FAN COIL UNITS FOR R- 410A REFRIGERANT SIZES 018 TO 060 50 Hz Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . 1 INTRODUCTION . . . . . . . . . . . . . . .…
-
Locate unit rating plate which contains proper installation
information. Check rating plate to be sure unit matches job specifications. Step 2 — Mount Unit Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit. IMPORTANT: When unit is installed over a finished ceiling and/or living area, building…
-
2. Remove coil mounting screw securing coil assembly to
right side casing flange. 3. Remove coil assembly. 4. Lay fan coil unit on its right side and reinstall coil assembly with condensate pan down. (See Fig. 4.) 5. Attach coil to casing flange using coil mounting screw previously removed. 6. Make sure the pan cap in the fitting door is properly seated…
-
Ductwork Acoustical Treatment
Metal duct systems that do not have a 90_ elbow and 10- ft (3m) of main duct to first branch takeoff may require internal acoustical insulation lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard…
-
FAN COIL
(CONTROL) RED R G GRY G C BRN C W2 WHT W 2 VIO E E SECONDARY R C BRN RED BLU W W2 ODTS 208 3 L terminal on transformer and connect it to the 208v terminal. (See Fig. 13.) O O Y Y YEL 230 R HEAT PUMP (CONTROL) C THERMOSTAT BLK PRIMARY A94061 Fig. 10 - Wiring Layout Heat Pump Unit (Cooling and 2…
-
Speed-taps 1, 2, and 3 have a 90 second blower off time delay
pre-programmed into the motor. Speed-tap 4 is used for electric heat only (with 0 second blower time delay) and the WHITE wire should remain on tap 4. Speed-tap 5 is used for high static applications, but has a 0 second blower time delay pre-programmed into the motor. See Airflow Performance tables…
-
CAUTION ! CAUTION UNIT OR PROPERTY DAMAGE HAZARD PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product or property damage. Failure to follow this caution may result in product or property damage. The conversion of the fan coil to downflow requires special procedures for the…
-
B. Cooling Mode
Thermostat energizes R to G, R to Y, and R to O (heat pump only). G energizes fan relay on PCB which completes circuit to indoor blower motor. When G is de- energized, there is a 90- sec delay before fan relay opens. FAN COIL (CONTROL) THERMOSTAT R RED R G GRY G BRN C W2 Refer to outdoor unit…
-
AIRFLOW PERFORMANCE TABLES
Table 1 – FB4C Airflow Performance (CFM) MODEL & SIZE BLOWER SPEED Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2 Tap 1 Tap 5 Tap 4 Tap 3 Tap 2…
-
38CKM042-XQR01-- 38CKM048-XQR01-- 38CKM060-XQR01-- FB4CQL042L00EAAA FB4CQL048L00EAAA FB4CQL060L00EAAA Engineered in USA, assembled in Mexico Country of Origin: Mexico 38CKM036-XQR01-- FB4CQL037L00EAAA 38CKM060-X-901-- FB4CSL060L00EAAA 38CKM036-XQQ01-- 38CKM048-X-901-- FB4CSL048L00EAAA…
-
Fig. 20 - FB4CSL - English Measurements
-
Fig. 21 - FB4CSL - English Measurements
-
Fig. 22 - FB4CSL - Metric Measurements
-
Fig. 23 - FB4CSL - Metric Measurements
-
Fig. 24 - FB4CQL - English Measurements
-
Fig. 25 - FB4CQL - English Measurements
-
Fig. 26 - FB4CQL - Metric Measurements
-
Fig. 27 - FB4CQL - Metric Measurements
-
R- 410A QUICK REFERENCE GUIDE
S Observe all warnings, cautions, and bold text. S R- 410A refrigerant operates at 50- 70 percent higher pressures than R- 22. Be sure that servicing equipment and replacement components are designed to operate with R- 410A refrigerant. S R- 410A refrigerant cylinders are rose colored. S Recovery…