Инструкция на Преобразователь частоты Danfoss серии VLT Refrigeration Drive FC 103 110-250 kW
Преобразователь частоты Danfoss серии VLT Refrigeration Drive FC 103 110-250 kW. Инструкция по эксплуатации.
Загружаем документ…
Текст инструкции
-
MAKING MODERN LIVING POSSIBLE
Operating Instructions VLT® Refrigeration Drive 110-250 kW
-
1 Safety
4 2 Introduction 5 2.1 Exploded Views 5 2.2 Purpose of the Manual 6 2.3 Additional Resources 6 2.4 Product Overview 6 2.5 Internal Controller Functions 6 3 Installation 8 3.1 Planning the Installation Site 8 3.2 Pre-Installation Checklist 8 3.3 Mechanical Installation 8 3.3.1 Cooling 8 3.3.2 Lifting…
-
4.5 System Start Up
5 User Interface 30 5.1 Local Control Panel 30 5.1.1 LCP Layout 30 5.1.2 Setting LCP Display Values 31 5.1.3 Display 31 5.1.4 Navigation Keys 32 5.1.5 Operation Keys 32 5.2 Back Up and Copying Parameter Settings 32 5.2.1 Uploading Data to the LCP 33 5.2.2 Downloading Data from the LCP 33 5.3…
-
9.3 Warning and Alarm Displays
50 9.4 Warning and Alarm Definitions 52 9.5 Fault Messages 54 10 Basic Troubleshooting 60 10.1 Start Up and Operation 11 Specifications 60 63 11.1 General Specifications 63 11.2 Mains Supply 68 11.3 Fuse Specifications 71 11.3.1 Protection 71 11.3.2 Non UL Compliance 71 11.3.3 UL Compliance 72…
-
Safety VLT® Refrigeration Drive 110-250 kW Operating Instructions 1 Safety WARNING HIGH VOLTAGE! Frequency converters contain high voltage when connected to AC mains input power. Installation, start up, and maintenance should be performed by qualified personnel only. Failure to perform installation…
-
2 Introduction
2 2 130BC301.10 2.1 Exploded Views 130BC252.10 Illustration 2.2 Close-up View: LCP and Control Functions 12 13 (IP 21/54 NEMA 1/12) 13 (IP 20/Chassis) Illustration 2.1 D1 Interior Components 1 LCP (Local Control Panel) 9 2 RS-485 serial bus connector 10 Lifting ring Relay 2 (04, 05, 06) 3 Digital…
-
Introduction VLT® Refrigeration Drive 110-250 kW Operating Instructions 2.2 Purpose of the Manual This manual is intended to provide detailed information for the installation and start up of the frequency converter. provides requirements for mechanical and electrical installation, including input…
-
Area
8 VLT® Refrigeration Drive 110-250 kW Operating Instructions Title Control circuitry Functions • Input power, internal processing, output, and motor current are monitored to provide efficient operation and control 2 2 • User interface and external commands are monitored and performed • Status output…
-
3 Installation
3.1 Planning the Installation Site • CAUTION Before performing the installation it is important to plan the installation of the frequency converter. Neglecting this may result in extra work during and after installation. Select the best possible operation site by considering the following (see…
-
heat not contained in the backchannel of the frequency converters and any additional losses generated by other components inside the enclosure. The total required air flow must be calculated so that the appropriate fans can be selected. 3.3.2 Lifting Always lift the frequency converter using the…
-
3 Phase
-
130BX370.10 For personal safety, comply with the following requirements Electronic controls equipment is connected to hazardous mains voltage. Extreme care should be taken to protect against electrical hazards when applying power to the unit. • Run motor cables from multiple frequency converters…
-
3.4.2 Earth (Ground) Requirements
WARNING EARTHING (GROUNDING) HAZARD! For operator safety, it is important to earth (ground) the frequency converter properly in accordance with national and local electrical codes as well as instructions contained within this document. Do not use conduit connected to the frequency converter as a…
-
3.4.2.3 Earthing (Grounding) IP21/54
Enclosures The frequency converter can be earthed (grounded) using conduit or shielded cable. For earthing (grounding) of the power connections, use the dedicated earthing (grounding) points as shown in Illustration 3.6. The frequency converter can be earthed (grounded) using conduit or shielded…
-
3.4.3 Motor Connection
• Do not install power factor correction capacitors between the frequency converter and the motor. WARNING • Do not wire a starting or pole-changing device between the frequency converter and the motor. • Connect the 3-phase motor wiring to terminals 96 (U), 97 (V), and 98 (W). • Earth (ground) the…
-
B
-
130BC254.10
3.4.3.1 Motor Cable The motor must be connected to terminals U/T1/96, V/ T2/97, W/T3/98. Earth (ground) to terminal 99. All types of three-phase asynchronous standard motors can be used with a frequency converter unit. The factory setting is for clockwise rotation with the frequency converter output…
-
3.5 Control Wiring Connection
• • 3 3 PLC Isolate control wiring from high power components in the frequency converter. If the frequency converter is connected to a thermistor, for PELV isolation, optional thermistor control wiring must be reinforced/double insulated. A 24 V DC supply voltage is recommended. 3.5.1 Access PE…
-
3.5.5 Wiring to Control Terminals
Terminal functions and default settings are summarized in 3.5.6 Control Terminal Functions. Terminal plugs can be removed for easy access. 130BA012.11 130BT306.10 3.5.4 Control Terminal Types Illustration 3.17 3.5.6 Control Terminal Functions Frequency converter functions are commanded by receiving…
-
potential throughout the network. Particularly in installations with long cables
To prevent impedance mismatch, always use the same type of cable throughout the entire network. When connecting a motor to the frequency converter, always use screened motor cable. Cable Screened twisted pair (STP) Impedance 120 Ω Max. cable length 1200 m (including drop lines) 500 m…
-
4 Start Up and Functional Test
4.1 Pre-start CAUTION 4 4 Before applying power to the unit, inspect the entire installation as detailed in Table 4.1. Check mark those items when completed. ☑ Inspect for Description Auxiliary equipment • Cable routing • Check function and installation of any sensors used for feedback to the…
-
4.2 Applying Power to the Frequency Converter
WARNING HIGH VOLTAGE! Frequency converters contain high voltage when connected to AC mains. Installation, start-up and maintenance should be performed by qualified personnel only. Failure to perform installation, start-up and maintenance by qualified personnel could result in death or serious…
-
130BC952.10
If [OK] is pressed, the Application Guide will start with the following screen: Compressor pack set-up As an example, see screens below for a compressor pack set-up: Voltage and frequency set-up 4 4 Illustration 4.2 NOTE Numbering of steps in wizard (e.g. 1/12) can change depending on choices in the…
-
Min. time between two starts
VLT® Refrigeration Drive 110-250 kW Operating Instructions NOTE Internal/Closed loop: The FC 103 will control the application directly using the internal PID control within the frequency converter and needs an input from an external input such as a temperature or other sensor which is wired directly…
-
Info: 4-20 mA feedback chosen - connect accordingly
Select fixed or floating setpoint 4 4 Illustration 4.16 Illustration 4.13 Set setpoint Info: Set switch accordingly Illustration 4.17 Illustration 4.14 Select unit and conversion from pressure Illustration 4.15 Set high/low limit for setpoint Illustration 4.18 MG16F102 - VLT® is a registered Danfoss…
-
Info: Connect accordingly
130BC955.10 Set cut out/in value VLT® Refrigeration Drive 110-250 kW Operating Instructions 4 4 Illustration 4.22 Info: Setup completed Illustration 4.19 Choose pack control set-up Illustration 4.23 After completing set-up, choose to re-run wizard or start application. Select between the following…
-
The Application Guide can be cancelled at any time by
pressing [Back]. The Application Guide can be re-entered through the Quick Menu: 3.84 A 1107 RPM 130BP066.10 Start Up and Functional Tes... 1 (1) Main menu 0 - Operation/Display 130BC957.10 1 - Load/Motor 2 - Brakes 3 - Reference / Ramps Illustration 4.26 Use navigation keys to scroll to parameter…
-
13.0A
1(1) Quick Menus Q1 My Personal Menu 130BB847.10 13.7% VLT® Refrigeration Drive 110-250 kW Operating Instructions Q2 Quick Setup Q6 Loggings Illustration 4.29 8. Select language and press [OK]. Then enter the motor data in parameters 1-20/1-21 through 1-25. The information can be found on the motor…
-
NOTE
4.2 Applying Power to the Frequency Converter through in this chapter concludes the procedures for applying power to the frequency converter, basic programming, set-up, and functional testing. 4.5 System Start Up 4 4 The procedure in this section requires user-wiring and application programming to…
-
5 User Interface
5.1.1 LCP Layout The local control panel (LCP) is the combined display and keypad on the front of the unit. The LCP is the user interface to the frequency converter. The LCP is divided into four functional groups (see Illustration 5.1). 130BC362.10 5.1 Local Control Panel The LCP has several user…
-
User Interface
VLT® Refrigeration Drive 110-250 kW Operating Instructions 5.1.3 Display The display area is activated when the frequency converter receives power from mains voltage, a DC bus terminal, or an external 24 V supply. Menu keys are used for menu access for parameter set-up, toggling through status…
-
5.1.5 Operation Keys
Navigation keys are used for programming functions and moving the display cursor. The navigation keys also provide speed control in local (hand) operation. Three frequency converter status indicator lights are also located in this area. Operation keys are found at the bottom of the LCP. Ba l ce ck n…
-
User Interface
VLT® Refrigeration Drive 110-250 kW Operating Instructions WARNING personal menu settings, fault log, alarm log, and other monitoring functions UNINTENDED START! When the frequency converter is connected to AC mains, the motor may start at any time. The frequency converter, motor, and any driven…
-
6 Programming
6.1 Introduction 3-02 Minimum Reference. Set minimum internal frequency converter reference to 0 Hz. (This sets the minimum frequency converter speed at 0 Hz.) The frequency converter is programmed for its application functions using parameters. Parameters are accessed by pressing either [Quick…
-
0.00A Analog Reference 1(1) Q3-21 6-11 Terminal 53 High Voltage 130BC958.10 6-11 Terminal 53 High Voltage. Set maximum external voltage reference on Terminal 53 at 10 V. (This sets the maximum input signal at 10 V.) 130BT765.10 5. VLT® Refrigeration Drive 110-250 kW Operating Instructions U-I 6-1*…
-
Scroll to parameter group 5-1* Digital Inputs and
press [OK]. 0.00A Digital In/Out 1(1) 5-** 5-0* Digital I/O mode 5-1* Digital Inputs 5-4* Relays 5-5* Pulse Input Illustration 6.10 6 6 Scroll to 5-10 Terminal 18 Digital Input. Press [OK] to access function choices. The default setting Start is shown. 14.7% 0.00A Digital Inputs 1(1) 5-1* 5-10…
-
Press [Quick Menu]. 2. Scroll to Q5 Changes Made and press [OK]. 25.9% 0.00A 1(1) Quick Menus Q1 My Personal Menu 130BP089.10 6.4.1 Parameter Data Check Q2 Quick Setup Q3 Function Setups Q5 Changes Made Illustration 6.13 3. 6 6 Select Q5-2 Since Factory Setting to view all programming changes or…
-
20-82 PID Start Speed [RPM] 20-83 PID Start Speed [Hz] Q3-20 Digital Reference 3-02 Minimum Reference 3-03 Maximum Reference 3-10 Preset Reference 5-13 Terminal 29 Digital Input 5-14 Terminal 32 Digital Input 5-15 Terminal 33 Digital Input Q3-21 Analog Reference 3-02 Minimum Reference 14-01…
-
22-62 Broken Belt Delay 4-64 Semi-Auto Bypass Set-up 1-03 Torque Characteristics 4-56 Warning Feedback Low 4-57 Warning Feedback High 20-20 Feedback Function Table 6.3 22-61 Broken Belt Torque 6-01 Live Zero Timeout Function 22-20 Low Power Auto Set-up Q3-41 Pump Functions 4-10 Motor Speed Direction…
-
MG16F102 - VLT® is a registered Danfoss trademark 0-7* 0-70 0-71 0-72 0-74 0-76 0-77 0-79 0-81 0-82 0-83 0-89 0-** 0-0* 0-01 0-02 0-03 0-04 0-05 0-1* 0-10 0-11 0-12 0-13 0-14 0-2* 0-20 0-21 0-22 0-23 0-24 0-25 0-3* 0-30 0-31 0-32 0-37 0-38 0-39 0-4* 0-40 0-41 0-42 0-43 0-44 0-45 0-5* 0-50 0-51 0-6*…
-
11-18 LonWorks Revision
6-61 Terminal X30/8 Min. Scale 11-2* LON Param. Access 6-62 Terminal X30/8 Max. Scale 11-21 Store Data Values 6-63 Terminal X30/8 Output Bus Control 6-64 Terminal X30/8 Output Timeout Preset 13-** Smart Logic 13-0* SLC Settings 8-** Comm. and Options 13-00 SL Controller Mode 8-0* General Settings…
-
20-14 Maximum Reference/Feedb
20-2* Feedback/Setpoint 20-20 Feedback Function 20-21 Setpoint 1 20-22 Setpoint 2 20-23 Setpoint 3 20-3* Feedb. Adv. Conv. 20-30 Refrigerant 20-31 User Defined Refrigerant A1 20-32 User Defined Refrigerant A2 20-33 User Defined Refrigerant A3 20-34 Duct 1 Area [m2] 20-35 Duct 1 Area [in2] 20-36 Duct…
-
28-8* PO Optimization
28-81 dPO Offset 28-82 PO 28-83 PO Setpoint 28-84 PO Reference 28-85 PO Minimum Reference 28-86 PO Maximum Reference 28-87 Most Loaded Controller 28-9* Injection Control 28-90 Injection On 28-91 Delayed Compressor Start Programming VLT® Refrigeration Drive 110-250 kW Operating Instructions 6 6…
-
7 Application Set-Up Examples
7.1 Introduction NOTE • A jumper wire may be required between terminal 12 (or 13) and terminal 37 for the frequency converter to operate when using factory default programming values. The examples in this section are intended as a quick reference for common applications. Parameter settings are the…
-
130BA761.11
-
130BA807.10
7.2.3 Compressor Pack P0 7 7 130BA808.12 Illustration 7.4 P0 Pressure Transmitter FC U V W Supply 1 2 AKS33 Illustration 7.5 How to Connect the FC 103 and AKS33 for Closed Loop Applications NOTE To find out which parameters are relevant, run the Wizard. 46 MG16F102 - VLT® is a registered Danfoss…
-
8 Status Messages
8.1 Status Display 8.2 Status Message Definitions Table When the frequency converter is in status mode, status messages are generated automatically from within the frequency converter and appear in the bottom line of the display (see Illustration 8.1.) The next three tables define the meaning of the…
-
Operation status
Operation status Ctrl. Ramp-down Control Ramp-down was selected in Jog request A jog command has been given, but the motor will be stopped until a run permissive signal is received via a digital input. Jogging The motor is running as programmed in 14-10 Mains Failure. • The mains voltage is below…
-
Operation status
Ref. low The sum of all active references is below the reference limit set in 4-54 Warning Reference Low. Run on ref. The frequency converter is running in the reference range. The feedback value matches the setpoint value. Run request A start command has been given, but the motor is stopped until a…
-
9 Warnings and Alarms
9.2.3 Alarm Trip-lock The frequency converter monitors the condition of its input power, output, and motor factors as well as other system performance indicators. A warning or alarm may not necessarily indicate a problem internal to the frequency converter itself. In many cases, it indicates failure…
-
Ba
ck el nc Ca 130BB467.10 In addition to the text and alarm code on the frequency converter display, there are three status indicator lights. Info OK On Warn. Alarm Hand on Off Auto on Reset Illustration 9.3 Warn. LED Alarm LED Warning ON OFF Alarm OFF ON (Flashing) Trip-Lock ON ON (Flashing) 9 9…
-
9.4 Warning and Alarm Definitions
Table 9.2 defines whether a warning is issued prior to an alarm, and whether the alarm trips the unit or trip locks the unit. No. Description Warning 1 10 Volts low X Alarm/Trip 2 Live zero error (X) (X) 4 Mains phase loss (X) (X) 5 DC link voltage high X 6 DC link voltage low X Alarm/Trip Lock…
-
No
Description Warning Alarm/Trip 49 Speed limit X (X) 50 AMA calibration failed 51 AMA check Unom and Inom X 52 AMA low Inom X 53 AMA motor too big X 54 AMA motor too small X 55 AMA Parameter out of range X 56 AMA interrupted by user X 57 AMA timeout 58 AMA internal fault Alarm/Trip Lock Parameter…
-
WARNING/ALARM 7, DC overvoltage
If the intermediate circuit voltage exceeds the limit, the frequency converter trips after a time. 9.5 Fault Messages The warning/alarm information below defines each warning/alarm condition, provides the probable cause for the condition, and details a remedy or troubleshooting procedure. WARNING 1…
-
Check that the motor current set in 1-24 Motor Current is correct. • Ensure that Motor data in parameters 1-20 through 1-25 are set correctly. • If an external fan is in use, check in 1-91 Motor External Fan that it is selected. • Running AMA in 1-29 Automatic Motor Adaptation (AMA) tunes the…
-
The warning will only be active when 8-04 Control Timeout
Function is NOT set to OFF. If 8-04 Control Timeout Function is set to Stop and Trip, a warning appears and the frequency converter ramps down until it trips then displays an alarm. Troubleshooting: • Check connections on the serial communication cable. • • Increase 8-03 Control Timeout Time •…
-
Remove power from the frequency converter and check
motor phase V. ALARM 32, Motor phase W missing Motor phase W between the frequency converter and the motor is missing. Remove power from the frequency converter and check motor phase W. ALARM 33, Inrush fault Too many power-ups have occurred within a short time period. Let the unit cool to operating…
-
No
3072-5122 VLT® Refrigeration Drive 110-250 kW Operating Instructions Text Parameter value is outside its limits 5123 Option in slot A: Hardware incompatible with control board hardware 5124 Option in slot B: Hardware incompatible with Control board hardware. 5125 Option in slot C0: Hardware…
-
ALARM 64, Voltage Limit
The load and speed combination demands a motor voltage higher than the actual DC link voltage. WARNING/ALARM 65, Control card over temperature The cutout temperature of the control card is 80° C. Troubleshooting • Check that the ambient operating temperature is within limits • • • Check for clogged…
-
10 Basic Troubleshooting
10.1 Start Up and Operation Symptom Display dark / No function Possible Cause Test Solution Missing input power See Table 4.1. Check the input power source. Missing or open fuses or circuit breaker tripped See open fuses and tripped circuit breaker in this table for possible causes. Follow the…
-
Symptom
VLT® Refrigeration Drive 110-250 kW Operating Instructions Possible Cause Motor rotation limit Test Check that 4-10 Motor Speed Solution Program correct settings. Direction is programmed correctly. Motor running in wrong direction Active reversing signal Check if a reversing command is programmed…
-
Symptom
VLT® Refrigeration Drive 110-250 kW Operating Instructions Possible Cause Test Solution Bypass critical frequencies by using parameters in parameter group 4-6*. Acoustic noise or vibration (e.g. a fan blade is making noise or vibrations at certain frequencies) Turn off over-modulation in Resonances…
-
11 Specifications
11.1 General Specifications Mains supply (L1, L2, L3) Supply voltage Supply voltage 380-480 V ±10% 525-600 V ±10% Mains voltage low/mains drop-out: During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops below the minimum stop…
-
Digital inputs
Programmable digital inputs Terminal number Logic Voltage level Voltage level, logic'0' PNP Voltage level, logic'1' PNP Voltage level, logic '0' NPN Voltage level, logic '1' NPN Maximum voltage on input Input resistance, Ri 4 (6) 18, 19, 27 1), 29 1), 32, 33, PNP or NPN 0-24 V DC <5 V DC >10 V DC…
-
Pulse inputs
Programmable pulse inputs Terminal number pulse Max. frequency at terminal, 29, 33 Max. frequency at terminal, 29, 33 Min. frequency at terminal 29, 33 Voltage level Maximum voltage on input Input resistance, Ri Pulse input accuracy (0.1-1 kHz) Analog output Number of programmable analog outputs…
-
Max. terminal load (AC-1)1) on 4-6 (NC) (Resistive load)
Max. terminal load (AC-15)1) on 4-6 (NC) (Inductive load @ cosφ 0.4) Max. terminal load (DC-1)1) on 4-6 (NC) (Resistive load) Max. terminal load (DC-13)1) on 4-6 (NC) (Inductive load) Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) Environment according to EN 60664-1 240 V AC, 2 A 240 V…
-
Control card performance
Scan interval Control card, USB serial communication USB standard USB plug 5 ms 1.1 (Full speed) USB type B “device” plug CAUTION Connection to PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage…
-
11.2 Mains Supply
-
typical control card power consumptions are included. Further options and customer load may add up to 30 W to the losses. (Though typical only 4 W extra for a fully loaded control card, or options for slot A or slot B, each). Although measurements are made with state of the art equipment, some…
-
11.3 Fuse Specifications
11.3.1 Protection Branch Circuit Protection: In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and overcurrent protected according to national/international regulations. Short-circuit…
-
11.3.3 UL Compliance
-
www.danfoss.com/drives