Инструкция на Модульные 3-фазные ИБП CyberPower серии SM/SMX (3:3)
Модульные 3-фазные ИБП CyberPower серии SM30KPMX/ SM180KMFX/ SM300KMFX/ SM600KMFX с повышенной отказоустойчивостью, возможностью масштабирования, резервирования N+X, 'горячей заменой' модулей для ЦОД и защиты ответственных объектов. Руководство по эксплуатации.
Загружаем документ…
Текст инструкции
-
User’s Manual
SM30KPMX SM180KMFX SM300KMFX SM600KMFX CyberPower Systems, Inc. www.cyberpower.com
-
This manual contains information concerning the installation and operation of Modular UPS
Please carefully read this manual prior to installation. The Modular UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its agent). Not doing so could result in personnel safety risk, equipment malfunction and invalidation of warranty. Safety…
-
Move & Install
Danger Warning Attention Keep the equipment away from heat source or air outlets. In case of fire, use dry powder extinguisher only, any liquid extinguisher can result in electric shock. Do not start the system if any damage or abnormal parts founded. Contacting the UPS with wet…
-
in this manual
Battery Safety Danger All the battery maintenance and servicing procedures involving internal access need special tools or keys and should be carried out only by trained personnel. When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal. Battery…
-
eyes and your skin may be damaged by the acid. At the end of battery life, the battery may have internal short circuit, drain of electrolytic and erosion of positive/negative plates. If this condition continues, the battery may have temperature out of control, swell or leak. Be sure to replace…
-
1.1 System Configuration
The Modular UPS is configured by the following part: Power modules, Bypass & Monitoring module, and cabinet with manual Bypass switch. One or several battery strings should be installed to provide backup energy once the utility fails. The UPS structure is shown in Fig. 1-1. Manual Bypass Static…
-
1.2 Power Module
The power module structure is shown as Fig.1-3. The power module contains a rectifier, an inverter, and a DC/DC converter for charge and discharge of the external batteries. Input Rectifier AC/DC Battery Inverter DC/AC Output DC/DC Fig 1-3 Power module structure 1.3 Operation Mode The Modular UPS is…
-
Manual Bypass
Static Bypass Bypass Main Battery Rectifier AC/DC Inverter DC/AC Output Discharge DC/DC Fig.1-5 Battery mode operation diagram 1.3.3 Bypass Mode If the inverter overload capacity is exceeded under Normal mode, or if the inverter becomes unavailable for any reason, the static transfer switch will…
-
Manual Bypass
Static Bypass Bypass Main Rectifier AC/DC Battery Inverter DC/AC Output Charger DC/DC Fig.1-7 Maintenance mode operation diagram Danger During Maintenance mode, dangerous voltages are present on the terminal of input, output and neutral, even with all the modules and the LCD turned off. 1.3.5 ECO…
-
after a delay time when the AC main recovers. The mode and the delay time are
programmed by the commissioning engineer. 1.3.7 Frequency Converter Mode By setting the UPS to Frequency Converter mode, the UPS could present a stable output of fixed frequency (50 or 60Hz), and the bypass static switch is not available. 1.4 UPS Structure 1.4.1 UPS Configuration The UPS…
-
Fig.1-9 Outlook of 6-slot UPS
Fig.1-10 Outlook of 10-slot UPS Fig.1-11 Outlook of 20-slot UPS The UPS front view are shown in Fig.1-12 to Fig. 1-14 6 SM 180-600 KMFX User Manual
-
Fig.1-12 Front view of 6-slot UPS
Fig. 1-13 Front view of 10-slot UPS Fig. 1-14 Front view of 20-slot UPS ①LCD control panel; ②SPD; ③Manual Bypass switch ④Battery cold start; ⑤Monitoring &static bypass module; ⑥Monitoring unit; ⑦Static Bypass unit; ⑧Output switch of 20-slot cabinet Q3; ⑨Input switch of 20-slot cabinet Q1 The UPS…
-
Fig. 1-15 Back view of 6-slot UPS Fig. 1-16 Back view of 10-slot UPS Fig. 1-17 Back view of 20-slot UPS ①PDU; ②Bypass Input switch of 20-slot cabinet Q3; ③Manual bypass switch of 20-slot cabinet Q3 8 SM 180-600 KMFX User Manual
-
2.1 Location
As each site has its requirements, the installation instructions in this section are to act as a guide for the general procedures and practices that should be observed by the installing engineer. 2.1.1 Installation Environment The UPS is intended for indoor installation and uses forced convection…
-
(a.) 6-slot cabinet
(b.) 10-slot cabinet (c.) 20-slot cabinet Fig.2-1 Space reserved for the cabinet(Unit:mm) The dimension and weight for the UPS cabinet is shown in Table 2.1 Table 2.1 Weight for the cabinet Configuration 6-slot Cabinet (with bypass module) Dimension(W×D×H)(mm) Weight(Kg) 600×1100×1600 170 10 SM…
-
10-slot Cabinet
(with bypass module) 20-slot Cabinet (with bypass module) 30KVA power module 600×1100×2000 220 2000×1100×2000 620 460×790×133 34 2.2 Unloading and Unpacking 2.2.1 Moving and Unpacking of the Cabinet The steps to move and unpack the cabinet are as follows: 1. Check if any damages to the packing. (If…
-
4. Remove the protective foam around the cabinet
Fig.2-4 Remove the protective foam 5. Check the UPS. (a) Visually examine if there are any damages to UPS during transportation. If any, contact to the carrier. (b) Check the UPS with the list of the goods. If any items are not included in the list, contact to our company or the local office. 6.…
-
(see Fig.2-6)
Fig.2-6 Open the carton 4. Remove the foam cover (See Fig.2-7). Fig.2-7 Remove the foam cover 5. Take out the UPS with plastic package and dismantle the packaging materials. Attention The waste materials of unpacking should be disposed to meet the demand for environmental protection. 2.3 Positioning…
-
(a.) 6&10-slot cabinet
(b.) 20-slot cabinet ①Adjustable anchor bolt ②L-shape corner fittings ③ supporting wheels Fig.2-8 Supporting structure(Bottom view) The steps to position the cabinet are as follows: 1. Ensure the supporting structure is in good condition and the mounting floor is smooth and strong. 2. Retract the…
-
Attention
Auxiliary equipment is needed when the mounting floor is not solid enough to support the cabinet, which helps distribute the weight over a larger area. For instance, cover the floor with iron plate or increase the supporting area of the anchor bolts. 2.3.2 Installing Power Module The installation…
-
Attention Do not place the module on the floor by rear side with connectors; All installation works for bypass module and power module should be done by 2 persons together, for its heavy weight. 2.4 Battery Three terminals(positive,neutral,negative)are drawn from the battery unit and connected to…
-
(a.) Bottom entry
(b.) Top entry Fig.2-10 Cable entry for 6-slot cabinet Fig.3-11 Top entry for 10-slot cabinet 17 SM 180-600 KMFX User Manual
-
Bottom entry
Top entry Fig.3-12 Cable entry for 20-slot cabinet 18 SM 180-600 KMFX User Manual
-
2.6 Power Cables
2.6.1 Specifications The UPS power cables are recommended in Table 2.2. Table 2.2 Recommended cables for power cables 150/25 180/30 250/25 300/30 A B Cable (mm²) C N A B Cable (mm²) C N A B Cable (mm²) C N + Cable (mm²) N Cable PE (mm²) Contents Main Input Output Bypass Input (Optional) Battery PE…
-
Cables crimped
OT terminal Cables crimped OT terminal Cables crimped OT terminal Cables crimped OT terminal Cables crimped OT terminal Cables crimped OT terminal Cables crimped OT terminal Cables crimped OT terminal Battery Output PE Main Input Bypass Input 20-slot cabinet Battery Output PE M12 13mm 22Nm M12 13mm…
-
Fig.2-13 6-slot connections terminals
Fig.2-14 10-slot connections terminals Fig.2-15 20-slot connections terminals 3. Connect the protective earth wire to protective earth terminal (PE). 4. Connect the AC input supply cables to the Input terminal and AC output supply cables to the Output terminal. 5. Connect the Battery cables to the…
-
qualified technical personnel. If you have any difficulties, contact the manufacturer or agency
Warning Tighten the connections terminals to enough torque moment, refer to Table 3.3, and please ensure correct phase rotation. Before connection,ensure the input switch and the power supply are off,attach warnings label to warn not to operate by others The grounding cable and neutral cable…
-
Fig.2-17 Dry contact &communication interface for20-slot cabinet
The UPS accepts external signal from zero-voltage (dry) contacts connected through external dry contact terminals produced and phoenix terminals. Through software programming, these signals become active when these contacts connect to +24V to ground).The cables connected to DRY terminal must be…
-
Default: Utility abnormal alarming
J10-2 UTILITY_FAIL_NO Output dry contact, (Normally open) function is settable. Default: Utility abnormal alarming J10-3 UTILITY_FAIL_GND Common terminal for J10-1 and J10-2 Note The settable functions for each port can be set by the monitor software. The default functions of each port are described…
-
+24V
+24V +24V EPO_NO +24V +24V EPO_NC J4 Fig.2-16 Diagram of input port for remote EPO Table 2.7 Description of input port for remote EPO Name Function REMOTE_EPO_NC Trigger EPO when disconnect with J4-2 +24V_DRY +24V +24V_DRY +24V REMOTE_EPO_NO Trigger EPO when connect with J4-3 Port J4-1 J4-2 J4-3…
-
+24V
+24V +24V BCB_DRV BCB_CONT BCB_ONL J7 J6 Fig.2-18 BCB Port Port J6-1 J6-2 Table 2.9 Description of BCB port Name Function BCB contact drive, provides +24V voltage,20mA BCB_DRIV drive signal BCB contact status, connect with the normally BCB_Status open signal of BCB J7-1 GND_DRY Power ground for +24V…
-
General Alarm Output Dry Contact Interface
The default function of J9 is the general alarm output dry contact interface. When one or more warnings are triggered, an auxiliary dry contact signal will be active via the isolation of a relay. The interface diagram is shown in Fig.2-20, and description is shown in Table 2.11. GND ALARM_NO…
-
Port
Name Function J10-1 UTILITY_FAIL_NC J10-2 UTILITY_FAIL_NO J10-3 UTILITY_FAIL_GND Mains failure warning relay(normally closed) will be open during warning Mains failure warning relay (normally open) will be closed during warning Common terminal 2.7.2 Communication Interface RS232 RS485 and USB…
-
3.1 Introduction
This chapter introduces the functions and operator instructions of the operator control and display panel in detail, and provides LCD display information, including LCD display types, detailed menu information, prompt window information and UPS alarm information. 3.2 LCD panel for Power Module The…
-
3.2.2 Control and Operation Keys
The control and operation keys include FUNC keys and OFF key that have different functions: (a) The FUNC key is used for turning the display pages; (b) The OFF key is mainly for turning off the power module, as the following procedures: 1) Enable:LCD panel -> Menu Operate -> Enable Module “OFF” Key…
-
highlighted: Fault and warning codes are shown in Digit Displays Area in recycle (shown with short dash when less than 3).The meanings of the codes are listed in Table 3.2. flashing: Indicating a fault occurs. Energy bar of : (a) Flashing: Rectifier soft start; (b) Highlighted: The rectifier is…
-
Rectifier fail 97 Power share fail 49 Inverter fail 109 51 Rectifier over temperature Fan fail Output overload Output overload time out Inverter over temperature UPS inverter Inhibited Low battery Inverter bridge open Temperature difference over limit Input current unbalanced DC bus over voltage…
-
Indicator
State Off Description Rectifier not operating Steady green Battery charging Flashing green Battery discharging Battery abnormal (battery failure, no battery or battery reversed) or Battery Steady red indicator battery converter abnormal (failure, over current or over temperature) , EOD Flashing red…
-
INV
MUTE Long press, transfer to the inverter Long press to switch between turning off and on the buzzing Attention When bypass frequency is over track, there is interruption time(less than 10ms) for transferring from bypass to inverter. 3.3.3 LCD touch Screen Users can easily browse the information…
-
Fig.3-5 Structure of menu tree
3.4 Main Menu The main menu includes Cabinet, Module, Setting, Log, Operate and Scope and it is described in details below. 3.4.1 Cabinet Touch the icon , (At the bottom left of the screen), and the system enters the page of the Cabinet, as it is shown in Fig.3-6. Title Operating information…
-
The Cabinet comprises sectors of title, information display, version running status,
information display and submenu. The sectors are described as follows. Title Display the information of the selected submenu. Running status The squares shown on the mini current path represent the various UPS power paths and show the current UPS operating status. (The green square indicating…
-
Submenu Name
Contents Meaning V Bypass Output Load Battery A Phase voltage Phase current Hz Bypass frequency PF V Power factor A Phase current Hz Output frequency PF Power factor kVA Sout: Apparent Power kW Pout: Active Power kVar Qout: Reactive power % Load (The percentage of the UPS load) V A Capacity (%)…
-
Information display
Display information of each submenu. Power module information The users can choose the power module to browse the information in the “Information display” sector. Colors of the square on the mimic current path represent the various power module paths and show the current operating status. (a) The…
-
Submenu Name
Output Load Information S-code Contents V Meaning Output phase voltage of selected module A Output phase current of selected module Hz Output frequency of selected module PF Output power factor of selected module V KW Load voltage of selected module Load (The percentage of the power module selected)…
-
Submenu
Name Date&Time Contents Meaning Time setting Three formats: (a) year/month/day, (b) month/date/year,(c) date/month/year Setting time Current language Language in use Date format setting Language Language selection Device Address RS232 Protocol Selection COMM. Baudrate Modbus Mode Modbus parity…
-
Submenu
Name Contents Meaning Single ECO, parallel ECO,LBS, parallel LBS RATE Configure Parameter the CONFIGURE Configure the system rated For the factory use For the factory use Note Users have various permissions to the configuration of the Setting :( a) for the Date &Time, LANGUAGE and COMM, user can…
-
the time stamp when it occurs, as is marked in the red box
Sequence number The serial number for the event. Content of the event Display the information of events, warnings and faults. (0# means the event happens to the cabinet, n# means the information is sent by the nth power module.) Time for the Event The time the event occurs. Total Log Items…
-
Byp Freq Over Track-Set Bypass Frequency Over Track Range 29 Byp Freq Over Track-Clear Event above disappears 30 Exceed Tx Times Lmt-Set Transfer times (from inverter to bypass) in 1 hour exceed the limit. 31 Exceed Tx Times Lmt-Clear Event above disappears 32 Output Short Circuit-Set Output shorted…
-
Inverter Protect-Clear Event above disappears 69 Input Neutral Lost-Set Input Grid Neutral Lost 70 Bypass Fan Fail-Set Bypass Module Fan Fail 71 Bypass Fan Fail-Clear Event above disappears 72 Manual Shutdown-Set N# Power Module Manually Shutdown 73 Manual Boost Charge-Set Manually Battery Boost…
-
Note
Different colors of the words represent different level of events: (a)Green, an event occurs; (b)Grey, the event occurs then clears; (c)Yellow, warning occurs; (d) Red, faults happen. 3.4.5 Operate Touch the icon (At the bottom of the screen), and the system enters the page of the “Operate”, as it…
-
Enable the switch for powering off the Power Module by touching the icon
. Reset Battery History Data Reset the battery history data by touching the icon times of discharge, days for running and hours of discharging. , the history data includes the Reset Dust filter Using Time Reset the time of dust filter using by touching the icon using and maintenance period. , it…
-
Fig.3-13 Scope Menu
Users can view the waves for output voltage, output current and bypass voltage by touching the corresponding icon in the left side of the interface. The waves can be zoomed in and zoom out. Touch the icon to display the 3 phase output voltage. Touch the icon to display the 3 phase output…
-
4.1 UPS Start-up
4.1.1 Start in Normal Mode The UPS must be started up by commissioning engineer after the completeness of installation. The steps below must be followed: 1. Ensure all the external circuit breakers are open. 2. Close the input external circuit breakers and the system starts initializing. If the…
-
menu Log
Users can check the information of the power module by the keys in the front of it. 4.1.2 Start from Battery The start from battery is referring to battery cold start. Take the 10-slot UPS as example, the steps for the start-up are as follows: 1. 2. Confirm the battery is correctly connected…
-
(b) Press and hold the BYP key on the operator control panel for longer than two seconds and
the system transfers to bypass mode. This needs to enable the switch behind the front door. See Fig.4-3. Fig.4-3 Enable the switch Warning Ensure the bypass is working normally before transferring to bypass mode. Or it may cause failure. 4.2.3 Switching the UPS into Normal Mode from Bypass Mode Two…
-
Warning
Before making this operation, read messages on LCD display to be sure that bypass supply is regular and the inverter is synchronous with it, so as not to risk a short interruption in powering the load. Danger If you need to maintain the power module, wait for 10 minutes to let the DC bus capacitor…
-
2. Auto discharging. The system can maintenance the battery automatically when the setting
is done. The setting procedures are as follows. (a) Enable battery auto discharge. Enter the “CONFIGURE” page of the menu Setting, tick the “Battery Auto Discharge” and confirm (This needs to be done by factory). (b) Setting period for battery auto discharge. Enter the “BATTERY “page of the Setting…
-
Fig .4-6 EPO Button
4.5 Installation of Parallel Operation System For the 6-slot and 10-slot system ,it can have three UPS cabinets in parallel,which can extend to a capacity of total 900KVA.Howerever, for the 20-slot system, parallel is not supported at present. Two UPS cabinets are connected as is shown in Fig.4-6.…
-
Fig.4-7 Location of the Parallel board
The control cables for the parallel operation must be connected with all single devices to form a closed loop, as is shown in Fig.4-8. Fig.4-8 Parallel connection For more details of parallel operation, please refer to the “Instruction for Parallel Operation of Modular UPS”. 54 SM 180-600 KMFX User…
-
This chapter introduces UPS maintenance, including the maintenance instructions of power
module and monitoring bypass module and the replacement method of dust filter. 5.1 Precautions 1. Only certified engineers are authorized to maintain the UPS. 2. The components or PCBs should be disassembled from top to bottom, so as to prevent any inclination from high gravity center of the…
-
5.3.2 Maintaining Static Bypass Unit for 20-slot Cabinet
1. Transfer the system to bypass mode through the LCD control panel (Refer to section4.5.5); 2. Open the battery switch, Close maintenance bypass switch; the UPS power will be supplied by maintenance bypass; 3. Open the Main Input switch, Input Bypass switch and UPS output switch; 4. Disconnect…
-
5.3.5 Disconnect the Inner Control Neutral cable
Inner control Neutral cable can be disconnected by turning off the Neutral Cable Switch. By doing this, the Auxiliary power supply is cut off from the utility. 6-slot cabinet and 10-slot cabinet doesn’t need to disconnect the inner control neutral cable. The Inner Control Neutral Cable is located in…
-
Fig.5-3 Configuration through monitoring software
5.4.1 Setting of Battery Type The battery type can be only set through the monitoring software. The system at present supports lead acid battery and Lithium iron phosphate battery (LFPB). 5.4.2 Setting of Battery Number 1) Setting battery number for Lead- Acid battery The nominal voltage of one…
-
5.4.5 EOD Voltage Setting
The EOD voltage 0.6C is the EOD voltage when the discharging current is larger than 0.6C; EOD voltage 0.15C is the EOD voltage when the discharging current is less than 0.15C.EOD voltage decreases linearly as the EOD voltage Current increases from 0.15C to 0.6C, as shown in Fig.6-4. Fig.5-4 EOD…
-
Fig.5-5 Enable the Auto maintenance Discharge period
The EOD voltage of Auto maintenance Discharge is 1.05 times of the normal EOD voltage. 5.4.11 Warnings for Battery and Environment Temperature Overheat This function can be set through the monitoring software. The system will read the temperature information of the battery and environment and give…
-
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics. 6.1 Applicable Standards The UPS has been designed to conform to the following European and international standards: Table 6.1 Compliance with European and International Standards Item Normative reference General safety…
-
Table 6.4 Mechanical Characteristics for Power Module
Item Mechanical Dimension, W*D*H Weight Unit 30KVA mm 460*790*134 kg 34 6.4 Electrical Characteristics 6.4.1 Electrical Characteristics (Input Rectifier) Item Grid System Rated AC Input Voltage Rated Frequency Input voltage range Input Frequency range Input Power factor THDI Table 6.5 Rectifier AC…
-
6.4.2 Electrical Characteristics (Intermediate DC Link)
Table 6.6 Battery Items Battery bus voltage Quantity of lead-acid cells Float charge voltage Temperature compensation Ripple voltage Ripple current Equalized charge voltage Unit Vdc Parameters Rated:±240V Nominal 40=[1 battery(12V)] ,240=[1 battery(2V)] V/cell (VRLA) 2.25V/cell(selectable from…
-
6.4.4 Electrical Characteristics (Bypass Mains Input)
Table 6.8 Bypass Mains Input Item Unit Rated AC voltage Vac Rated AC Current A Overload % Current rating of neutral cable Rated frequency Switch time (between bypass and inverter) Bypass voltage range Bypass frequency range Synchronized Range 380/400/415 (three-phase four-wire) 454 110% Long term…