User manual LEGGI E CONSERVA QUESTE ISTRUZIONI READ AND SAVE THESE INSTRUCTIONS
-
IMPORTANT WARNINGS
CAREL bases the development of its products on decades of experience in HVAC, on the continuous investments in technological innovations to products, procedures and strict quality processes with in-circuit and functional testing on 100% of its products, and on the most innovative production…
-
1. Selecting the valve
The electronic expansion valve must be sized based on the cooling capacity of the evaporator it serves. For the correct selection of the valve, see the "E2V– E4V valve selection" manual +030220815, downloadable from www.carel.com. Alternatively, guided selection software is available on…
-
2.2 In-line filter
Always install a mechanical filter before the refrigerant inlet, with both welded valves (E2V***S***) and valves with threaded fittings (E2V***RB**). For the latter, a filter is supplied inside the packaging that can be placed directly in the valve inlet pipe. If the installation is bi-directional…
-
Observe the following warnings
• do not let water or other foreign bodies/fluids inside the valve: this would make it impossible to completely clean the parts inside; • preferably use the side fitting on the valve for the refrigerant inlet; • do not install the valve with the stator facing downwards; • install a mechanical filter…
-
3.2 Positioning with external pressure probe
If there is the need to simplify the inspection and replacement of the pressure probe, or to share the reading of the probe between master and slave utilities (for multiplexed showcases with controllers that support this function), the pressure probe can be installed outside of the showcase and away…
-
4. Installing the probes
NTC**HP** 4.1 Suction temperature probe The temperature probe must be selected based on the application. Showcases/cold rooms: NTC***HF** (with clamp) or NTC***HP**. Air-conditioners/chillers: NTC***WF** preferably in a socket, or NTC***HF** or NTC***HP**. NTC**HF** Fig. 4.b Fig. 4.a Fig. 4.c The…
-
In air-conditioners/above-zero chillers, where better measurement precision and a faster response is required, the NTC***WF** probe should be used, with installation in a socket. Good thermal coupling must be guaranteed between the socket and the probe, applying abundant conductive paste inside the…
-
Both types of transducers use the SPKC****** 3-wire cable with Packard co-moulded connector. The ratiometric transducer uses all and three wires, the 4-20 mA transducer only uses two (the green wire is not used). Each pressure transducer is supplied with a different range of measurement. The…
-
5.2 Probe and power supply connections
Then complete the wiring of the driver, following the information provided on the instruction sheet supplied in the packaging. Connect the 24 V power supply, the optional battery module, the optional communication LAN (pLAN, tLAN or RS485), the alarm relay, if used, the digital input for enabling…
-
еее 1
-
6. Electronic valve control devices
There are different types of driver and different controllers with built-in drivers. 6.1 Drivers The drivers (EVD family) mainly differ as regards: • type of pressure transducer (ratiometric or 4-20 mA) • user interface for programming the parameters • local network connection (tLAN, pLAN, RS485…
-
6.2 Controllers with built-in driver
Some specific CAREL controllers for showcases and cold rooms include the hardware and software for the management of electronic valves; these are programmed in different ways. Model MasterCase MasterCase 2 MPXPRO Code MGE000*020 MC200N0B10 MX20**3* or MX20**5* Software user interface PC with…
-
8. Control devices: advanced parameter settings
The control of the electronic valve can be divided into two categories: superheat control with reference to the corresponding set point, and control of unit safety with protectors that are activated only if the pressure or temperature reach dangerous values that can be set by the user. 8.1 Superheat…
-
8.2 Protection function control parameters
The software that manages the valve includes four protection functions: • LowSH protection (low superheat) • LOP protection (low evaporation temperature) • MOP protection (high evaporation temperature) • HITCond protection (high condensing temperature, optional) The LowSH protection acts quickly to…
-
SHOWCASES - COLD ROOMS
Multiplexed With compressor on board Perturbed system Shset Superheat set point °C K prop PID: proportional gain - Ti PID: integration time s Td PID: derivative time s LowSH LowSH prot.: threshold °C LowSH Ti LowSH prot.: integration time s PID PROTECTORS LOP LOP prot.: threshold °C 0 -45 °C (LT)…
-
AIR-CONDITIONERS - CHILLERS
Plate evaporator Tube bundle evaporator Finned coil evaporator SHset Superheat set point °C K prop PID: proportional gain - Ti PID: integration time sec Td PID: derivative time sec LowSH LowSH prot.: threshold °C LowSH Ti LowSH prot.: integration time sec 2.5 2.5 10 LOP prot.: threshold °C -5 -5 -5…
-
9. Start-up
When starting control for the first time, make sure that: 1) 2) 3) the electronic valve opens and starts controlling when the start control signal is sent (from digital input, pLAN, tLAN or built-in controller); the valve position constantly follows the superheat value, opening or closing when the…
-
As concerns the control parameters, the following general indications can be used as a guide
Proportional gain (from 3 to 30) Increasing the proportional gain K increases the reaction speed of the valve and is recommended if the system is particularly perturbed or to make superheat control faster. If high (>20), may cause swings and instability. Integration time (from 40 to 400 sec)…
-
10. Troubleshooting
The following table lists a series of situations of malfunctions that may occur when starting and operating the driver and the electronic valve. These cover the more common problems and provide an initial response to help resolve the fault. PROBLEM CAUSE SOLUTION Check that the pressure and the…
-
PROBLEM
CAUSE SOLUTION The condensing pressure swings Check the controller condenser settings, giving the parameters “blander” values (e.g. increase the proportional band or increase the integration time). Note: the required stability involves a variation within +/- 0.5 bar. If this is not effective or the…
-
PROBLEM
CAUSE SOLUTION The unit switches off due to low pressure during control (only for units with compressor on board) LOP protection disabled Set a LOP integration time greater than 0 sec. LOP protection ineffective Make sure that the LOP protection threshold is at the required saturated evaporation…
-
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 049.9716611 Fax (+39) 049.9716600 http://www.carel.com - e-mail: carel@carel.com Cod.: +030220811 Rel. 1.0 – 26/04/07 Agency