MIDDLE STATIC PRESSURE DUCT TYPE AIR CONDITIONER
Installation Manual Middle Static Pressure Duct Type Model: 42KSS012NS/38KUS012NS 42QSS012NS/38QUS012NS 42QSS048NT/38QUS048NT 42QSS060NT/38QUS060NT IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future…
-
Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or equipment failure. NAME Tubing & Fittings Drainpipe…
-
Safety Precautions
2 Read Safety Precautions Before Installation Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION. WARNING Failure to observe a warning may result in death. The appliance…
-
Unit Installation
Overview 3 Installation Overview INSTALLATION ORDER Install the indoor unit (Page 7) Install the outdoor unit (Page 18) 6 5 MC 4 L N MC Evacuate the refrigeration system (Page 30) 7 Perform a test run (Page 32) Page 6 Install the drainpipe (Page 21) Connect the wires (Page 26) Connect the…
-
Indoor Unit Parts
Air inlet Electric control cabinet Air filter(on some models) Air outlet Drain hose Refrigerant connecting pipe Fig. 4.1 Safety Precautions CAUTION WARNING • Securely install the indoor unit on a structure that can sustain its weight. If the structure is too weak, the unit may fall causing personal…
-
Step 2: Hang indoor unit
Indoor Unit Installation 1. Please refer to the following diagrams to locate the four positioning screw bolt holes on the ceiling. Be sure to mark the paces where you will drill ceiling hook holes. Air outlet dimensions(Applicable to 18-36K series only) Air inlet dimensions Air filter Descending…
-
Wood
Place the wood mounting across the roof beam, then install the hanging screw bolts.(See Fig.4.4) Roof beam Ceiling Hanging screw bolts Fig. 4.4 New concrete bricks Inlay or embed the screw bolts. (See Fig. 4.5) (Blade shape insertion) (Slide insertion) Fig. 4.5 Original concrete bricks Use embedding…
-
Horsepower code setting The capacity of the indoor unit has been set in the factory according to the below table. PO WER_S 78 9 A ENC1 Canvas tie-in Canvas tie-in Isolation booth Air outlet Air inlet Isolation booth checking orifice Air dust filter Fig. 4.10 5. Refer to the following static pressure…
-
Step 6: Fresh air duct installation
Dimension : Duct joint for fresh air Indoor Unit Installation Step 5: Adjust the air inlet direction (From rear side to under-side.) 1. Take off ventilation panel and flange, cut off the staples at side rail. Air return flange MODLE 12-24 Side rail 2. Stick the attached seal sponge as per the…
-
Fan performances
Static pressure curve(middle static pressure duct) Indoor Unit Installation 9K Code 0 External static pressure In. WG (Pa) External static pressure In. WG (Pa) 0.06 (15) Limit 0.02 (5) Middle High Rated Point Low 0 176 (300) 0.12 (30) 0.10 (25) 0.08 (20) 0.04 (10) Code 1 0.08 (20) 0.04 (10) 0.02 (5)…
-
12K
Code 1 Code 0 External static pressure In. WG (Pa) External static pressure In. WG (Pa) 0.06 (15) Limit High 0.04 (10) Rated Point 0.02 (5) Low 0 206 (350) 265 (450) 324 (550) 382 (650) Rated Point 0.04 (10) Middle 0.02 (5) 206 (350) Low 265 (450) 324 (550) 382 (650) Air volume CFM (m3/h) Code 2…
-
18K
Code 1 Code 0 0.12 (30) Limit 0.10 (25) High 0.08 (20) 0.06 (15) Rated Point 0.04 (10) 0.02 (5) 0 Low (300) (400) (500) (600) External static pressure In. WG (Pa) External static pressure In. WG (Pa) 0.14 (35) 0.16 (40) 0.12 (30) Rated Point 0.08 (20) 0.04 (10) (700) (800) (900) (1000) (1100) High…
-
24K
Code 1 Code 0 0.16 (40) 0.20 (50) High Limit External static pressure In. WG (Pa) External static pressure In. WG (Pa) 0.20 (50) 0.12 (30) Middle 0.08 (20) Rated Point 0.04 (10) 0 353 (600) Low 471 (800) 588 (1000) 706 (1200) 824 (1400) High Limit 0.16 (40) Middle Rated Point 0.12 (30) 0.08 (20)…
-
36K
Code 1 Code 0 0.28 (70) 0.24 (60) Limit High 0.20 (50) 0.16 (40) Middle 0.12 (30) Rated Point 0.08 (20) 0.04 (10) 0 Low External static pressure In. WG (Pa) External static pressure In. WG (Pa) 0.24 (60) 0.24 (60) Rated Point Middle 0.16 (40) 0.12 (30) 0.08 (20) Low 0.04 (10) 1059 1176 1294 (800)…
-
48K
Code 0 Code 1 High Limit 0.16 (40) Middle 0.12 (30) 0.08 (20) 0.04 (10) 0 Low 0.28 (70) External static pressure In. WG (Pa) External static pressure In. WG (Pa) 0.20 (50) Air volume CFM (m3/h) 0.16 (40) 0.12 (30) 0.08 (20) 0.04 (10) Low 1059 1176 1294 1412 1529 (1000) (1200) (1400) (1600) (1800)…
-
Outdoor Unit Installation Outdoor Unit Installation Instructions Outdoor Unit Installation Step 1: Select installation location. The outdoor unit should be installed in the location that meets the following requirements: √ Place the outdoor unit as close to the indoor unit as possible. √ Ensure…
-
Split Type Outdoor Unit
-
Outdoor Unit
Installation 60 cm / 23.6” above NOTE: The minimum distance between the outdoor unit and walls described in the installation guide does not apply to airtight rooms. Be sure to keep the unit unobstructed in at least two of the three directions (M, N, P) (See Fig. 5.10) 30 c m/1 1.8” ck ” 1.8 m 0c /1…
-
Drainpipe Installation The drainpipe is used to drain water away from the unit. Improper installation may cause unit and property damage. CAUTION NOTE ON PURCHASING PIPES Installation requires a polyethylene tube (exterior diameter = 3.7-3.9cm, interior diameter = 3.2cm), which can be obtained at…
-
the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 12mm (0.5”). This will ensure proper water drainage (See Fig. 6.5). Place the protective wall cuff in the hole. This protects the edges of the hole and…
-
Refrigerant Piping Connection Safety Precautions Notes On Pipe Length and Elevation WARNING • Table 7.1: The Maximum Length And Drop Height Based on Models. (Unit: m/ft.) Type of model Capacity (Btu/h) Length of piping Maximum drop height North America, Australia and the eu frequency conversion…
-
Table 7.2
CAUTION Permitted length Total piping length 18K+18K 30m/98’ 24K+24K 50m/164’ L+Max (L1, L2) 30K+30K Piping length Drop height (farthest distance from the line pipe branch) 15m/49’ L1, L2 (farthest distance from the line pipe branch) 10m/32.8’ L1-L2 Drop height between indoor and outdoor unit…
-
5. Clamp flare form on the end of the pipe
The end of the pipe must extend beyond the flare form. Flare form NOTE: Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit. Fig. 7.8 Pipe Fig. 7.5 6. Place flaring tool onto the form. 7. Turn the handle of the flaring tool clockwise until the pipe is fully…
-
Wiring Safety Precautions WARNING To prevent distortion when the compressor starts (you can find the unit’s power information on the rating sticker): Wiring • The unit must be connected to the main • Disconnect the power supply before outlet. Normally, the power supply must working on the unit. have…
-
Table 8.2: Other World Regions
Rated Current of Nominal Cross-Sectional Appliance (A) Area (mm²) ≤ 6 0.75 6 - 10 10 - 16 16 - 25 25- 32 32 - 45 1 1.5 2.5 4 6 b. Using wire strippers, strip the rubber jacket from both ends of the signal cable to reveal approximately 15cm (5.9”) of wire. c. Strip the insulation from the ends. d.…
-
Power Specifications
-
MODEL(Btu/h)
≤36K 37K~60K ≤36K 37K~60K PHASE FREQUENCY AND VOLT CIRCUIT BREAKER/FUSE(A) PHASE POWER (outdoor) FREQUENCY AND VOLT CIRCUIT BREAKER/FUSE(A) 1 Phase 1 Phase 1 Phase 1 Phase 208-240V 208-240V 208-240V 208-240V 15/10 3 Phase 15/10 3 Phase 15/10 3 Phase 15/10 3 Phase 380-420V 380-420V 208-240V 208-240V…
-
Air Evacuation 4. Turn on the vacuum pump to evacuate the system. 5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-1x105Pa). 6. Close the manifold gauge’s Low Pressure valve and turn off the vacuum pump. 7. Wait for 5 minutes, then check that there has been no…
-
Note On Adding Refrigerant
CAUTION • Refrigerant charging must be performed after wiring, vacuuming, and the leak testing. • DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system. Doing so can damage the unit or impact it’s functioning. • Charging with unsuitable substances may cause explosions…
-
Test Run
Before Test Run A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test: a) Indoor and outdoor units are properly installed. b) Piping and wiring are properly connected. c) No obstacles near the inlet and outlet of…
-
The design and specifications are subject to change without prior notice for product
improvement. Consult with the sales agency or manufacturer for details. QST2I-035AEN(B) 16123000000732 20160606 Page 33