CEILING & FLOOR TYPE AIR CONDITIONER
Installation Manual Ceiling & Floor Type Model: 42KZL012NS/38KUS012NS 42KZL018NS/38KUS018NS 42KZL024NS/38KUS024NS 42KZL030NS/38KUS030NS 42KZL036NT/38KUS036NT 42KZL048NT/38KUS048NT 42KZL060NT/38KUS060NT 42QZL012NS/38QUS012NS 42QZL018NS/38QUS018NS 42QZL024NS/38QUS024NS 42QZL030NS/38QUS030NS…
-
Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or equipment failure. Name Refrigeration Fittings Shape 1…
-
Safety Precautions
2 Read Safety Precautions Before Installation Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION. WARNING Failure to observe a warning may result in death. The appliance…
-
Unit Installation
Overview 3 Installation Overview INSTALLATION ORDER Install the indoor unit (Page 7) Install the outdoor unit (Page 12) 6 5 MC 4 L N MC Evacuate the refrigeration system (Page 24) 7 Perform a test run (Page 26) Page 6 Install the drainpipe (Page 15) Connect the wires (Page 20) Connect the…
-
Indoor Unit Parts
Installation part Louver grille Air outlet Display panel Air inlet Fig. 4.1 Safety Precautions WARNING • Securely install the indoor unit on a structure that can sustain its weight. If the structure is too weak, the unit may fall and cause personal injury, unit and property damage, or death. • DO…
-
Indoor Unit Installation Instructions
CAUTION Step 1: Select installation location DO NOT install the unit in the following locations: Areas with oil drilling or fracking The indoor unit should be installed in a location that meets the following requirements: Enough room for installation and maintenance. Enough room for the…
-
A
-
Step 2: Hang indoor unit
CAUTION Indoor Unit Installation Wood Place the wood mounting across the roof beam, then install the hanging screw bolts.(See Fig.4.4) Wood mounting Roof beam Ceiling Hanging screw bolts Fig. 4.4 New concrete bricks Inlay or embed the screw bolts. (Blade shape insertion) (Slide insertion) Fig. 4.5…
-
Hanging arm
Fig. 4.12 Grille Side board Fig. 4.10 10. Mount the indoor unit onto the hanging screw bolts with a block. Position the indoor unit on a flat level by using a level to prevent leaks. (See Fig. 4.11). D. Refrigerant pipe connection (D.gas side) E. Refrigerant pipe connection (E. Liquid side) Drain…
-
Outdoor Unit Installation Outdoor Unit Installation Instructions Outdoor Unit Installation Step 1: Select installation location. The outdoor unit should be installed in the location that meets the following requirements: √ Place the outdoor unit as close to the indoor unit as possible. √ Ensure…
-
Split Type Outdoor Unit
-
Outdoor Unit
Installation 60 cm / 23.6” above NOTE: The minimum distance between the outdoor unit and walls described in the installation guide does not apply to airtight rooms. Be sure to keep the unit unobstructed in at least two of the three directions (M, N, P) (See Fig. 5.10) 30 cm / 11.8 M ” on ck 30 cm m…
-
Drainpipe Installation The drainpipe is used to drain water away from the unit. Improper installation may cause unit and property damage. 1-1.5m (39-59”) CAUTION Downward slope 1/100 Insulate all piping to prevent condensation, which could lead to water damage. • If the drainpipe is bent or…
-
the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 12mm (0.5”). This will ensure proper water drainage (See Fig. 6.4). Place the protective wall cuff in the hole. This protects the edges of the hole and…
-
Refrigerant Piping Connection Safety Precautions Notes On Pipe Length and Elevation WARNING • Table 7.1: The Maximum Length And Drop Height Based on Models. (Unit: m/ft.) Type of model Capacity (Btu/h) Length of piping Maximum drop height North America, Australia and the eu frequency conversion…
-
Table 7.2
Permitted length(Unit:m/ft.) Total piping length 18K+18K 24K+24K 30K+30K Piping length Drop height 30/98 L+Max (L1, L2) 50/164 (farthest distance from the line pipe branch) 15/49 L1, L2 (farthest distance between L1 and L2) 10/32.8 L1-L2 Drop height between indoor and outdoor unit 20/65.6 H2 Drop…
-
6. Place flaring tool onto the form
7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions shown in table 7.3. Table 7.3: PIPING EXTENSION BEYOND FLARE FORM Pipe gauge Tightening torque Flare dimension (A) (Unit: mm/Inch) Min. Max. Ø 6.4 14.2-17.2 N.m (144-176…
-
Wiring Safety Precautions WARNING To prevent distortion when the compressor starts (you can find the unit’s power information on the rating sticker): Wiring • The unit must be connected to the main • Disconnect the power supply before outlet. Normally, the power supply must working on the unit. have…
-
Table 8.2: Other World Regions
Rated Current of Nominal Cross-Sectional Appliance (A) Area (mm²) ≤ 6 0.75 Indoor Unit Wiring 1. Prepare the cable for connection a. Using wire strippers, strip the rubber jacket from both ends of the signal cable to reveal 6 - 10 1 about 15cm (5.9”) of the wire. b. Strip the insulation from the…
-
Power Specifications
-
MODEL(Btu/h)
≤36K 37K~60K ≤36K 37K~60K PHASE FREQUENCY AND VOLT CIRCUIT BREAKER/FUSE(A) PHASE POWER (outdoor) FREQUENCY AND VOLT CIRCUIT BREAKER/FUSE(A) 1 Phase 1 Phase 1 Phase 1 Phase 208-240V 208-240V 208-240V 208-240V 15/10 3 Phase 15/10 3 Phase 15/10 3 Phase 15/10 3 Phase 380-420V 380-420V 208-240V 208-240V…
-
Air Evacuation 4. Turn on the vacuum pump to evacuate the system. 5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-1x105Pa). 6. Close the manifold gauge’s Low Pressure valve and turn off the vacuum pump. 7. Wait for 5 minutes, then check that there has been no…
-
Note On Adding Refrigerant
CAUTION • Refrigerant charging must be performed after wiring, vacuuming, and the leak testing. • DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system. Doing so can damage the unit or impact it’s functioning. • Charging with unsuitable substances may cause explosions…
-
Test Run
Before Test Run A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test: a) Indoor and outdoor units are properly installed. b) Piping and wiring are properly connected. c) No obstacles near the inlet and outlet of…
-
The design and specifications are subject to change without prior notice for product
improvement. Consult with the sales agency or manufacturer for details. QSDLI-043AEN(E) 16122500000308 20160830 Page 27