Инструкция на Модульные 3-фазные ИБП CyberPower серии OLS (3:1)
Модульные 3-фазные ИБП CyberPower серии OLS3S15KE(XL), OLS3S20KE(XL) способные обеспечивать N + X резервирование питания для корпоративных приложений. Руководство по эксплуатации.
Загружаем документ…
Текст инструкции
-
Userˊs Manual
-
1. Safety
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1.1. Installation This is permanently connected equipment, and it must be installed by qualified maintenance personnel. Condensation may occur if the UPS is moved directly…
-
The UPS output terminal block may be electrically lived even if the UPS system is not connected to the building wiring terminal, for there is internal current source (batteries). In order to fully disconnect the UPS, turn the Main1/Main2/N input breaker in the "OFF" position, then disconnect the…
-
1.4. Transport
Please transport the UPS only in the original packaging to protect against shock and impact. 1.5. Storage The UPS must be stockpiled in the room where is ventilated and dry. 1.6. Standards * Safety IEC/EN 62040-1 * EMI Conducted Emission :IEC/EN 62040-2 Category C3 Radiated Emission :IEC/EN 62040-2…
-
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourself with them and understand their meaning: Symbol and Explanation Symbol Explanation Symbol Explanation Alert you to pay special attention Caution of high voltage Alternating current source(AC)…
-
Model NO
Type OLS3S15KE Model NO. Type OLS3S15KEXL Standard OLS3S20KE Extended backup time OLS3S20KEXL " XL" Model: Extended backup time. EPO Port RS232 Port USB Port Parallel Port Dry Contact (optional) Intelligent Slot Fan Maintenance Bypass Switch Neutral Switch Input Breaker Terminal Block Self-locking…
-
management to increase battery service life, optimize recharge time
Selectable High ECO mode or Converter mode operation. Start-on-battery capability for powering up the UPS even if utility power is not available. Standard communication options: one RS232 communication port, one USB communication port. Optional connectivity cards with enhanced communication…
-
Electrical Performance
Input Model OLS3S15KE(XL) /OLS3S20KE(XL) Frequency Phase Range Three-phase (45~55)/(54~66)Hz Power Factor ≥0.99 @ full load Output Voltage Regulation ±1% Load Type 0.9 lag Frequency Synchronized 50/60Hz±10% @Line mode ±0.1% of normal frequency @Battery mode THD<2% Full load (Linear Load) THDV THD<5%…
-
3.3. Operating Environment
Temperature Humidity Altitude Storage temperature 0℃~40℃ <95% <1000m -15℃~50℃ Note: if the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following: Altitude (M) 1000 1500 2000 2500 3000 Maximum Power 100% 95%…
-
4. Installation
4.1. Tools Tools Kit Phillips Lifter screwdriver Scissors Wrench 4.2. Unpacking Unpacking-step1 Unpacking-step2 Unpacking-step3 Unpacking-step4 9
-
4.3. Contains
User’s Manual UPS USB Cable Parallel Cable RS232 Cable Parallel Cable (optional) Terminal *PowerPanel® Business Edition software is available on our website. Please visit www.cyberpower.com and go to the Software Section for free download. CAUTION! Inspect the appearance of the UPS to see if there…
-
4.4. Electrical Installation
4.4.1. Notes for installation The UPS must be installed in a location with good ventilation, far away from water, inflammable gas and corrosive agents. Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5m of space on each side. Condensation to water drops…
-
Use cable cross section and protective device specification :
Model OLS3S15KE(XL)/OLS3S20KE(XL) Input Main1 L1,L2,L3 Min.conductor cross section 6mm² (UL1015 8AWG) 10mm² Max.conductor cross section Input Main1 breaker 60A,250Vac Input N, Main2 Min.conductor cross section 21mm² Max.conductor cross section 25mm² (UL1015 6AWG) Input Main2 breaker 100A,250Vac…
-
Note: Do not use the wall receptacle as the input power source for the UPS, as its
rated current is less than the UPS's maximum input current. Otherwise the receptacle may be burned and destroyed. 3) Connect the input and output wires to the corresponding input and output terminals according to the following diagram. Note: Make sure that the input and output wires and the input…
-
may have electricity. The parts inside the unit may still have hazardous voltage
after turning off the UPS. To make the UPS have no output, power off the UPS, and then disconnect the utility power supply. 9) Suggest charging the batteries for 8 hours before use. After connection, turn the M1/M2/N input breaker in the "ON" position, the UPS will charge the batteries…
-
Fig.4-4 Connnect the internal Battery Pack DC connectors
4.6. External Battery Pack Connecting Procedure 1) The nominal DC voltage of external battery pack is 240Vdc. To achieve longer backup time, it is possible to connect multi-battery packs, but the principle of "same voltage, same type" should be strictly followed. 2) Select the UL1015 6AWG (25mm²)…
-
4.7. EPO Connection
EPO (Emergency power off): when the emergency occurs, such as the failure of load, the UPS can cut off the output at once by operating the EPO port manually. The connection: Normally the EPO connector is closed with a wire on the rear panel (Fig.4-6), which is supplied in the accessory. Once the…
-
5. Operation
5.1. Display Panel The UPS has a five-button, dot matrix LCD with white text and a blue background. Besides the LCD, the UPS has four colorized LED to provide more convenient information. Fig.5-1 LCD Panel Control button functions: The Button Function Power on Turn on Turn off Enter ESC Exit…
-
UP
Down Press this button more than 200ms to move the focus to the up menu Press this button for more than 200ms to move the focus to the down menu LED definition: UPS State Normal (Green LED) Battery (Yellow LED) Bypass (Yellow LED) Fault (Red LED) ★ □ □ □ □ □ Bypass mode with no output Bypass mode…
-
identification, and settings through the front panel display
During powering on, the LCD would display the CyberPower logo for several seconds and then enter to the default page which shows the UPS status summary. On the UPS status screen it provides the following information: Status summary, including mode, load, battery and utility Alarm status, if any…
-
Then LCD will show the default UPS status summary screen after UPS finishing
self-test. 3) By pressing button continuously for more than 1 second,the buzzer will beep for 1s, UPS starts to turn on. 4) A few seconds later, the UPS turns into Battery mode. If the mains power comes back, the UPS will transfer to Line mode without output interruption of the UPS. Turning off UPS…
-
event menu and identification menu. See Fig.5-3
The control menu: By pressing on the menu of ″Control″, the display would enter the next control menu screen. 1) Buzzer mute 2) Battery test: is one command to control all UPS in a parallel system to do the battery test at the same time. 3) Clear EPO status: once EPO status is enabled, the UPS…
-
Alarm
-
Buzzer mute
Yes No Clr EPO status Buzzer mute EPO Bat test Single UPS off Yes No Battery test Yes No Single UPS off Yes No Please input Password … Sub settings Event 0001:12:00:00 Utility abnormal 1/10 Alarm 0002:12:00:00 Overload 1/10 Control Setting Events ID Events&alarms Fault Clear all events Clear all…
-
The setting menu:
Please contact your local distributor for further information before using the settings. Some settings would change the specification, and some settings would enable or disable some functions. The unsuitable option set by user may result in potential failures or protecting function loss, even…
-
Set running time
Day: hour: minute: second 0000:0000:00~9999:23:59:59 Restore default setting*** Running time Yes/NO *Password is AAAA when enabled. **Read the chapter of 6.1 and 6.2, before using ECO or Converter function. UPS need shut down, if change work mode from converter to others. ***UPS need shut down. 6.…
-
6.2. Converter Function
Brief introduction of Converter function: In converter mode, the UPS would free run with fixed output frequency (50Hz or 60Hz). Once the mains power is loss or abnormal, the UPS would transfer to Battery mode and the load is supplied continuously. The great virtue is the output frequency is fixed…
-
Fig.6-1 Parallel cable connect diagram
TO UTILITY Main Maintenance Bypass Switch Maintenance Bypass for Parallel Main I/P Breaker UPS3 I/P Breaker UPS2 I/P Breaker UPS1 I/P Breaker TO LOAD Fig.6-2 Parallel installation diagram 27 UPS3 O/P Breaker UPS2 O/P Breaker UPS1 O/P Breaker Main O/P Breaker
-
L1
MAIN1 INPUT MAIN2 INPUT L2 L L3 N OUTPUT N L N L2 L3 L N J1 N L J1 N J2 UPS2 O/P Breaker UPS2 Main2 I/P Breaker UPS2 Main1 I/P Breaker To Main2 I/P Breaker BATTERY + - + 1# Battery Package + - + 2# Baterry Package O/P Ground Main2 I/P Ground Main1 I/P Ground To Main1 I/P Breaker J2 UPS1 O/P Breaker…
-
10) Press the button
of one UPS, each UPS would start to turn on, all the UPS would transfer to the Line mode together. Measure the output voltage of each UPS separately to check if the voltage difference between them is less than 0.5V. If the difference is more than 0.5V, the UPS need to be regulated. 11) Press the…
-
Set the main maintenance bypass switch from ″UPS″ to ″BPS″, switch off the main output breaker and the main input breaker, the UPS would shut down. 4) Ensure the UPS shut down totally, remove the wanted UPS and reinstall the new UPS parallel system by following step 1) to 9) of the last chapter…
-
Bat over voltage
Over charged Battery voltage is Check if the battery quantity is right higher than normal Battery is over charged The UPS will turn off the charger until the battery voltage is normal Check the loads and remove some Over load Over load non-critical loads; Check if some loads are failed Charger fail…
-
The Main2 bypass input
Bypass differ of some UPS is connected to same input source different setting in Check the setting parallel system ECO function is ECO In Parallel cable. Check if the M2 breaker is closed. Ensure the UPS are disconnected Setting differ Check the building wiring and input ECO function is forbidden in…
-
DC under
Bus under Voltage Consult dealer. DC unbalance Bus unbalance Consult dealer. DC soft fail Bus soft start fail Consult dealer. Output soft fail Output soft start fail Consult dealer. Output volt low Output volt low Consult dealer. Output volt high Output volt high Consult dealer. 7.3. Trouble…
-
ventilation condition
5) The information (battery capacity, quantity) of external battery pack if the UPS is "XL" model. 6) Other information for complete description of the problem. 8. Battery Maintenance Battery replacement should be performed by qualified personnel. This series UPS only requires minimal maintenance.…
-
materials from the authorized distributors or service centers, so as to avoid
overheat or spark resulting in fire due to insufficient capacity. Do not dispose of batteries or battery packs in a fire, they may explode. Do not open or mutilate batteries, released electrolyte is highly poisonous and harmful to the skin and eyes. Do not short the positive and negative of…
-
Remove front panel and disconnect the connector on the LCD display board. 2) Disconnect the battery pack DC connectors and remove the battery fixed plate. DC Connector Battery fixed plate 3) Remove the battery pack from the cabinet. 4) Replace the old battery packs with the new ones. 5) Reconnect…
-
9. Communication Port
9.1. USB Interface The USB port is compliance with USB 1.1 protocol for its communication software. 9.2. Dry contact Interface(optional) This series UPS has independent dry contact interface. Please contact your local distributor for details. 9.3. RS232 Interface The RS232 port is available for UPS…