User’s Manual
SM20KPM SM200KMF SM120KMF SM060KMF CyberPower Systems, Inc. www.cyberpower.com
-
Safety Precautions
Safety Precautions This manual contains information concerning the installation and operation of Modular UPS . Please carefully read this manual prior to installation. The Modular UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its agent). Not…
-
Safety Precautions
Battery voltage higher than 400Vdc All the battery maintenance and servicing procedures involving internal access need special tools or keys and should be carried out only by trained personnel. SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH THIS EQUIPMENT. WHEN…
-
1.1 Introduction
This chapter introduces the relevant requirements for positioning and cabling of the Modular UPS and related equipment. Because each site has its requirements, it is not the aim of this chapter to provide step-by-step installation instructions, but to act as a guide for the general procedures and…
-
1.3.2 External Battery Room
The battery will generate some amount of hydrogen and oxygen at the end of charging, so the fresh air volume of the battery installation environment must meet EN50272-2001 requirements. The ambient temperature of the battery must be stable. Ambient temperature is a major factor in determining the…
-
1.4.3 Clearances Required for Operating
As rack module UPS has no ventilation grills at either sides, no clearances are required for the sides. To enable routine tightening of power terminations within the UPS, it is recommended that clearance around the front of the equipment should be sufficient to enable free passage of personnel with…
-
(b) 6 module cabinet
(c) 3 module cabinet Fig.1- 1: UPS structure Table.1- 1: UPS Configuration List Item Component 1 System Display 2 Bypass module 3 Input/output/maintenance bypass breakers 4 Power module Quantity Remarks Requisite, factory installed Requisite, factory installed Requisite, factory installed 1 ≤n ≤10…
-
Fig.1- 2: Power Module Installation Diagram
1.4.9 Cable Entry Cables can enter the module UPS rack system and battery cabinet both from bottom and top. Cable entry is made possible through a blanking plate fitted at the bottom or top of the equipment. The recommended installation practice is to install glands to prevent foreign material or…
-
1.5.2 External Battery
The DC compatible circuit breaker provides over current protection for UPS system and battery, which is provided by the external battery cabinet. See Appendix A for a selection guide. 1.5.3 UPS Output In the eventuality that an external distribution panel is used for load distribution, the selection…
-
1.6.1 Cable Connections
Note The operations described in this section must be performed by authorized electricians or qualified technical personnel.. If you have any difficulties, do not hesitate to contact our Customer Service & Support department. After the equipment has been finally positioned and secured, refer to…
-
Battery warning output dry contact interface Battery circuit breaker interface Mains failure warning output dry contact interface Intelligent card interface User communication interface The UPS dry contact board provides input dry contacts and output dry contacts. Fig.1- 4: Front Panel of…
-
or shorting NO and +24v. The port diagram is shown in fig.1-6, and port description is shown in table.1-4. +24V EPO_NO EPO_NC +24V J4 Fig.1- 6: Diagram of input dry contact for remote EPO Table.1- 4: Description of Input Dry Contact for Remote EPO Position Name Purpose J4.1 EPO_NC EPO is activated…
-
+24V
J5 GEN AUX-N.O. AUX-N.O. Generator Fig.1- 7: Connection of Generator Table.1- 5: Description of Status Interface and Connection of Generator Position Name Purpose J5.1 +24V Internal +24V power supply J5.2 GEN Connection status of generator J5.3 GND Power ground Note All auxiliary cables must be…
-
Note
All auxiliary cables must be double insulated twisted cables with cross sectional area of 0.5mm2 ~ 1.5mm2 for maximum connection length between 25m and 50m. 1.7.6 Dry Contact Interface: Battery Warning Output (J8) J8 is the output dry contact interface, which outputs the battery warnings of low or…
-
Table.1- 8: Integrated warning dry contact interface description
Position Name Purpose J9.1 ALARM_NC Integrated warning relay (normally closed) will be open during warning J9.2 ALARM_NO Integrated warning relay (normally open) will be closed during warning J9.3 GND Common connection Note All auxiliary cables must be double insulated twisted cables with cross…
-
2.1 General Recommendations
Take special care when operating the batteries of the Modular UPS system. When all the battery cells are connected, the battery voltage can exceed 400Vdc, which is potentially lethal. Note The precautions for battery installation, use and maintenance are to be provided by the batteries…
-
2.2 Battery Typologies
Traditional: consisting of one of more strings of battery blocks installed on shelves in a locked cabinet or dedicated battery room. Note The Traditional external battery cabinet can make use of each even number of battery per string between 36 and 44. The default factory setting, if the unit is…
-
2.2 Battery Maintenance
For the battery maintenance and precautions, please refer to IEEE-Std-1188-2005 and the relevant manuals provided by the battery manufacturers. Battery Maintenance Note Check to ensure that all the safety devices are in place and function normally. Check if the battery management…
-
Chapter 3 Installation of UPS Rack System and Parallel System
Chapter 3 Installation of UPS Rack System and Parallel System 3.1 Overview The single or parallel system should be installed according to the installation procedures of the UPS rack module system and the requirements in this Chapter. For single UPS rack module installation the EPO button on the…
-
Chapter 3 Installation of UPS Rack System and Parallel System
3.2.3 Power Cables The power cable connection of the parallel rack module system is similar to that of the single UPS rack module system. If the bypass input and rectifier input share the same neutral terminal and if an RCD protective device is installed at the input, then the RCD device must be…
-
SNMP Card
To User Safety Ground SNMP ENV. Temperature J3 EPO J4 GEN J5 J6 BCB General Alarm J9 Utility Fail J10 Main Supply Bypass Supply External Batt. + N - J8 Connect to Critical Load Power Cables Rack Modular UPS system J7 Batt. Low Alarm Output J2 Dry Contact Board GJ Batt. Temperature Input RS485…
-
Fig.4- 2: External Battery Connection
External BCB interface: BCB DRV: J6-1 BCB drive signal BCB STATUS: J6-2 BCB contactor status, normally opened. Shorted to GND when activated GND: J7-1 ground Fig.4- 3: 200KVA UPS Module System, Front View and Rear View without Door Fig.4- 4: 120KVA UPS Module System, Front View and Rear View…
-
Fig.4- 5: 60KVA UPS Module System, Front View and Rear View without Door
Top view Fig.4- 6: 200KVA UPS External Dimensions Modular UPS SM series User Manual 27
-
Fig.4- 7: 120KVA UPS External Dimensions
Fig.4- 8: 60KVA UPS External Dimensions Modular UPS SM series User Manual 28
-
(a)
200KVA UPS power connection (b) 120KVA UPS power connection (c) 60KVA UPS power connection Fig.4- 9: Power Connection of Module System UPS Fig.4- 10: Power Module Modular UPS SM series User Manual 29
-
Fig.4- 11: Static Bypass Module
Notes for installing modules: 1. When installing the modules, install the modules from bottom to top. When removing the modules, remove the modules from top to bottom. The purpose is to maintain the stable center of gravity. 2. After inserting the module, tighten all the screws. 3. When removing the…
-
Warning: Hazardous mains voltage and/or battery voltage present(s) behind the protective cover
The components that can only be accessed by opening the protective cover with tools cannot be operated by user. Only qualified service personnel are authorized to remove such covers. 5.1 Introduction The Modular UPS rack system provides the critical load (such as communication and data processing…
-
through a separate switch. Where a separate power source is not available, the bypass and rectifier input supply connections are linked. Note Split-Bypass Input function is optional. Default of factory is single input. 5.1.2 Static Transfer Switch The circuit blocks labeled Static Switch in fig.5-1…
-
Note
Optional isolation transformers are available for applications where sources do not share the same neutral reference or where the neutral is not available. 5.3 Operating Mode The Modular UPS is an on-line, double-conversion, reverse-transfer UPS that permits operation in these modes: Normal mode …
-
5.3.8 Eco Mode
To improve system efficiency, UPS rack system works in bypass mode at normal time, and inverter is standby. When utility fails, UPS transfer to battery mode, and inverter power the loads. The efficiency of ECO system can be up to 98%. NOTE: There is a short interruption time (lower than 10ms) when…
-
Warning-Hazardous mains voltage and/or battery voltage present(s) behind the protective cover
The components that can only be accessed by opening the protective cover with tools cannot be operated by user. Only qualified service personnel are authorized to remove such covers. 6.1 Introduction The Modular UPS operates in the following 3 modes listed in table.6-1. This section describes…
-
LED
Status Rectifier indicator Battery indicator Bypass indicator Inverter Indicator Load indicator Status indicator Green Red Green Off Green Green Note The output circuit breaker (Q3) must be closed first, followed by input circuit breaker (Q1), or the rectifier cannot be started. 3. The inverter…
-
Fig.6- 1: Location of Battery Cold Start Button
6.3 Procedure for Switching the UPS between Maintenance Bypass and Normal Mode 6.3.1 Procedure for Switching from Normal Mode to Maintenance Bypass Mode This procedure can transfer the load from the UPS inverter output to the maintenance bypass supply, but the precondition is that the UPS is in…
-
Warning
Before opening the maintenance breaker (Q2), make sure that static bypass switch is working according power flow displayed on LCD. 3. After about 60s, UPS transfers to inverter. Close external battery breaker. 6.4 Procedure for Completely Powering Down a UPS If you need to power down the UPS…
-
Maintenance guidance for power modules
If the system is normal mode and the bypass is normal, the redundant number of power module is at least 1: 1. Press “off” button on the front panel of power module to manually power off power module. 2. Loosen the screws of the main power module and remove the module after 2 minutes. If there are no…
-
This chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail, and provides LCD display information, including LCD display types, detailed menu information, prompt window information and UPS alarm list. 7.1 Introduction The operator…
-
7.1.1 Mimic Current Path
The LEDs shown on the mimic current path represent the various UPS power paths and show the current UPS operating status. The status description of indicators is shown in table.7-2. Table.7- 2: Status Description of Indicator Indicator State Purpose Steady green Rectifier normal for all modules…
-
7.2 LCD Display Type
Following the self-check of UPS LCD display, the main LCD display is shown as fig.7-2, which can be divided into three display windows: system information, data command and current record. Fig.7- 2: Main LCD Display The description of LCD icon is shown in table.7-5: Table.7- 5: Description of LCD…
-
7.3 Detailed Description of Menu Items
The LCD main display shown in fig.7-3 is described in details below. UPS information window UPS information window: display the current time and UPS name. The information of the window is not necessary for the user to operate. The information of this window is given in table.7-6. Table.7- 6…
-
Menu name
Menu item Meaning display panel please refer to table 4-8 History record (history alarm) Display all history alarm. The alarm list displayed on LCD of UPS operator control and display panel please refer to table 4-9 Menu Language (language option) 4 languages can be selected Display calibration…
-
EPO Emergency Power Off 14 Inverter on Less Available power module capacity is less than the load capacity. Please reduce the load capacity or add extra power module to make sure that the UPS capacity is big enough. 15 Generator Input Generator is connected and a signal is sent to the UPS. 16…
-
N# Fan Fail N# Output Over Load 34 N# INV Over Load Tout 35 N# INV Over Temp. 36 37 On UPS Inhibited 38 Manual Transfer Bypass 39 Esc Manual Bypass 40 Battery Volt Low 41 Battery Reverse signal disappears. If over temperature exists, check: 1. Whether the ambient temperature is too high. 2. Whether…
-
ManFloat Manually force the charger work in float charge mode. 48 Arrears Shutdown Reserved. 49 Lost N+X Redundant Lost N+X Redundant. There is no X redundant powers module in system. 50 EOD Sys Inhibited System is inhibited to supply after the battery is EOD (end of discharging) Modular UPS SM…
-
Chapter 8 Optional Parts
Chapter 8 Optional Parts 8.1 Replacing Dust Filters Each filter is held in place by a bracket on either side of each filter. To replace each filter: 1. Open the UPS front door and locate the filters on the back side of the front door (see Fig. 8-1). 2. Remove one bracket and loosen the screw on the…
-
This chapter provides UPS product specification
9.1 Applicable Standards The UPS has been designed to conform to the following European and international standards: Table.9- 1: Compliance with European and International Standards Item Normative reference General safety requirements for UPS used in EN50091-1-1/IEC62040-1-1/AS 62040-1-1 operator…
-
9.4 Electrical Characteristics (Input Rectifier)
Table.9- 4: Rectifier AC Input (mains) Items Unit Parameter Rated AC Input Voltage Vac 380/400/415 (three-phase and sharing neutral with the bypass input) Input voltage range Vac -40%~+25% Frequency1 Hz 50/60 (range: 40Hz~70Hz) Power factor kW/kVA, full load 0.99 THD THDI% 3 9.5 Electrical…
-
Rated capacity (kVA)
Unit 20~200 Steady state voltage stability % ±1 (balanced load) ±1.5 (100% imbalance load) Transient voltage response2 % ±5 THD % <1.5 (linear load) , <5 (non-linear load ) Synchronization Window - Rated frequency ±2Hz (selectable: ±1~±5Hz) Max change rate of synch frequency Hz/s 1: selectable…
-
Note
1. Factory setting is 400V. Commissioning engineers can set to 380V or 415V. 2. Commissioning engineers can set to 50Hz or 60Hz. For example, UPS is set to frequency inverter mode, and then bypass status will be neglected. 9.8 Efficiency Table.9- 8: Efficiency, Air Exchange Rated Efficiency (kVA)…