Operating Manual
OM 200MICRO Group: Chiller Part Number: 585515Y Effective: April 2000 Supersedes: OM125 200-Series MicroTech Control Panel For Centrifugal Chillers © 1999 McQuay International
-
Introduction
This manual provides installation, setup and troubleshooting information for the 200 Series MicroTech control panel for McQuay centrifugal chillers. Please refer to IOMM WSCWDC for information relating to the unit itself. All operational descriptions contained in this manual are based on MicroTech…
-
General Description
General Description The MicroTech control panel contains a model 280 microprocessor based controller which provides all monitoring and control functions required for the safe, efficient operation of the chiller. The operator can monitor all operating conditions by using the panel’s built in 4-line…
-
Features of the Control Panel
• Control of leaving chilled water within a ±0.2°F (±0.1°C) control band. • Readout of all temperature and pressure readings: − − − − − − − OM 200MICRO shutdown can be recalled to aid in isolating the cause of the problem. • Eight previous faults and related operating conditions are available from…
-
Component Description
Figure 2, Model 280 Microprocessor Control Board Microprocessor Control Board (MCB1) The Model 280 Microprocessor Control Board contains the electronic hardware and software required to monitor and control the unit. It receives input from the ADI Board and sends commands to the Output Board to…
-
With the controller powered up and the green running LED illuminated, the backlite panel on the
display module will be illuminated and the unit status menu will be visible. If the display text looks faded or appears as “blocks” the contrast control needs to be adjusted. Watch the display and adjusting the contrast control with a small flat-blade screwdriver until the best setting is…
-
Table 1, Digital Outputs
No. Description LED Off LED On 0 Alarm LED and Contact Programmable Programmable 1 Unload Solenoid and Front Panel LED - Unload 2 Load Solenoid and Front Panel LED - Load 3 Motor Control Relay Off On 4 Motor Control Relay Latch Unlatched Latched 5 Oil Pump Off On 6 Oil Sump Heater Off On 7 Oil…
-
of 4-20 mA. Temperature and pressure readings have a resolution of 0.1°F and 0.1 psi respectively
Flow readings and remote reset signals are resolved to ±1%. OM 200MICRO 9
-
Table 2, Controller Input Signals
ADI Sensor No. Description Range 0 S00 Leaving Evaporator Water Temperature -40 - 263 F (-40-128.4°C) 1 S01 Entering Evaporator Water Temperature -40 - 263 F (-40-128.4°C) 2 S02 Compressor Suction Temperature -40 - 263 F (-40-128.4°C) 3 S03 External Chilled Water Reset (by others) 4-20mA = 0-100% 4…
-
Analog Output Board (AOX)
The AOX board converts control instructions from the Microprocessor Control Board’s expansion bus into an analog control signal suitable for driving a cooling tower bypass valve. Each AOX board is factory set via jumper to provide an output signal range of 0 - 10 VDC. An additional output on the AOX…
-
Signal Converter Board
The AC current signal generated by the starter is converted by the signal converter board into a 0-5 VDC signal that is directly proportional to the chiller amp draw. The amp draw signal is sent to the ADI board for conditioning and then to the M280 controller. Figure 8, Signal Converter Board TB1…
-
Keypad/Display Operation
The Keypad/Display is the primary operator interface to the unit. All operating conditions, system alarms and setpoints can be monitored from this display and all adjustable setpoints can be modified from this keyboard if the operator has entered a valid operator password. General Description The…
-
Category Group
The keys in this group provide quick access to strategic menus throughout the menu tree-structure. This reduces the need to step through all the menus, one by one, in order to reach the desired information. Figure 12, Category Group Status Key Menus and menu items in this category provide…
-
Menu - Item Group
Figure 13, Menu - Item Group Prev. Item Next Menu Prev. Menu Next Item The keys in this group are used to scroll through the various menus and items presented on the controller’s display. A menu contains a specific group of items. Note: When Menu #1 is currently in the display (the first menu in the…
-
Increment
(+) When changing the value of a menu item entry, pressing ''INCR. +" shifts the selected menu item to the next higher value or next available selection. Decrement (-) When changing the value of a menu item entry, pressing "DECR.-" shifts the selected menu item to the next lower value or previous…
-
English Customary Units
Temperature = ºF Pressure = Psi Psig Psid Metric Units: Temperature = Pressure = ºC kPa kPag kPda (Fahrenheit) (Pound per sq. inch) (Centigrade) (Kilo Pascals) Menu Structure Displaying Setpoints To view set points or operating conditions press the "PREV MENU" or "NEXT MENU" key until menu of…
-
MicroTech Status Menus
Press the "STATUS" key under the Category Group and the information in Menu 1 (Unit Status) will be displayed. Information displayed in menus 1-10 indicates current operating conditions and cannot be reset from the display keypad. Refer to the Metric Menu section for displays in metric values. This…
-
temperature and line 2, field 2 indicates the leaving condenser water temperature. Line 3, field 1
indicates the evaporator delta temperature. This is the difference between the entering and leaving water temperature and indicates the 'load' on the chiller and the performance of the chiller. Line 3, field 2 indicates the condenser delta temperature. The design delta temperature of the evaporator…
-
approach temperature. This temperature is calculated by subtracting the evaporator refrigerant
temperature from the evaporator leaving water temperature. Press the "NEXT ITEM" key and screen 3 will display additional information. Line 1, field 1 indicates the compressor lift pressure. This value is calculated by subtracting the evaporator pressure from the condenser pressure. This indicates…
-
Press the "NEXT MENU" key and Menu 6 (Pump Status) will be displayed. Menu six has one screen
Line 1, field 1 displays the evaporator pump running status. Line 1, field 2 displays the condenser pump running status. Line 2, field 1 indicates which evaporator pump is operating as the lead pump. Line 2, field 2 indicates which condenser pump is operating as the lead pump. Pressing the switch…
-
Menu 8, Operating Hours
Item Screen Line 1 1 Display Comp Hours=xxxxx Starts=xxxx 2 Last Start=xx:xx mm/dd/yy 3 Last Stop=xx:xx mm/dd/yy Evap Pmp #1=xxxx Cond Pmp #1=xxxx Evap Pmp #2=xxxx Cond Pmp #2=xxxx Field Range Extended Name Compressor Operating Hours Compressor Starts Time of Last Chiller Start Date of Last Chiller…
-
Menu 10, Auto Logging
Item Screen 1 Line OM 200MICRO Display Wk Ending Peak=xxx% Evap=xx.xxpsi mm-dd xx:xx Cond=xxx.xpsi Field Range Extended Name Date of Current Log Recorded Peak % RLA Recorded Evaporator Pressure Date and Time of Log Entry Recorded Condenser Pressure Ent Evap=xx.x°F Ent Cond=xx.x°F Lvg Evap=xx.x°F Lvg…
-
Control Menu Description
Press the "CONTROL" key under the 'Category Group' and Menu 11 (Control Mode) will be displayed. Menus 11-26 are the control menus. All control set points and value selections are entered into the MicroTech from these menus. The default set point is indicated under the display column and the range…
-
Menu 12, Leaving Evap Set Points
Item Screen Line Display Field Spt Source=Local 1 Active Spt=xx.x°F Local Spt=44.0°F Startup DT=3.0°F Network Spt=xx.x°F Shutdn DT=3.0°F Range Local Network 40-80 1-10 1-3 Chw Reset=No Reset 1 Max Lvg Spt=54.0°F Return Spt=54.0°F No Reset at 70°F Reset Signal=xx.xmA Max Reset At=50°F No Reset Return…
-
4-20mA—This is an optional input to the MicroTech. This input is usually from a building
automation system. As the input changes from 4 to 20 mA, the leaving chilled water temperature is increased from local spt (in a linear manner) until the max lvg spt is reached. When the spt source is set to network, the 4-20 mA input is supplied to the master MicroTech control. The master will…
-
Demand Limit—Allows the MicroTech to control chiller motor amperage based on a remote 4-20
mA signal supplied by a building automation system input. The 4-20 mA signal limits the capacity of the chiller and saves electrical demand charges. Active Spt= This is a status value and cannot be changed. Active spt indicates the set point that is controlling the chiller. If current limiting is…
-
Menu 15, Schedule
Item Screen Line Display Override=00.0Hr Network Sched= Sun 00:00-23:59 Tue 00:00-23:59 Mon 00:00-23:59 Wed 00:00-23:59 Field Range 00.00-63.75 1-32 00:00-23:59 00:00-23:59 00:00-23:59 00:00-23:59 Extended Name Manual Schedule Override Network Time Schedule Sunday Run Schedule Tuesday Run Schedule…
-
Table 16 Continued
Item Screen Line Display #7=N/A-00 00 Day(s) 1 #10=N/A-00 00 Day(s) #8=N/A-00 00 Day(s) 2 2 #11=N/A-00 00 Day(s) #9=N/A-00 00 Day(s) 3 #12=N/A-00 00 Day(s) 1 #13=N/A-00 00 Day(s) 2 #14=N/A-00 00 Day(s) 3 Field Range Jan-Dec 00-31 00-31 Jan-Dec 00-31 00-31 Jan-Dec 00-31 00-31 Jan-Dec 00-31 00-31…
-
Menu 18, Pump Set Points
Item Screen Line Display Field 1 Evap=Pmp 1 Only 1 2 Cond=Pmp 1 Only 1 1 Range Pmp 1 Only Pmp 2 Only Auto Lead #1 Primary #2 Primary Pmp 1 Only Pmp 2 Only Auto Lead #1 Primary #2 Primary Extended Name Evap Pump Selection Mode Cond Pump Selection Mode Evap= This value determines how the pumps will be…
-
stage down time. The number of stages also will be decreased when the maximum number of stages is
less than the current stage. The sequence described above allows stages to be turned on based on temperature only or on a combination of temperature and time. Control may be based only on temperature by setting the stage 1 set point lowest and the other stages set points successively higher. This…
-
The number of cooling tower stages is decreased only when the valve position drops below the
minimum position set point and the temperature and time requirements described above for fan staging down are met. The valve then modulates open as the temperature starts to rise after the fan stage is turned off. When the chiller is commanded to start, and either type of valve control is selected…
-
Min Start Pos= This value will control the minimum position of the valve during pre-start at a preselected (Min Pos At=) outside air temperature. Max Start Pos= This value will control the maximum position of the valve during pre-start at a pre-selected (Max Pos At=) outside air temperature. Min Pos…
-
Menu 23, Lead Lag Setup
Item Screen Line 1 2 Display Slave Address=01.00 Field 1 Start-Up=NotUnld 2 LL Mode=auto 1 Enable Lag=95% 2 LL SwOver=N/A 1 Disable Lag=40% 2 Range 00-09 NoUnload Unload Auto Slave Lead Master Lead 0-100% N/A Sun Mon Tue Wed Thu Fri Sat 1-100% Delay timer=5Min Lag-Standby=No 1 1 1-60Min No-Yes…
-
Menu 24, Service
Item Screen Line Display Manual Load=Off Hot Gas Bypass=30% Setpoint=40% Post Lube=15 Extended Name Enable Manual Loading Hot Gas Bypass Enable Setpoint Manual Load Setpoint Oil Pump Delay Off Time 2 Range Off-on 20-70% 0-100% 10Sec-5Min Normal Fast 10Sec-5Min Evap Offset=0.0psi Sun-Sat 00:00-23:59…
-
Basic Chiller Setup
Press the "NEXT MENU" key and menu 26 (Unit Setup) will be displayed. Menu 26 has three screens. This menu is password protected and requires the operator password. Changing the values in this menu can cause network communications failure. There are several menus that require resetting the default…
-
Port A Baud= This value defines the communication baud rate for port A. This is critical if there is a network. (Port A baud rate must be set to 9600 on the master unit.) Low Temperature= This value selects the operational mode of the unit. If 'ice' is selected, the MicroTech default values have to…
-
Alarm Menus Description
Press the "ALARM" key under the 'Category Group' and menu 27 (Alarms) will be displayed. Menus 27-35 are the alarm menus. Menu 27 has four screens. This menu is a display and does not require a password. The values displayed indicate the current alarm and the conditions at the time the alarm…
-
3 Evap Flow=xxxxgpm Cond Flow=xxxxgpm 1 1 Evaporator Water Flow at Alarm Condenser Water Flow at Alarm Follow the above sequence to view the alarm menu 29-35 (Alarm Buffers #2-#8). Press the "NEXT MENU" key and menu 36 (Alarm Output) will be displayed. Menu 36 has one screen. This menu is password…
-
Menu 37, Message Board
Item 40 Screen Line Display 1 1 No Message Field Range Extended Name A Message can be Posted via a Connected Computer OM 200MICRO
-
Master/Slave Setup
Chiller setup for dual unit (WDC) or two single (WSC) units with master/slave and or lead/lag control. There are several menus that require modification to accomplish this setup. The first menu that has to be modified is menu 26. One MicroTech controller has to be designated as the Master unit. The…
-
Menu 23, Lead Lag Setup
Item Screen Line 1 2 Display Slave Address=01.00 Field 1 Start-Up=NotUnld 2 LL Mode=auto 1 Enable Lag=95% 2 LL SwOver=N/A 1 Disable Lag=40% 2 Range 00-09 NoUnload Unload Auto Slave Lead Master Lead 0-100% N/A Sun Mon Tue Wed Thu Fri Sat 1-100% Delay timer=5Min Lag-Standby=No 1 1 1-60Min No-Yes…
-
Alarms
Any condition that requires corrective action by the controller that overrides normal chiller operation or any condition that initiates an emergency chiller shutdown can be considered to be an alarm. Alarms are arranged in increasing priority with higher priority alarms replacing any lower priority…
-
Problems, continued
44 PROBLEM CONDITION DISPLAY ACTION CLEAR Evaporator Refrigerant Temperature > Evaporator Freeze Protect Set Point + Differential (2°F) Evaporator Freeze Protect Evaporator Refrigerant Temperature < Evaporator Freeze Protect Set Point (34°F) Evap Pres Lo-Freeze Start the Evaporator pump Evaporator…
-
Faults
The chiller will be shut down by the MicroTech control panel in response to any of the following fault conditions. These faults must be cleared manually to restart the unit. FAULT CONDITION DISPLAY Low Evaporator Pressure Evaporator Pressure is less than low limit (26 psig) Lo Evap Pressure-SD Low…
-