…
-
Input resistance, Ri
approx. 4 kΩ All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 1) Terminals 27 and 29 can also be programmed as output. Analog inputs Number of analog inputs Terminal number Modes Mode select Voltage mode Voltage level Input resistance, Ri…
-
Resolution on analog output
8 bit The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Control card, RS-485 serial communication Terminal number Terminal number 61 68 (P,TX+, RX+), 69 (N,TX-, RX-) Common for terminals 68 and 69 The RS-485 serial communication circuit is…
-
Control card, 10 V DC output
Terminal number Output voltage Maximum load 50 10.5 V ±0.5 V 25 mA The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Control characteristics Resolution of output frequency at 0-590 Hz System response time (terminals 18, 19, 27, 29, 32, 33)…
-
values stated in the tables on the following pages (Guideline - these temperatures may vary for different power sizes, frame sizes, enclosure ratings etc.). • • • • The frequency converter is protected against short circuits on motor terminals U, V, W. If a mains phase is missing, the frequency…
-
1) For type of fuse see section Fuses
2) American Wire Gauge. 3) Measured using 5 m screened motor cables at rated load and rated frequency. 4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety in voltage and cable conditions). Values are based on a typical motor…
-
8 Troubleshooting
8.1 Alarms and Warnings A warning or an alarm is signalled by the relevant LED on the front of the frequency converter and indicated by a code on the display. A warning remains active until its cause is no longer present. Under certain circumstances operation of the motor may still be continued.…
-
No
Description Warning Alarm/Trip 28 Brake check (X) (X) 29 Drive over temperature X X X 30 Motor phase U missing (X) (X) (X) 4-58 31 Motor phase V missing (X) (X) (X) 4-58 32 Motor phase W missing (X) (X) (X) 4-58 33 Inrush fault X X 34 Fieldbus communication fault X X 35 Out of frequency range X X 36…
-
No
Description 220 Overload Trip Warning 243 Brake IGBT X X Alarm/Trip Alarm/Trip Lock Parameter Reference X X 244 Heatsink temp X X 245 Heatsink sensor X X 246 Pwr.card supply X X 247 Pwr.card temp X X 248 Illegal PS config X X 250 New spare part 251 New Type Code X X X Table 8.1 Alarm/Warning Code…
-
Alarm Word and Extended Status Word
Bit Hex Dec Alarm Word Warning Word Extended Status Word 0 00000001 1 Brake Check Brake Check Ramping 1 00000002 2 Pwr. Card Temp Pwr. Card Temp AMA Running 2 00000004 4 Earth Fault Earth Fault Start CW/CCW 3 00000008 8 Ctrl.Card Temp Ctrl.Card Temp Slow Down 4 00000010 16 Ctrl. Word TO Ctrl. Word…
-
WARNING 1, 10 Volts low
The control card voltage is <10 V from terminal 50. Remove some of the load from terminal 50, as the 10 V supply is overloaded. Maximum 15 mA or minimum 590 Ω. A short-circuit in a connected potentiometer or improper wiring of the potentiometer can cause this condition. Troubleshooting • Remove the…
-
Ensure that the motor data in parameters 1-20 to 1-25 are set correctly. • If an external fan is in use, check that it is selected in 1-91 Motor External Fan. • Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the frequency converter to the motor more accurately and reduces…
-
The warning is only active when 8-04 Control Timeout
Function is not set to [0] Off. If 8-04 Control Timeout Function is set to [2] Stop and [26] Trip, a warning appears and the frequency converter ramps down until it trips and then displays an alarm. Troubleshooting: • Check the connections on the serial communication cable. • • Increase 8-03 Control…
-
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the motor is missing. Troubleshooting • Remove the power from the frequency converter and check motor phase W. ALARM 33, Inrush fault Too many power-ups have occurred within a short time period. Troubleshooting • Let the unit cool to operating…
-
Number
Operating Instructions Text 2561 No communication from DSP to ATACD. 2562 No communication from ATACD to DSP (state running). 2816 Stack overflow control board module 2817 Scheduler slow tasks 2818 Fast tasks 2819 Parameter thread 2820 LCP stack overflow 2821 Serial port overflow 2822 USB port…
-
WARNING 60, External interlock
External interlock has been activated. To resume normal operation, apply 24 V DC to the terminal programmed for external interlock and reset the frequency converter (via serial communication, digital I/O, or by pressing [Reset]). ALARM 70, Illegal FC configuration The control card and power card are…
-
ALARM 95, Broken belt
Torque is below the torque level set for no load, indicating a broken belt. 22-60 Broken Belt Function is set for alarm. Troubleshooting • Troubleshoot the system and reset the frequency converter after the fault has been cleared. ALARM 96, Start delayed Motor start has been delayed due to…
-
2 = Second frequency converter from the left
inverter module in enclosure size F14. 3 = Right inverter module in enclosure sizes F12 or F13. 3 = Third from the left inverter module in enclosure size F14. 4 = Far right inverter module in enclosure size F14. 5 = Rectifier module. 6 = Right rectifier module in enclosure size F14. ALARM 247, Power…
-
www.danfoss.com/drives
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being…