Remote Management Card
RMCARD205 / RMCARD305 User’s Manual The Remote Management Card allows a UPS system and environmental sensor to be managed, monitored, and configured. Copyright © 2020 CyberPower Systems, Inc. All rights reserved. K01-E000001-11
-
Introduction
Overview The CyberPower Remote Management Card allows for remote monitoring and management of a UPS attached to a network. After installing the hardware and configuring an IP address, the user can access, monitor, and control the UPS from anywhere in the world! Simply use a web browser, command line…
-
System Requirements
A 10/100Mbps Ethernet connection to an existing network Web Browser or SSH client (Optional) NMS (Network Management System) compliant with SNMP Application with PowerPanel® Business Unpacking Inspect the Remote Management Card upon receipt. The package should contain the following: …
-
Front Panel
RMCARD205 1. Universal Port 2. Ethernet Port RMCARD305 3. Tx/Rx Indicator 4. Link Indicator LED Status Indicators Link LED Condition Off The Remote Management Card is not connected to the Network/ or the Remote Management Card power is off On (Yellow) The Remote Management Card is connected to the…
-
Installation Guide
Step 1. Hardware Installation Note: The CyberPower Remote Management Card is hot-swappable, so you do not need to turn off the UPS to install it. 1. Remove the two retaining screws from the expansion slot and remove the cover. 2. Install the CyberPower Remote Management Card into the expansion slot.…
-
RMCARD305
Step 2. Configure the IP address for the CyberPower Remote Management Card Note: These instructions are for Windows OS. For other OS please refer to Appendix 4. Method 1: Using the Power Device Network Utility 1. Install the Power Device Network Utility available for download at…
-
5. You can modify the IP Address, Subnet Mask, and Gateway address for the Device MAC Address
listed in the Device Network Settings window, as shown in Figure 2. The factory default IP Address is 192.168.20.177 and the default Subnet Mask is 255.255.255.0. Figure 2. The Device Network setting window. 6. Modify the IP, subnet mask or gateway address. Enter the new addresses into the…
-
shown in Figure 4. Figure 4. Setup IP Address successfully message. 9. In case the change is not successful, for example, if the IP address change is unsuccessful you will see a warning message. Attempt to make the desired changes again. If the problem persists please see the Troubleshooting section…
-
Web Interface
Login User Account You will need to enter a User Name and Password to login to the interface, and can select a preferred language after login. There are two user account types. 1. Administrator - Default user name: cyber - Default password: cyber 2. View only - Default username: device - Default…
-
Definition
Envir Data Name The name of the environmental sensor. Location The location of the environmental sensor. Recent Device Events A list of the five most recent device events. All events are related to configuration changes. [UPS] The following items can be displayed/configured through the UPS page…
-
Remaining Runtime
Voltage Definition The amount of estimated time that the UPS can supply power to its load. The present voltage of the UPS battery. System Status The present operating status of the UPS. Temperature The operating temperature of the UPS. [UPS->Battery Status] Display the information of the built-in…
-
Information
Description The date that the batteries were last replaced. This must be set manually Battery Replacement Date after the batteries have been replaced or when the unit is first installed. If this date has not been set, it is recommended that it be set immediately. NCL Bank The amount of Non-Critical…
-
Generator Mode
Definition If the UPS uses generator as its input power, this option should enable the UPS to function normally. If this option is selected, the UPS will be forbidden to enter Bypass Mode or ECO Mode to protect the connected equipment. ECO Mode Economy mode. The UPS will enter Bypass Mode when the…
-
Returned Delay
Line Stable Delay Definition The Returned Delay will take effect every time when the UPS is turned on. When the UPS is in Battery Mode and utility power is restored, the UPS will wait for the specific delay time to change Battery Mode to Line Mode. When the UPS battery is lower than the Low Battery…
-
Definition
If this option is enabled, the UPS will detect if the input wiring is not Wiring Fault Detecting grounded or is reversed. It is recommended to insure the UPS wiring has a ground connection first. When the UPS is in Battery Mode with 0% for the time configured, the RMCARD will switch the UPS to Sleep…
-
[UPS->Bank Control] Display the current state of each outlet Bank, and it provides on/off control for the Non-Critical Outlet Bank. Outlet Number and Device Name displays the device name associated with the specific outlet. Item Bank Control Options Definition ON Turns non-critical bank on…
-
Runtime Estimation
Definition batteries will then be recharged automatically after the estimation is done. Note: This estimated runtime may vary based on the load and the level of charge on the batteries when the runtime estimation is initiated. The batteries will be recharged then automatically after the estimation…
-
[UPS->Wake on Lan] This function is used to wake a computer through the network. Enter the IP
address of that computer when it is on and the system will search its MAC address accordingly. The maximum number of IP addresses that can be set is 50. Item PowerPanel® Remote Load/Sync with PowerPanel® Remote List Definition Enable this option to Load and Synchronize WoL Client List with…
-
Node List
Definition EnergyWise Parent/Children List shows all EnergyWise entities and allows users to configure EnergyWise Entity attributes. Name The name used to identify each outlet. Role This parameter is a string used to describe the function of the entity (max length 31 characters). Keywords This…
-
[Envir] Following items can be displayed/configured through the Envir page. Note that Envir Tab only
appears when an ENVIROSENSOR is connected to the RMCARD. [Envir->Status] Display the basic information of the environmental sensor and contact closure inputs. Item Information Definition Name The name of the environmental sensor. Location The location of the environmental sensor. Temperature Current…
-
[Logs->Event Logs] Display the list of events and a brief description of each event along with the date and time stamp. Note: 1. The recordable events are listed under “System->Notifications->Event Action.” 2. The recorded time is using the 24-hour clock format. [Logs->Status Records] This page is…
-
[Logs->Graphing] This page is used to display the data of the Status Record. The graphing function
makes the status records easier to view. Item Graph Period Definition The period used to draw the graph. Longer periods will require more time to be displayed. Graph Data The data used to draw the graph. The more data selected, the more graphing time is needed. Graph Node Selecting “Display All…
-
[Logs->Syslog] Allow users to set syslog server and send test message
Item Definition Syslog Enable or disable Syslog function. Facility Code Select Syslog facility. Server IP The IP address of Syslog server. Server Port The UDP port used by the Syslog server. Send Test Send test message to Syslog server. [System->General->Time] Display the system date and time and…
-
[System->Security->Management] Set for login authentication and software authentication
Item Definition Login Authentication Local Account Use local account Administrator or Viewer settings to log in. RADIUS , Local Account Use RADIUS configuration settings to log in. If RADIUS authentication fails then Local Account settings will be used to log in. RADIUS Only Use RADIUS configuration…
-
[System->Security->Local Account] This page is used to configure the login account
Information Description Administrator Administrator has full access to read/write configuration settings. Viewer Viewer has restricted access to read only. Change Administrator account: 1. Enter User Name 2. Enter Current Password 3. Set the Manager IP (optional) 4. Enter New Password 5. Enter…
-
[System->Security->LDAP Configuration] After setting the proper LDAP server, the Remote
Management Card can use user name and password that set on the LDAP server to login. Item LDAP Server Definition LDAP Server The IP address/domain of LDAP server. LDAP SSL Enable to communicate with LDAP server by LDAPS. Port The TCP port used by the LDAP(S) server. User Base DN The Base DN of LDAP…
-
[System->Security->Session Control] Set for timeout setting for open sessions to automatically log
off. Item Timeout Definition The period (in minutes) that the system waits before automatically logging off. [System->Network Service->TCP/IPv4] Display the current TCP/IPv4 settings. Set DHCP and DNS server settings. Item Current Configuration Definition Displays the current TCP/IP settings: IP…
-
IP Address
Access Type Definition NMS access can be restricted by entering a specific IP address or an IP network subnet mask. The following subnet mask rules apply: • 192.168.20.255: Access only by an NMS on the 192.168.20 segment. • 192.255.255.255: Access only by an NMS on the 192 segment. • 0.0.0.0 (the…
-
[System->Network Service->Web Service] Select Enable to allow access to the HTTP or HTTPS
Service and configures the TCP/IP port for them. Item Definition Access Enable the access to HTTP or HTTPS service. The HTTPS supports encryption algorithm list as follow: Allow Access ‧ ‧ ‧ ‧ AES (256/128 bits) Camellia (256/128 bits) 3DES (168 bits) DES (168 bits) Http Settings Http Port The…
-
SSH Settings
SSH Port Definition The TCP/IP port (22 by default) that SSH uses to communicate. Hostkey Status ‧ Display the status of hostkey fingerprint to show whether it is valid or invalid. ‧ Upload Hostkey: Click to upload a Hostkey and replace the current one. ‧ Export Hostkey: Click to export a current…
-
Gmail
Definition Select Gmail as the service provider. Click Authorize for an authorization to send a mail notification. Then complete the sender name and click Apply to save the settings. SMTP server address The IP address or Host Name of the SMTP server used to send email notifications. Sender's E-mail…
-
[System->Notifications->SMS Service] Short Message Service (SMS) is a communication service
used by mobile communication systems. Using standardized communication protocols will allow the interchange of short text messages between mobile devices. The system provides 4 methods for users to choose how they want to send the messages. Item Description Select the Clickatell option in the SMS…
-
Service provider accepts
E-mail (SMTP) Definition This specification from a SMS provider is required before using the E-mail to deliver the messages via SMS providers. Select the Using E-mail option in the Service Provider field. Insert E_PHONE_NUMBER as recipient's mobile phone number and the E_PHONE_MESSAGE as event…
-
[System->About] Display system information for the Remote Management Card
Item Definition Model Name Model name of the Remote Management Card. Hardware Version The hardware version of the Remote Management Card. Firmware Version The current firmware version installed on the Remote Management Card. Firmware Updated Date The last date the firmware was updated. Serial Number…
-
Command Line Interface
How to log on Users can log on to the command line interface through either console network access (Telnet or SSH) or local access (Serial port). 1. Network access to the command line interface When user logs in with the admin username and admin password through Telnet or SSH, there are two types of…
-
2. Local access to the command line interface
To log on via serial connection, the PC/server must be connected directly to the Universal port of the RMCARD using the included RJ45/DB9 Serial Port Connection Cable, and perform the following steps. Step 1. Open Hyper Terminal software (eg. PuTTY, HyperTerminal, or Tera Term) on your PC and select…
-
Command Descriptions
ups Description: Show the information about UPS, input, output. And use master switch to control UPS. Option Argument Description info show Display UPS information input show Display UPS input information output show Display UPS output information Example 1: To view UPS information CyberPower > ups…
-
sleep
Argument Description This command is available in Utility Power 0 | 10 | 20 | 30 | 60 | 120 | 180 | 300 | 600 Failure Mode. It can make UPS in sleep mode until power restore. The argument means Sleep Delay in seconds. Example 1: To reboot UPS turn off delay 10sec and reboot duration 20sec.…
-
bypasscond
Argument nobypass | freqvolt | voltonly Description No Bypass-If this option is selected, the UPS will not enter Bypass mode and will stop supplying output power. Check Volt/Freq-If the utility voltage is in the range of the High/Low Bypass Voltage and the utility frequency is in the range of the…
-
workmode
Argument Description normal-Normal working mode of the UPS. eco10%-On-line UPS enters Economy 10% mode. eco15%-On-line UPS enters Economy 15% mode. generator-If the UPS uses generator as its input power, this option should enable the UPS to function normal | eco10% | eco15% normally. If this option…
-
upsbatt
Description: Show information of battery, and execute the battery test and battery runtime calibration. Option show Argument test Description Display all battery information for this UPS Execute the battery test immediately. cal start | stop Start or stop Runtime calibration. rdyyyy <number of year>…
-
atsoltcfg
Description: Show and configure information of ATS outlet. Option Argument Description show Show information of ATS Outlet Config index <1 | 2 |…| outlet number |all> Select ATS outlet index name <Outlet Name> Configuration ATS Outlet Name td_on <-1 | 0 | 1 | 2 |…|7200 > Configuration ATS Outlet On…
-
atsoltctrl
Description: Configure ATS outlet status. Option Argument Description index <1 | 2 |…|outlet number |all> Select ATS outlet index act <on | off | reboot | td_on | td_off | td_reboot> Control ATS Outlet Example 1: To turn on outlet #1 immediately CyberPower > atsoltctrl index 1 act on Example 2: To…
-
Argument
Description mm <number of month> Set month of system date. dd <number of date> Set day of month. time <00:00:00> Set system time. Example 1: To define timezone offset as +08:00 CyberPower > date timezone +0800 Example 2: To define the date as March 21, 2015 CyberPower > date yyyy 2015 mm 3 dd 21…
-
sys
Description: Show and configure identification of RMCARD, reset RMCARD. Option show Argument Description Display all system information for RMCARD name <system name> Set name of the equipment. location <system location> Set the location of power equipment. contact <system contact> Set the person to…
-
dst
Description: Show and configure type of Daylight Saving Time. Option show Argument Description Display all DST information for RMCARD disable-Disable DST. us-Tradition US DST manual-Manual DST date time rules. After finish this command, input start and end time step by step. mode disable | us |…
-
login
Description: Show and configure authentication for login. Option show Argument Description Display all login information for RMCARD local-User to login Remote Management Card with user name and password that configured in Local Account. radiuslocal-User to login Remote Management Card with user name…
-
admin / device
Description: Show and configure the primary/secondary manager IP, username, password of admin/device user. Option show Argument Description Display all admin or device information for this RMCARD access enable | disable Enable or disable Device primip <primary manager IP> Set primary manager IP of…
-
Server IP: 192.168.26.33
Server Secret: testsecret Server Port: 1826 Example 2: To view secondary radius server information CyberPower > radius sec show Server IP: 192.168.30.58 Server Secret: testsecret2 Server Port: 1508 Enter the following command to add Radius server information configuration with a single command…
-
Example 1
To add LDAP Server CyberPower > ldap add Input LDAP Server Type [openldap | ad]: ad Input IP address: 192.168.26.33 Use SSL [enable | disable]: disable Input LDAP port: 389 Input base DN: dc=cyber,dc=com Input login attribute: cn Input AD Domain: cyber.com Example 2: To view information about LDAP…
-
tcpip6
Description: Show and configure status of IPv6 router control, IPv6 manual IP. Option show access Argument Description Display all IPv6 information for RMCARD enable | disable Enable or disable IPv6 service. routerctrl enable | disable The IPv6 address is assigned through the method (Stateless…
-
Example 2
To change the community name of first SNMPv1 community to Public1 CyberPower > snmpv1 index 1 community Public1 Example 3: To change the IP address of third SNMPv1 community to 192.168.203.88 CyberPower > snmpv1 index 3 ip 192.168.203.88 Example 4: To change the community type of forth SNMPv1…
-
Example 2
To change the user name of second SNMPv3 user to CyberPower CyberPower > snmpv3 index 2 name CyberPower Example 3: To enable the third SNMPv3 user CyberPower > snmpv3 index 3 status enable Example 4: To change the IP address of forth SNMPv3 user to 192.168.203.66 CyberPower > snmpv3 index 4 ip…
-
trap
Description: Show and configure information of SNMP trap receiver. Option Argument Description show Display trap RMCARD. receiver information add Add trap receiver for RMCARD. index <1 | 2 | | 10> Select trap receiver index. name <Trap Receiver Name> Modify trap name of trap receiver. ip <Trap…
-
To change the community name of second trap receiver to CyberPower with the condition that the
SNMP version of trap receiver must be SNMPv1. CyberPower > trap index 2 community CyberPower Example 7: To change the SNMPv3 user of tenth trap receiver to SNMPv3 user2 with the condition that the SNMP version of trap receiver must be SNMPv3 CyberPower > trap index 10 user 2 Example 8: To delete the…
-
console
Description: Show and configure console network access type, telnet port and SSH port. Option show Argument access telnet | ssh | disable telnet <enable | disable> ssh <enable | disable reset_hostkey> Description Display all console information for RMCARD telnet-Enable the access to Telnet…
-
Example 1
To enable FTP service CyberPower > ftp access enable eventlog Description: View and clear the eventlog of RMCARD and UPS. Option Argument Description show Displays the list of events and a brief description of each event along with the date and time stamp. clear Clear the existing event logs.…
-
Argument
kernel | user | mail | system | auth1 | syslog | link | news | uucp | clock1 | auth2 | ftp | ntp | logaudit | logalert | clock2 | local0 | local1 | local2 | local3 | local4 | local5 | local6 | local7 facility s1test s2test s3test s4test Description Set Syslog facility. Send test message to Syslog…
-
Example 4
To view syslog information of server 4 CyberPower > syslog s4 show IP: 192.168.26.93 Port: 358 Enter the following command to perform all parameters configuration with a single command: syslog add <Server IP address> <Server Port> For example: CyberPower > syslog add 192.168.203.65 180 Note: This…
-
Reset to Factory Default Setting / Recover from a Lost Password
To reset the CyberPower Remote Management Card to its factory default setting (including web log-in user name and password), please following these steps: RMCARD205 RMCARD305 1. Remove the card from the UPS without turning the UPS/ATS PDU off. 2. Remove the jumper from the reset pins as illustrated.…
-
RMCARD Firmware Upgrade
By upgrading the firmware, you can obtain both the new features and updates/improvements to existing functionality. FTP service needs to be Enabled before attempting to execute a Firmware Upgrade. You can check the “Firmware version” on the [System->About] page on the web user interface of the…
-
Method 2: Using Upgrade and Configuration Utility (Bulk firmware upgrade tool)
1. Install the CyberPower Upgrade and Configuration Utility tool available for download at www.CyberPower.com. 2. After installation completes, run the “Upgrade and Configuration Utility”. 3. The main window of the Upgrade and Configuration Utility tool program is shown in Figure 6. The…
-
Figure 7. The File Locations of Firmware & Data window
7. Click “Yes” to start firmware upgrade on selected devices, as shown in Figure 8. Figure 8. Confirm Upgrade Firmware message window 8. If the firmware upgrade is implemented, you will see the Result in the main window, as shown in Figure 9. Figure 9. Firmware upgrade success in the main window. 64
-
Method 3: Using Secure Copy (SCP) command
Use the following steps to update firmware via SCP. Note: Only firmware version 1.1.2 and above supports the functionality to update firmware via SCP. For Windows Users: 1. Download any PuTTY Secure Copy client (PSCP) utility. 2. Save the firmware files and the PSCP Utility in the same folder. 3.…
-
For Linux, MacOS and Unix Users
1. Install the related distribution of an SSH or SCP client, for example Openssh client. 2. Open the Terminal and change the path to where the firmware files are saved. 3. Enter the following Command to perform firmware update: scp <filename> <user>@< IP address of RMCARD>: Note: (1) The SSH setting…
-
Save and Restore Configuration Settings
Method 1: Using Web Interface You can easily save and restore the device configuration to your local PC on [System->About] Figure 10. Save/Restore Configuration in the main window. You can easily save and restore the device configuration to your local PC on the [System->About], as shown in Figure…
-
For Windows Users
1. Download any PuTTY Secure Copy client (PSCP) utility. 2. Save the configuration file and the PSCP Utility in the same folder. 3. Open the Command Line Interface and change the path to where the configuration file and the PSCP Utility are saved. 4. Enter the following command to restore…
-
Note: YYYY_MM_DD_HHMM.txt is the configuration file to be restored
4. After executing the command, a message may appear asking if you trust the host. To continue type "y” for yes within 10 seconds. 5. On the next screen enter the RMCARD password. Please wait until the progress indicator displays 100%. The system will automatically log out and reboot after the…
-
Troubleshooting
Problem Unable to configure the Remote Management Card using method 1 or method 2 Solution 1. Check the LED status, it is normal when the yellow and green LEDs are both on. If green LED is off : ►Check if the Remote Management Card is properly seated in the device and the device has power. If yellow…
-
Conformance Approvals
FCC Warning This equipment has been tested and found to comply with the limits for a Class A Digital Device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and…
-
Appendix 1: IP Address Identification for CyberPower Remote
Management Card Overview All devices on a computer network need to have an IP address. Each device’s IP address is unique. The same address cannot be used twice. In order to assign an IP address to the CyberPower Remote Management Card, you must determine the range of the available IP addresses, and…
-
2. Select an IP Address for the CyberPower Remote Management Card
Verify the IP Addresses for the computer and the Remote Management Card belong to the same subnet. Refer to the above network information, the possible IP Address for the Remote Management Card could be 192.168.20.* (* hereafter represents any number between 1 and 255). Similarly, if the Subnet Mask…
-
Appendix 2: How to Configure a RMCARD User Account in
Authentication Servers RADIUS 1. Add a new attribute to RADIUS Dictionary as the Cyber vendor: 3808 – Vendor 2. Add two new specific attributes to RADIUS server interface under the vendor: (1)Cyber-Service-Type (integer variable) Cyber-Service-Type can accept three integer parameter values: 1…
-
Appendix 3: UPS Firmware Upgrade
You can check the “Firmware version” on the [UPS->Information] page on the web user interface of the RMCARD. Method 1: Using Web Interface 1. Turn off the UPS via the [UPS->Master Switch]. 2. Go to Firmware Version page via the [UPS->Information->Firmware Version]. 3. Upload the UPS firmware by…
-
(1) The file is Binary file for UPS firmware
(2) The UPS firmware file is supporting the UPS Model. Appendix 4: Software Support PowerPanel® Business Remote is used to perform a graceful operating system shutdown when protected by a UPS/ATS PDU with a remote management card installed. PowerPanel® Business software is available on CyberPower…
-
Obtain IP Address for Linux Operating System
The instructions in ‘Configure the IP address for the CyberPower Remote Management Card’ section are for Windows OS. For Linux Operating System, please use PowerPanel® Business Remote software to scan and obtain the IP address. To do this, go to [Power->Configuration] on the PowerPanel® Business…
-
Appendix 5: RMCARD Adapter Guide
Remove the Adapter to convert an RMCARD305 to an RMCARD205 Step 1. Remove the two screws from the adapter holding the card in place. Step 2. Remove the card from the adapter. Step 3. Remove the screw holding the RMCARD305 front panel to the card. Step 4. Attach the RMCARD205 front panel to the card.…
-
CyberPower Systems, Inc
www.cyberpowersystems.com For USA and Canada: 4241 12th Ave East, Suite 400 Shakopee, MN 55379 Toll-free: (877) 297-6937 For all other regions: Please visit our website for local contact information. K01-E000001-11