Инструкция на Настенные сплит-системы Carrier серии 42QHA-N
Настенные сплит-системы Carrier 42QHA007N / 38QHA007N, 42QHA009N / 38QHA009N, 42QHA012N / 38QHA012N, 42QHA018N / 38QHA018N. 42QHA024N / 38QHA024N. Инструкция по монтажу.
Загружаем документ…
Текст инструкции
-
SPLIT-TYPE ROOM AIR CONDITIONER
Installation Manual CS78421-548-754 IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.
-
Safety Precautions
Read Safety Precautions Before Installation Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION. This symbol indicates that ignoring instructions may cause death or…
-
WARNING
6. For all electrical work, follow all local and national wiring standards, regulations, and the Installation Manual. You must use an independent circuit and single outlet to supply power. Do not connect other appliances to the same outlet. Insufficient electrical capacity or defects in electrical…
-
Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. Name Shape Quantity Mounting…
-
Shape
Name Quantity SPLIT-TYPE ROOM AIR CONDITIONER Owner’s Manual Forest Series All Model Numbers 1 Owner’s manual CS78421-548-754 IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference. SPLIT-TYPE ROOM…
-
Installation
Overview Installation Summary - Indoor Unit 1 2 15cm (5.9in) 12cm (4.75in) 2 12cm (4.75in) 2.3m (90.55in) Select Installation Location (Page 11) 3 Determine Wall Hole Position (Page 12) 4 Attach Mounting Plate (Page 12) Page 8 Drill Wall Hole (Page 12)
-
7 1 Connect Piping (Page 25) Installation Overview Connect Wiring (Page 17) Prepare Drain Hose (Page 14) 8 Wrap Piping and Cable (Page 18) 9 STEP 8 Mount Indoor Unit (Page 18) Page 9
-
Unit Parts Installation Overview Wall Mounting Plate Front Panel Power Cable (Some Units) Louver Drainage Pipe Signal Cable Refrigerant Piping Remote Control Remote Holder (Some Units) Outdoor Unit Power Cable (Some Units) Fig. 3.1 NOTE ON ILLUSTRATIONS Illustrations in this manual are for…
-
Indoor Unit Installation
4 Indoor Unit Installation Fig. 3.1-a Installation Instructions – Indoor Unit PRIOR TO INSTALLATION Before installing the indoor unit, refer to the label on the product box to make sure that the model number of the indoor unit matches the model number of the outdoor unit. Step 1: Select installation…
-
Refer to the following diagram to ensure proper distance from walls and ceiling
15cm (5.9in) or more 12cm (4.75in) or more 12cm (4.75in) or more Indoor Unit Installation 2.3m (90.55in) or more Fig. 3.1-b Step 2: Attach mounting plate to wall The mounting plate is the device on which you will mount the indoor unit. 1. Remove the screw that attaches the mounting plate to the back…
-
Indoor
-
Step 4: Prepare refrigerant piping
The refrigerant piping is inside an insulating sleeve attached to the back of the unit. You must prepare the piping before passing it through the hole in the wall. Refer to the Refrigerant Piping Connection section of this manual for detailed instructions on pipe flaring and flare torque…
-
NOTE ON DRAIN HOSE
PLACEMENT PLUG THE UNUSED DRAIN HOLE To prevent unwanted leaks you must plug the unused drain hole with the rubber plug provided. CORRECT Make sure there are no kinks or dent in drain hose to ensure proper drainage. Fig. 3.5 NOT CORRECT Kinks in the drain hose will create water traps. Make sure to…
-
BEFORE PERFORMING ELECTRICAL WORK, READ THESE REGULATIONS
1. All wiring must comply with local and national electrical codes, and must be installed by a licensed electrician. 2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units. 3. If there is a serious safety issue…
-
Step 6: Connect signal cable
The signal cable enables communication between the indoor and outdoor units. You must first choose the right cable size before preparing it for connection. Cable Types • Indoor Power Cable (if applicable): Minimum Cross-Sectional Area of Power and Signal Cables North America Appliance Amps (A) AWG…
-
6. Feed the signal wire through this slot, from
the back of the unit to the front. 7. Facing the front of the unit, match the wire colors with the labels on the terminal block, connect the u-lug and and firmly screw each wire to its corresponding terminal. CAUTION Indoor Unit Installation DO NOT MIX UP LIVE AND NULL WIRES This is dangerous, and…
-
the wall, do the following: 1. Hook the top of the indoor unit on the upper hook of the mounting plate. 2. Use a bracket or wedge to prop up the unit, giving you enough room to connect the refrigerant piping, signal cable, and drain hose. Refer to Fig. 3.11 for an example. 3. Connect drain hose and…
-
Outdoor Unit Installation 60cm (24in) above Outdoor Unit Installation Installation Instructions – Outdoor Unit Step 1: Select installation location Before installing the outdoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate…
-
SPECIAL CONSIDERATIONS FOR EXTREME
WEATHER If the unit is exposed to heavy wind: Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds. See Fig. 4.2 and Fig. 4.3 below. Strong wind Strong wind Wind Baffle Base pan…
-
Step 3: Anchor outdoor unit
The outdoor unit can be anchored to the ground or to a wall-mounted bracket. W A UNIT MOUNTING DIMENSIONS B Air inlet D The following is a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the installation base of the unit according to the dimensions below.…
-
If you will install the unit on a wall-mounted
bracket , do the following: CAUTION Before installing a wall-mounted unit, make sure that the wall is made of solid brick, concrete, or of similarly strong material. The wall must be able to support at least four times the weight of the unit. 1. Mark the position of bracket holes based on TO REDUCE…
-
PAY ATTENTION TO LIVE WIRE
WARNING BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM. 1. Prepare the cable for connection: USE THE RIGHT CABLE • Indoor Power Cable (if applicable): H05VV-F or H05V2V2-F • Outdoor Power Cable: H07RN-F • Signal Cable: H07RN-F Minimum Cross-Sectional Area of…
-
Refrigerant Piping Connection The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal efficiency is tested on units with a pipe length of 5 meters (16.5ft). Refer to the table below for specifications on the maximum length and drop height of piping.…
-
DO NOT DEFORM PIPE
WHILE CUTTING Flare nut Be extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit. Step 2: Remove burrs Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed. 1. Hold the…
-
6. Place flaring tool onto the form
7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. 8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring. Step 4: Connect pipes When connecting refrigerant pipes, be careful not to use excessive torque or to deform the…
-
Instructions for Connecting Piping
to Outdoor Unit USE SPANNER TO GRIP MAIN BODY OF VALVE 1. Unscrew the cover from the packed valve on Torque from tightening the flare nut can snap off other parts of valve. the side of the outdoor unit. (See Fig. 5.9) Valve cover Fig. 5.9 2. Remove protective caps from ends of valves. 3. Align…
-
Air Evacuation MC MC Preparations and Precautions Evacuation Instructions Air and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which can damage the air conditioner, reduce its efficiency, and cause injury. Use a vacuum pump and manifold gauge to evacuate the…
-
Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed. Flare nut 4. Turn on the vacuum pump to evacuate the system. 5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-105 Pa). 6. Close the Low Pressure side of the manifold gauge, and turn off the vacuum pump. Cap 7. Wait for…
-
Electrical and Gas Leak Checks
Electrical Safety Checks After installation, confirm that all electrical wiring is installed in accordance with local and national regulations, and according to the Installation Manual. BEFORE TEST RUN DURING TEST RUN Check for Electrical Leakage During the Test Run, use an electroprobe and…
-
Test Run Before Test Run Only perform test run after you have completed the following steps: • Electrical Safety Checks – Confirm that the unit’s electrical system is safe and operating properly • Gas Leak Checks – Check all flare nut connections and confirm that the system is not leaking • Confirm…
-
DOUBLE-CHECK PIPE CONNECTIONS
During operation, the pressure of the refrigerant circuit will increase. This may reveal leaks that were not present during your initial leak check. Take time during the Test Run to double-check that all refrigerant pipe connection points do not have leaks. Refer to Gas Leak Check section for…
-
European Disposal Guidelines
10 This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment. Do not dispose of this product as household waste or unsorted municipal waste. When disposing of this appliance, you have the…
-
The design and specifications are subject to change without prior notice for
product improvement. Consult with the sales agency or manufacturer for details. CS372I-AF 16122000002734 20160620
-
此面无需印刷
: 1.80 / 2. :A4 3. : 4. : , 5.
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.