Инструкция на Модульные 3-фазные ИБП CyberPower серии HSTP33 (3:3)
Модульные 3-фазные ИБП CyberPower серии HSTP3T15KE-C/ HSTP3T15KEBC-C/ HSTP3T20KE-C/ HSTP3T20KEBC-C с возможностью параллельного расширения, для достижения резервирования питания N+X для корпоративных приложений. Руководство по эксплуатации.
Загружаем документ…
Текст инструкции
-
User’s Manual
-
This manual contains information concerning the installation and operation of Tower UPS
Please carefully read this manual prior to installation. The Tower UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its agent). Not doing so could result in personnel safety risk, equipment malfunction and invalidation of warranty. Safety…
-
Move & Install
Danger Warning Attention Keep the equipment away from heat source or air outlets. In case of fire, use dry powder extinguisher only, any liquid extinguisher can result in electric shock. Do not start the system if any damage or abnormal parts founded. Contacting the UPS with wet…
-
in this manual
Battery Safety Danger All the battery maintenance and servicing procedures involving internal access need special tools or keys and should be carried out only by trained personnel. When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal. Battery…
-
eyes and your skin may be damaged by the acid. At the end of battery life, the battery may have internal short circuit, drain of electrolytic and erosion of positive/negative plates. If this condition continues, the battery may have temperature out of control, swell or leak. Be sure to replace…
-
1.1 System Configuration
The Tower UPS is configured by the following part: Rectifier, Charger, Inverter, Static Switch and Manual Bypass Switch. One or several battery strings should be installed to provide backup energy once the utility fails. The UPS structure is shown in Fig. 1-1. Fig.1-1 UPS Configuration 1.2 Operation…
-
1.2.2 Battery Mode
Upon failure of the AC mains input power, the inverter of power modules, which obtain power from the battery, supply the critical AC load. There is no interruption in power to the critical load upon failure. After restoration of the AC mains input power, the” Normal mode” operation will continue…
-
Fig.1-5 Maintenance mode operation diagram
Danger During Maintenance mode, dangerous voltages are present on the terminal of input, output and neutral, even with all the modules and the LCD turned off. 1.2.5 ECO Mode To improve system efficiency, UPS rack system works in Bypass mode at normal time, and inverter is standby. When the utility…
-
1.2.7 Frequency Converter Mode
By setting the UPS to Frequency Converter mode, the UPS could present a stable output of fixed frequency (50 or 60Hz), and the bypass static switch is not available. 1.3 UPS Structure 1.3.1 UPS Configuration The UPS configuration is provided in Table 1.1 Item Standard Backup Type Long Backup Type…
-
Fig.1-8 System outlook
Fig.1-9 15/20 kVA back appearance 5 HSTP3T 15/20KE-C/KEBC-C User Manual
-
2.1 Location
As each site has its requirements, the installation instructions in this section are to act as a guide for the general procedures and practices that should be observed by the installing engineer. 2.1.1 Installation Environment The UPS is intended for indoor installation and uses forced convection…
-
Fig.2-1-1 Size of the Long Backup Type (Unit : mm)
Fig.2-1-2 Size of the standard backup Type (Unit : mm) Fig.2-2 Room reserved for the cabinet(Unit:mm) 7 HSTP3T 15/20KE-C/KEBC-C User Manual
-
The weight for the UPS cabinet is shown in Table 2.1
Table 2.1Weight for the cabinet Configuration Weight 15kVA/20kVA Standard Backup Type 52kg(No Batteries Included) 15kVA/20kVA Long Backup Type 31kg 2.2 Unloading and Unpacking 2.2.1 Moving and Unpacking of the Cabinet The steps to move and unpack the cabinet are as follows: 1. Check if any damages…
-
4. Remove the protective foam around the cabinet
Fig.2-5 Remove the protective foam 5. Check the UPS. (a) Visually examine if there are any damages to UPS during transportation. If any, contact to the carrier. (b) Check the UPS with the list of the goods. If any items are not included in the list, contact to our company or the local office. 6.…
-
2.3 Positioning
2.3.1 Positioning Cabinet The UPS cabinet has two way of supporting itself: One is to support itself temporarily by the four wheels at the bottom, making it convenient to adjust the position of the cabinet;The other is by anchor bolts to support the cabinet permanently after adjusting the position…
-
2.4 Battery
Three terminals(positive,neutral,negative)are drawn from the battery unit and connected to UPS system. The neutral line is drawn from the middle of the batteries in series (See Fig.2-7). N + N batteries in series Fig.2-7 Battery string wiring diagram Danger The battery terminal voltage is of more…
-
2.6 Power Cables
2.6.1 Specifications The UPS power cables are recommended in Table 2.2. Table 2.2 Recommended cables for power cables Contents 15/20kVA Main Input Current(A) 18/28A A 6 Cable B 6 Section Main Input C 6 (mm²) N 6 Main Output Current(A) 15/23A A 6 Cable Main Output B 6 Section C 6 (mm²) N 6 Bypass…
-
Output
Cables crimped OT terminal M6 7mm 4.9Nm PE Cables crimped OT terminal M6 7mm 4.9Nm 2.6.3 Circuit Breaker The circuit breakers (CB) for the system are recommended in Table 2.4. Table 2.4 Recommended CB Installed position 15/20kVA Battery CB 32A,250Vdc Attention The CB with RCD (Residual Current…
-
Warning
Tighten the connections terminals to enough torque moment, refer to Table 2.3, and please ensure correct phase rotation. The grounding cable and neutral cable must be connected in accordance with local and national codes. When the cable holes does not goes through by cables, it should be…
-
J5-3
GND_DRY J6-1 BCB Drive J6-2 BCB_Status J7-1 GND_DRY J7-2 BCB_Online J8-1 BAT_LOW_ALARM_NC Ground for +24V Output dry contact, function is settable. Default: Battery trip signal Input dry contact, function is settable. Default: BCB Status and BCB Online, (Alert no battery when BCB Status is invalid).…
-
TEMP_ENV
TEMP_BAT Chapter 2 Installation Instruction J2 J3 Fig.2-11 J2 and J3 for temperature detecting Port J2-1 J2-2 J3-1 J3-2 Table 2.6 Description of J2 and J3 Name Function TEMP_BAT Detection of battery temperature TEMP_COM Common terminal ENV_TEMP Detection of environmental temperature TEMP_COM Common…
-
power supply; it indicates that the generator has been connected with the system. The interface diagram is shown in Fig.2-13, and interface description is shown in Table 2.8. +24V J5 GEN AUX-N.O. AUX-N.O. Generator Fig.2-13 Diagram of status interface and connection of generator Port J5-1 J5-2 J5-3…
-
Battery Warning Output Dry Contact Interface
The default function of J8 is the output dry contact interface, which presents the battery warnings of low or excessive voltage, when the battery voltage is lower than set value, an auxiliary dry contact signal will be activated via the isolation of a relay. The interface diagram is shown in…
-
Port
Name J9-2 GENERAL_ALARM_NO J9-3 GENERAL_ALARM_GND Function Integrated warning relay (normally open) will be closed during warning Common terminal Utility Fail Warning Output Dry Contact Interface The default function of J10 is the output dry contact interface for utility failure warning, when the…
-
Communication Port
Table 2.14 Pin assignment for communication port RS_232 RS_485 COMM Set : Modbus COMM Set : SNT Pin 1 2 Signal DCD TXD Description Data Carrier Detect Transmit Data Pin Signal 1 485_+ 2 485_- 3 RXD Receive Data 3 4 DTR Data Terminal Ready 4 5 GND Ground 5 6 DSR Data set Ready 6 7 RTS Request to Send…
-
3.1 Introduction
This chapter introduces the functions and operator instructions of the operator control and display panel in detail, and provides LCD display information, including LCD display types, detailed menu information, prompt window information and UPS alarm information. 3.2 LCD panel for Cabinet The…
-
Indicators
Bypass indicator Inverter indicator State Off Steady green Steady red Flashing red Off Steady green Flashing green Steady red Flashing red Off Steady green Load indicator Status indicator Steady red Flashing red Off Steady green Steady red Description Battery and battery converter normal, battery…
-
3.2.3 LCD Screen
After the monitoring system starts self-test, the system enters the home page, following the welcome window. The home page is shown in Fig.3-2. Home page consists of System Information Window, Menu Window and Current Command and Record Menu. Fig.3-2 Home page The description of LCD icons is shown in…
-
Select the icon, system enters the corresponding page; take the icon
for example, as shown in Fig.3-3. (Main Input) HOME A I/P MAIN B NEXT C 220.1 V 45.0 A 50.01 Hz 0.99 PF 220.1 V 45.0 A 50.01 Hz 0.99 PF 220.1 V 45.0 A 50.01 Hz 0.99 PF Fig.3-3 Main input page Select the icon of HOME , it will display the information of battery, as shown in Fig.3-4. BATTERY P.1 Batt…
-
3.3 System Information Window
System Information Window displays the current time and UPS model, as is shown in the following Table 3.5. Table 3.5 Description of System Information Window Content Description UPS mode:3-phase in 3-phase out 20kVA,standard HSTP3T20KE backup type 16:30 Current time 3.4 Menu Window The Menu Window…
-
Menu
name alarm Menu item on LCD History log Display calibration Date format set Function Settings Date & Time Language set Communication set Control password 1 set Battery maintenance test Command Battery self-check test Stop testing UPS system information Meaning Monitoring software version Rectified…
-
capacity
13 Less-Clear Incident above disappears 14 Generator Input-Set Generator as the AC Input Source 15 Generator Input-Clear Incident above disappears 16 Utility Abnormal-Set Utility (Grid) Abnormal 17 Utility Abnormal-Clear Incident above disappears 18 19 Bypass Sequence Error-Set Bypass Sequence…
-
INV Overload Tout-Clear Incident above disappears 54 Inverter Over Temp.-Set Inverter Over Temperature 55 Inverter Over Temp.-Clear Incident above disappears 56 On UPS Inhibited-Set Inhibit system transfer from bypass to UPS (inverter) 57 On UPS Inhibited-Clear Incident above disappears 58 Manual…
-
DC Bus Over Volt-Clear Incident above disappears 93 REC Soft Start Fail-Set Rectifier soft start fails 94 REC Soft Start Fail-Clear Incident above disappears 95 Relay Connect Fail-Set Relay in open circuit 96 Relay Connect Fail-Clear Incident above disappears 97 Relay Short Circuit-Set Relay shorted…
-
4.1 UPS Start-up
The UPS must be started up by commissioning engineer after the completeness of installation. The steps below must be followed: 1. Ensure all the circuit breakers are open. 2. Close the output circuit breaker (CB) and then the input CB and the system starts initializing. If the system has dual…
-
4.2 Procedure for Switching between Operation Modes
4.2.1 Switching the UPS into Battery Mode from Normal Mode The UPS transfers to Battery model immediately after input circuit breaker disconnects from the utility. 4.2.2 Switching the UPS into Bypass Mode from Normal Mode Manual Byp Follow the path by selecting the icon of the system to Bypass Mode.…
-
Waring
Once the cover on the maintenance bypass breaker is removed, the system will transfer to bypass mode automatically. Waring Before making this operation, confirm the messages on LCD display to be sure that bypass supply is regular and the inverter is synchronous with it, so as not to risk a short…
-
BACK
FUNCTION END ManualByp/Esc Batt. Test Fault Clear Maint Test Manual INV Stop Test Fig.4.3 Battery maintenance 4.4 EPO The EPO button located in the operator control and display panel (with cover to avoid disoperation, see Fig.4-5) is designed to switch off the UPS in emergency conditions (e.g.…
-
4.5 Installation of Parallel Operation System
4.5.1 Parallel system diagram Up to four UPS could be paralleled,with a diagram as shown in Fig.4-6. Power Supply UPS1 UPS2 UPS3 UPS4 Output Power Supply Load Connected Fig. 4-6 Parallel diagram The parallel board is located at the back of the UPS cabinet, as is shown in Fig.4-7. 34 HSTP3T…
-
A
Fig.4-7 Location of the Parallel board All the parallel cables are designed to be shielded and double insulated, and are connected between the UPS to form a loop as shown below in Fig. 4-8. Fig.4-8 Parallel connection 35 HSTP3T 15/20KE-C/KEBC-C User Manual
-
4.5.2 Parallel system setting
Parallel system connection For field installation, please connect the cables according to Fig.4-6 and Fig.4-8. In order to assure that all units are equally utilized and to comply with relevant wiring rules, the following requirements apply: 1. All units shall be of the same rating and must be…
-
1. Parallel boards settings
A. For single UPS, no need parallel board. When a parallel board is installed, connectors of J33 to J42 should be shorted by the jumpers. B. For 2 UPS in parallel, short the connectors of J33/J35/J37/J39/J41 by jumpers on each board, keep connectors of J34/J36/J38/J39/J42 open C. For 3 or 4 UPS in…
-
This chapter introduces UPS maintenance, including the maintenance instructions of power
module and monitoring bypass module and the replacement method of dust filter. 5.1 Precautions 1. Only certified engineers are authorized to maintain the UPS. 2. The components or PCBs should be disassembled from top to bottom, so as to prevent any inclination from high gravity center of the…
-
Warning
If a battery has leakage or is damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations. The waste lead-acid battery is a kind of hazardous waste and is one of the major contaminants controlled by government. Therefore, its…
-
2. Install battery and fix the crossbeams
3. Connect the battery cable according to the series number 4. Recover the cover Fig.5-1 Installation of inner battery for15/20K standard UPS Warning Make sure the polarity of the battery is correct according to the diagrams above. Test and confirm the battery voltage before connectting to the main…
-
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics. 6.1 Applicable Standards The UPS has been designed to conform to the following European and international standards: Table 6.1 Compliance with European and International Standards Item Normative reference General safety…
-
Color
Protection Level IEC(60529) N/A BLACK,RAL 7021 N/A IP20 6.4 Electrical Characteristics 6.4.1 Electrical Characteristics (Input Rectifier) Item Grid System Rated AC Input Voltage Rated Frequency Input voltage range Input Frequency range Input Power factor THDI Table 6.5 Rectifier AC input Mains) Unit…
-
6.4.3 Electrical Characteristics (Inverter Output)
Item Rated capacity Rated AC voltage Rated Frequency Frequency Regulation Voltage precision Table 6.7 Inverter Output (To critical load) Unit Value kVA 15/20 Vac 380/400/415 (Line-Line) Hz 50/60 Hz 50/60Hz±0.1% % ±1.5(0~100% linear load) \ 110%, 60min; 125%,10min; 150%,1min; >150%,200ms Hz Settable…
-
6.5 Efficiency
Table 6.9 Efficiency Rated power(kVA) Unit 15/20kVA Overall efficiency Normal mode(dual conversion) % >95 Battery discharging efficiency (battery at nominal voltage 480Vdc and full-rated linear load) Battery mode % >94.5 6.6 Display and Interface Display Interface Table 6.10 Display and Interface…