Инструкция на Модульные 3-фазные ИБП CyberPower серии HSTP33 (3:3)
Модульные 3-фазные ИБП CyberPower серии HSTP3T60/80/90/100/120/150/200/250/300/400/500KE с возможностью параллельного расширения, для достижения резервирования питания N+X для корпоративных приложений. Руководство по эксплуатации.
Загружаем документ…
Текст инструкции
-
User’s Manual
HSTP3T60/80/90/100/120/150 /200/250/300/400/500KE Cyber Power Systems, Inc. www.cyberpower.com
-
This manual contains information concerning the installation and operation of Tower UPS
Please carefully read this manual prior to installation. The Tower UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its agent). Not doing so could result in personnel safety risk, equipment malfunction and invalidation of warranty. Safety…
-
Move & Install
Danger Keep the equipment away from heat source or air outlets. In case of fire, use dry powder extinguisher only, any liquid Warning extinguisher can result in electric shock. Do not start the system if any damage or abnormal parts founded. Contacting the UPS with wet material or hands may…
-
this manual
Battery Safety All the battery maintenance and servicing procedures Danger involving internal access need special tools or keys and should be carried out only by trained personnel. WHEN CONNECTED TOGETHER, THE BATTERY TERMINAL VOLTAGE WILL EXCEED 400Vdc AND IS POTENTIALLY LEATHAL.…
-
you may become blind if acid enters your eyes and your skin may be damaged by the acid. At the end of battery life, the battery may have internal short circuit, drain of electrolytic and erosion of positive/negative plates. If this condition continues, the battery may have temperature out of…
-
1.1 System Configuration
The Tower UPS is configured by the following part: Power modules, Bypass & Monitoring module, and cabinet with manual Bypass switch. One or several battery strings should be installed to provide backup energy once the utility fails. The UPS structure is shown in Fig. 1-1. Manual Bypass Static Bypass…
-
rectifier/charger derives power from the AC mains input source and supplies DC power to
the inverter while simultaneously FLOAT or BOOST charging its associated backup battery. Manual Bypass Static Bypass Bypass Main Output Rectifier AC/DC Battery Inverter DC/AC Charge/ Discharge Fig.1-3 Normal mode operation diagram 1.3.2 Battery Mode Upon failure of the AC mains input power, the…
-
Manual Bypass
Static Bypass Bypass Main Output Rectifier AC/DC Battery Inverter DC/AC Charge/ Discharge Fig.1-5 Bypass mode operation diagram 1.3.4 Maintenance Mode (Manual Bypass) A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS becomes unavailable e.g. during…
-
Manual Bypass
Static Bypass Bypass Main Output Rectifier AC/DC Battery Inverter DC/AC Charge/ Discharge Fig.1-7 ECO Mode operation diagram Note There is a short interruption time (less than 10ms) when transfer from ECO mode to battery mode, it must be sure that the interruption has no effect on loads. 1.3.6…
-
30kVA
Power unit 50kVA Power unit Power unit 1~4 Power unit 1~10 Except for 400kVA and 500kVA, all of the factory configureuration Except for 400kVA and 500kVA, all of the factory configureuration 1.4.2 UPS Outlook The UPS outlook is shown as Fig.1-8-1 to Fig.1-8-5. Fig.1-8-1 60KVA System outlook…
-
Fig.1-8-3 150-200KVA System outlook-Front View
Fig. 1-8-4 250-300KVA System outlook-Back View 6 HSTP3T 60-500 KE User Manual
-
Fig. 1-8-5 400-500KVA System outlook-Back View
7 HSTP3T 60-500 KE User Manual
-
2.1 Location
As each site has its requirements, the installation instructions in this section are to act as a guide for the general procedures and practices that should be observed by the installing engineer. 2.1.1 Installation Environment The UPS is intended for indoor installation and uses forced convection…
-
Fig.2-1 Room reserved for the cabinet(Unit:mm)
Fig.2-2-1 Size of the 60KVA UPS (Unit : mm) 9 HSTP3T 60-500 KE User Manual
-
Fig.2-2-2
Fig.2-2-3 Size of the 80-120KVA for the cabinet(Unit:mm) Size of the 150-200KVA for the cabinet(Unit:mm) 10 HSTP3T 60-500 KE User Manual
-
Fig.2-2-4
Size of the 250-300KVA for the cabinet(Unit:mm) Fig.2-2-5 Size of the 400-500KVA for the cabinet(Unit:mm) 11 HSTP3T 60-500 KE User Manual
-
Ensure that the floor or installation support can bear the weight of the UPS, batteries, and
battery racks. The weight of batteries and battery racks depends on the site requirements. The weight for the UPS cabinet is shown in Table 2.1 Table 2.1 Weight for the cabinet Capacity Weight 60KVA 170Kg 80KVA 210Kg 90KVA 231Kg 100KVA 210Kg 120KVA 266Kg 150KVA 305 Kg 200KVA 350 Kg 250KVA 445 Kg…
-
Fig.2-4 Disassemble the case
4. Remove the protective foam around the cabinet. Fig.2-5 Remove the protective foam 5. Check the UPS. (a) Visually examine if there are any damages to UPS during transportation. If any, contact to the carrier. (b) Check the UPS with the list of the goods. If any items are not included in the list…
-
2.3 Positioning
2.3.1 Positioning Cabinet The UPS cabinet has two way of supporting itself: One is to support itself temporarily by the four wheels at the bottom, making it convenient to adjust the position of the cabinet;The other is by anchor bolts to support the cabinet permanently after adjusting the position…
-
Fig.2-9-3 Supporting structure of 150kVA, 200kVA, 250kVA and 300kVA (Bottom view,
unit:mm) Fig.2-9-4 Supporting structure of 400kVA and 500kVA (Bottom view, unit:mm) The steps to position the cabinet are as follows: 1. Ensure the supporting structure is in good condition and the mounting floor is smooth and strong. 2. Retract the anchor bolts by turning them counterclockwise…
-
cabinet, which helps distribute the weight over a larger area. For instance, cover the floor with
iron plate or increase the supporting area of the anchor bolts. 2.4 Battery Three terminals (positive, neutral, negative) are drawn from the battery unit and connected to UPS system. The neutral line is drawn from the middle of the batteries in series (See Fig.2-10). N + N - 40 batteries in series…
-
Fig.2-11-1 Cable Entry of 60kVA-200kVA
Fig.2-11-2 Cable Entry of 250kVA-300kVA 17 HSTP3T 60-500 KE User Manual
-
Fig.2-11-3 Top cable Entry of 400kVA and 500kVA
Fig.2-11-4 Bottom cable Entry of 400kVA and 500kVA 18 HSTP3T 60-500 KE User Manual
-
2.6 Power Cables
2.6.1 Specifications The UPS power cables are recommended in Table 2.2. Table 2.2 Recommended cables for power cables Contents Main Input Current(A) Main Input CableSection (mm²) A B C N Main Output Current(A) Main Output Bypass Input (Optional) Battery Input PE Main Input CableSection (mm²) A B C N…
-
Note
The recommended cable section for power cables are only for situations described below: Ambient temperature:30℃. AC loss less than 3%,DC loss less than 1%,The length of the AC power cables are no longer than 50 m and the length of the DC power cables are no longer than 30 m. Currents listed…
-
2.6.3 Circuit Breaker
-
Fig.2-12-2 Connections terminals of 150kVA and 200kVA
Fig.2-12-3 Connections terminals of 250kVA and 300kVA Fig.2-12-3 Connections terminals of 400kVA and 500kVA 22 HSTP3T 60-500 KE User Manual
-
3. Connect the protective earth wire to protective earth terminal (PE)
4. Connect the AC input supply cables to the Input terminal and AC output supply cables to the Output terminal. 5. Connect the Battery cables to the Battery terminal. 6. Check to make sure there is no mistake and re-install all the protective covers. Attention The operations described in this…
-
Fig.2-13-2 Dry contact &communication interface of 400kVA and 500kVA
2.7.1 Dry Contact Interface Dry contact interface includes port J2-J11 and the functions of the dry contact are shown in Table 2.5. Table 2.5 Functions of the port Port Name Function J2-1 J2-2 J3-1 J3-2 J4-1 J4-2 J4-3 J4-4 J5-1 TEMP_BAT TEMP_COM ENV_TEMP TEMP_COM REMOTE_EPO_NC +24V_DRY +24V_DRY…
-
J8-2
BAT_LOW_ALARM_NO J8-3 BAT_LOW_ALARM_GND J9-1 GENERAL_ALARM_NC J9-2 GENERAL_ALARM_NO J9-3 GENERAL_ALARM_GND J10-1 UTILITY_FAIL_NC J10-2 UTILITY_FAIL_NO J10-3 UTILITY_FAIL_GND Output dry contact (Normally open), function is settable. Default: Low battery alarming Common terminal for J8-1 and J8-2…
-
Remote EPO Input Port
J4 is the input port for remote EPO. It requires shorting NC and +24V and disconnecting NO and +24V during normal operation, and the EPO is triggered when opening NC and +24V or shorting the NO and +24V. The port diagram is shown in Fig.2-15, and port description is shown in Table 2.7. +24V +24V…
-
BCB Input Port
The default function of J6 and J7 are the ports of BCB. The port diagram is shown in Fig.2-17, and description is shown in Table 2.9. +24V +24V +24V BCB_DRV BCB_CONT BCB_ONL J7 J6 Fig.2-17 BCB Port Port J6-1 J6-2 J7-1 J7-2 Table 2.9 Description of BCB port Name Function BCB_DRIV BCB contact drive…
-
Port
J8-3 Name BAT_LOW_ALARM_GND Function Common terminal General Alarm Output Dry Contact Interface The default function of J9 is the general alarm output dry contact interface. When one or more warnings are triggered, an auxiliary dry contact signal will be active via the isolation of a relay. The…
-
Table 2.12 Utility failure warning dry contact interface description
Port Name J10-1 UTILITY_FAIL_NC J10-2 UTILITY_FAIL_NO J10-3 UTILITY_FAIL_GND Function Mains failure warning relay(normally closed) will be open during warning Mains failure warning relay (normally open) will be closed during warning Common terminal 2.7.2 Communication Interface RS232 RS485 and USB…
-
3.1 Introduction
This chapter introduces the functions and operator instructions of the operator control and display panel in detail, and provides LCD display information, including LCD display types, detailed menu information, prompt window information and UPS alarm information. 3.2 LCD panel for Cabinet The…
-
Indicators
Rectifier indicator Battery indicator State Steady green Flashing green Steady red Flashing red Off Steady green Flashing green Steady red Flashing red Off Steady green Bypass indicator Inverter indicator Steady red Flashing red Off Steady green Flashing green Steady red Flashing red Off Steady…
-
Continuous alarm
When system has serious faults (for example: fuse or hardware fault) 3.2.2 Control and Operation Keys Control and operation keys include four keys, which are used together with LCD touch screen. The functions description is shown in Table 3.3. Table 3.3 Functions of Control and operation keys…
-
Icon
Description Main input parameter(voltage, current, PF, frequency) History log, system information Function setting (display calibration, password setting, time setting, date format, communication protocol and language setting), system setting (used only for manufacturer) Battery data, battery…
-
Home page consists of Status bar, Information display, warning information and main menu
Status bar The Status bar contains the model of the product, capacity, operational mode, and the number of the power module and the time of the system. Warning Information Display the warning information of the cabinet. Information Display Users can check the information of the cabinet in this…
-
(Status) Normal, alarm, fault Current Time (format: 24 hours, hour :minute) Normal: UPS in normal condition Alarm: UPS has general alarm, such as AC input fault Fault: UPS fuse or hardware fault 3.4 Menu Window The Menu Window displays the menu name of data window, while the data window displays the…
-
Menu name
Settings Menu item Date format set Date & Time Language set Communication set Control password 1 set Battery maintenance test Command Battery self-check test Stop testing UPS system information Monitoring software version Rectified software version Inverted software version Serial No. Rated…
-
The Cabinet comprises sectors of title, information display, version running status,
information display and submenu. The sectors are described as follows. Title Display the information of the selected submenu. Running status The squares shown on the mini current path represent the various UPS power paths and show the current UPS operating status. (The green square indicating…
-
Submenu Name
Contents Meaning Power factor PF V Bypass Output Load Phase voltage Phase current Bypass frequency Power factor Phase voltage Phase current Output frequency Power factor Sout: Apparent Power Pout: Active Power Qout: Reactive power Load (The percentage of the UPS load) A Hz PF V A Hz PF kVA kW kVar %…
-
Information display
Display information of each submenu. Power unit information The users can choose the power unit to browse the information in the “Information display” sector. Colors of the square on the mimic current path represent the various power unit paths and show the current operating status. (a) The green…
-
Submenu
Name Output Load Information S-code Contents Meaning Input phase current of selected module Input frequency of selected module Input power factor of selected module Output phase voltage of selected module Output phase current of selected module Output frequency of selected module Output power factor…
-
The submenus are listed on the right side of the Setting page. Users can enter each of the
setting interfaces by touching the relevant icon. The submenus are described in details below in Table 3.9. Table 3.9 Description of each submenu of Setting Submenu Name Date & Time Contents Time setting Three formats: (a) year/month/day,(b) month/date/year,(c) date/month/year Setting time Current…
-
Submenu
Name Contents Auto Boost Period Auto Maintenance Discharge Period Meaning Setting the auto boost period Setting the period for auto maintenance discharge Setting the system mode: Single , parallel, Single ECO, parallel ECO, LBS, parallel LBS SERVICE System Mode RATE Configure the rated Parameter…
-
EPO-Set Emergency Power Off 12 Module On Less-Set Valid Inverter capacity is less then the load capacity 13 Module On Less-Clear Incident above disappears 14 Generator Input-Set Generator as the Ac Input Source 15 Generator Input-Clear Incident above disappears 16 Utility Abnormal-Set Utility (Grid)…
-
Output Overload-Set N# Power Module Output Over Load 53 Output Overload-Clear Incident above disappears 54 Inverter Overload Tout-Set N# Power Module Inverter Over Load Timeout 55 INV Overload Tout-Clear Incident above disappears 56 Inverter Over Temp.-Set N# Power Module Inverter Over Temperature…
-
Input Curr Unbalance-Set Input current is not balance 92 Input Curr Unbalance-Clear Incident above disappears 93 DC Bus Over Volt-Set DC bus over Voltage 94 DC Bus Over Volt-Clear Incident above disappears 95 REC Soft Start Fail-Set Rectifier soft start fails 96 REC Soft Start Fail-Clear Incident…
-
Log Clear Load On UPS Load On Bypass No Load Battery Boost Battery Float Battery Discharge Battery Connected Battery Not Connected Maintenance CB Closed Maintenance CB Open EPO 14 Module On Less 15 Generator Input 16 Utility Abnormal 17 Bypass Sequence Error 18 Bypass Volt Abnormal Bypass Module…
-
Exceed Tx Times Lmt 24 Output Short Circuit 25 Battery EOD 26 Battery Test 27 Battery Test OK Battery Maintenance Battery Maintenance OK Module inserted Module Exit Rectifier Fail Inverter Fail Rectifier Over Temp. Fan Fail Output Over load breaker open”, “Byp Sequence Err” and “Ip Neutral Lost”. If…
-
Inverter Overload
Tout 37 Inverter Over Temp. 38 39 On UPS Inhibited 40 Manual Transfer Byp 41 Esc Manual Bypass 42 Battery Volt Low 43 Battery Reverse 44 Inverter 45 Input Neutral Lost 46 47 Bypass Fan Fail Manual Shutdown Protect 2. If this alarm is true, measure the actual output current to confirm if the…
-
shuts down rectifier and inverter, and there’s on inverter output
Manual Boost Charge Manual Float Charge UPS Locked 51 Parallel Cable Error 53 Lost N+X Redundant 54 EOD Sys Inhibited 55 Battery Test Fail 56 Battery Maintenance Fail 57 Ambient Over Temp 58 REC CAN Fail 59 INV IO CAN Fail 60 INV DATA CAN Fail 61 Power Share Fail 62 Sync Pulse Fail 63 Input Volt…
-
Input Curr Unbalance 70 DC Bus Over Volt 71 REC Soft Start Fail 74 Relay Connect Fail Relay Short Circuit PWM Sync Fail 75 Intelligent Sleep 76 Manual Transfer to INV 77 Input Over Curr Tout No Inlet Temp. Sensor No Outlet Temp. Sensor Inlet Over Temp. Capacitor Time Reset Fan Time Reset Battery…
-
Bypass Fan Expired 87 Capacitor Expired 88 Fan Expired 89 INV IGBT Driver Block 90 Battery Expired 91 102 Bypass CAN Fail Dust Filter Expired Wave Trigger 103 Bypass CAN Fail 105 Firmware Error System Setting Error Bypass Over Temp. 108 Module ID Duplicate Working life of bypass fans is expired, and…
-
ESC Mute
B I Transfer to Bypass Fig.3-11 Operate menu The “Operate” menu includes FUNCTION BUTTON and TEST COMMAND. The contents are described in details below. FUNTION BUTTON Clear/Restore Buzzing Mute or Restore buzzing of the system by touching the icon Fault Clear Clear the faults by touching the…
-
By touching the icon
, the system transfers to the Battery mode. Thisfunction is used for maintaining the battery, which requires the normalityof the bypass and minimum capacity of 25% for the battery. Battery Boost By touching the icon Battery Float , the system starts boost charging. By touching the icon Stop…
-
4.1 UPS Start-up
4.1.1 Start in Normal Mode The UPS must be started up by commissioning engineer after the completeness of installation. The steps below must be followed: 1. Ensure all the circuit breakers are open. 2. One by one to turn on the output breaker (Q4), input breaker (Q1), bypass input breaker (Q2), and…
-
Note
When the system starts, the stored setting will be loaded. Users can browse all incidents during the process of the starting up by checking the menu Log. Users can check the information of the power unit by the keys in the front of it. 4.1.2 Start from Battery The start from battery is…
-
Press and hold the BYP key on the operator control panel for longer than two seconds and the system transfers to bypass mode. This needs to enable the switch behind the front door. As shown in Fig. 4-2. A Enable the switch Zoom in A area Fig. 4-2 Enable the switch Warning Ensure the bypass is…
-
bypass breaker, so need to used external circuit breakers). The maintenance bypass
supplies power to loads. Note 150kVA - 300kVA only have a manual bypass breaker. In manual bypass mode (The manual bypass supplies power to loads), dangerous voltages are present on terminal and internal copper bar. 150kVA - 300kVA need to use external circuit breakers (Includes external input…
-
(a) 60kVA – 120kVA
(a) 150kVA – 500kVA Fig.4-3 Battery maintenance 2. Auto discharging. The system cans maintenance the battery automatically when the setting is done. The setting procedures are as follows. (a) Enable battery auto discharge. Enter the “CONFIGURE” page of the menu Setting, tick the “Battery Auto…
-
Fig.4-4 Setting period for battery auto discharge Warning The load for the auto maintenance discharge should be 20%-100%,if not, the system will not start the process automatically. 4.4 EPO The EPO button located in the operator control and display panel (with cover to avoid disoperation, see…
-
(a) 60kVA – 120kVA
(b) 150kVA – 500kVA Fig. 4-5 EPO Button 4.5 Installation of Parallel Operation System The UPS system can have three cabinets in parallel. Two UPS cabinets are connected as is shown in Fig.4-6. 60 HSTP3T 60-500 KE User Manual
-
Power Supply
UPS1 UPS2 Output Power Supply Load Connected Fig. 4-6 Parallel diagram The parallel interfaces of 60kVA-300kVA are located in the front panel of the cabinet, and the 400kVA -500kVA are located inside the cabinet, open the panel can see. The parallel terminal is shown in Fig. 4-7. (a) The parallel…
-
(b) The parallel interfaces of 4000kVA and 500kVA
Fig. 4-7 Location of the Parallel board The control cables for the parallel operation must be connected with all single devices to form a closed loop, as is shown in Fig.4-8. Fig. 4-8 Parallel connection For more details of parallel operation, please refer to the “Instruction for Parallel Operation…
-
This chapter introduces UPS maintenance, including the maintenance instructions of power
module and monitoring bypass module and the replacement method of dust filter. 5.1 Precautions Only maintaining engineers can maintain the power module and monitoring bypass module. 1. The power module should be disassembled from top to bottom, so as to prevent any inclination from high gravity…
-
After the completion of maintenance, insert power unit and tighten the screws on both sides of the power unit. 6) One by one to turn on the output breaker, bypass input breaker, input breaker and battery breaker. 7) After 2 minutes, the bypass indicator LED goes green, and the load is powered…
-
9) Turn off the maintenance bypass breaker
10) After 30S, the rectifier starts, the rectifier indicator LED goes green, and then inverter starts. 11) After 60S, the system transfers to Normal mode. 5.4 Battery Setting The setting of battery needs to be done after the first time of powering off or any changes done on the batteries. The…
-
battery is 40, it means that there are 40 blocks of batteries and both the positive
and negative are 20 blocks of batteries. In the case of cell battery of 2V (usually with large capacity) is used, battery number should be the same as the block battery. The cell battery actually in use should be 240 cells (6*40), with both and positive and negative of 120 cells. The battery number…
-
For Lead-Acid battery, the cell voltage is suggested to set to 1.65V/cell at 0.6C, and
set to 1.75V at 0.15C For the LFPB battery, the cell voltage is suggested to set to 2.7V/cell at both 0.6C and 0.15C. 5.4.6 Charging Current Percent Limit This setting is for limiting the charging power, max current limit can be20% of the rated active power. The max current that one power unit can…
-
The system discharges the battery when the reaching the Auto maintenance
discharge period. This function should be enabled by checking the AutoMaint (Rate Setting->SysCodeSetting1) through the monitoring software, as shown in Fig.5-4. Fig.5-4 Enable the Auto maintenance Discharge period The EOD voltage of Auto maintenance Discharge is 1.05 times of the normal EOD…
-
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics. 6.1 Applicable Standards The UPS has been designed to conform to the following European and international standards: Table 6.1 Compliance with European and International Standards Item General safety requirements for UPS used…
-
Model
Mechanical Dimension (W*D*H) Weight color Protection Level, (IEC60529) Model Unit 150kVA 200kVA 250kVA 300kVA mm 650*960*1600 650*960*1600 650*970*2000 650*970*2000 kg N/A Black N/A IP20 Unit 400kVA 500kVA Mechanical Dimension (W*D*H) mm 1300*1100*2000 1300*1100*2000 Weight kg 810 900 color N/A…
-
VRLA
charge voltage Final discharging voltage ≤1 ≤5 2.4V/cell(selectable from : 2.30V/cell~2.45V/cell) % % Ripple voltage Ripple current Equalized V/cell (VRLA) Battery Charge V/cell Battery Charging Power Max Current kW Constant current and constant voltage charge mode 1.65V/cell(selectable from…
-
Current rating of
neutral cable Rated frequency Switch time (between bypass and inverter) Bypass voltage range Bypass frequency range Synchronized Range A 1.7×In 1.7×In Hz 50/60 50/60 ms Synchronized transfer: 0ms % Settable, default -20%~+15% Up limited: +10%, +15%, +20%, +25% Down limited: -10%, -15%, -20%, -30%…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.