pCO compact
controle eletrônico electronic controller Folha de instruções Technical leaflet LEIA E CONSERVE ESTAS INSTRUÇÕES READ AND SAVE THESE INSTRUCTIONS Integrated Control Solutions & Energy Savings
-
Symbol
Warning: the symbol in the plastic cover of the control, means to refertto this techinical leaflet, during the electrical installation. Symbol: Warning: the symbol in the plastic cover of the control, means to refertto this techinical leaflet, during the electrical installation.
-
1. INTRODUÇÃO
A nova série pCO compact nasce da exigência de ter um controle capaz de gestir um fluxo elevado de informações. A esta habilidade somam-se as numerosas vantagens de um controle programável. O modelo pCO compact é compatível tanto a nível hardware quanto software com a família pCO e foi desenvolvido…
-
1.2 Instalação
Fixação mecânica O pCO compact deve ser instalado sobre guia DIN. Para a fixação na guia DIN, basta uma ligeira pressão do dispositivo apoiado previamente na correspondência da própria guia. O encaixe das lingüetas traseiras estabelece o seu bloqueio na guia. A desmontagem ocorre também…
-
1.5 Conectores
Características elétricas dos conectores extraíveis utilizados Passo: 5,08 mm; Tensão nominal: 250 V; Corrente nominal: 12 A; Seção do cabo: 0,25 mm2 - 2, 5 mm2 (AWG: 24 a 12); Comprimento de descascação: 7 mm; Dimensão da rosca do parafuso: M3; Torque de aperto: 0,5-0,6 Nm Passo: 3,81 mm; Tensão…
-
2. CARACTERÍSTICAS TÉCNICAS
2.1 Características mecânicas dimensões montagem todas as versões estão disponíveis em mecânica 6 Módulos DIN 105x115x60 mm sobre guia DIN 2.2 Recipiente plástico • De enganchar sobre guia DIN conforme normas DIN 43880 e CEI EN 50022 • Material: tecnopolímero • Ignífugo: V2 (segundo UL94) e 960°C…
-
2.4 Características das SERIAIS
Item Tipologia Referência Características fundamentais Serial ZERO PLAN J4, J5 Serial UM Serial DOIS • Incorporada em placa base • Não optoisolada • Driver HW: RS485 • Conectores: Jack telefônico + Extraíveis 3 vias p. 3,81 Conector Tipo de cabo blindado J4 J4 J4 J5 Telefônico AWG24 AWG20/22…
-
2.6 Ligação rede tLAN
-
2.8 Entradas Digitais
Comprimento máximo do cabo Tipo Alimentação Modelos Entrada analógicas multifuncionais (ver nota) Entrada digital rápida Entrada digital normal 10 m Não optoisolados com contato limpo Interna TYPE A B5, B6, B7, B8 ID1 ID2 B5, B6 ID1 ID2 Total 6 4 TYPE B Tab. 2.h Nota: Entradas analógicas…
-
2.10 Saídas Digitais
O modelo pCO compact TYPE A prevê 7 saídas digitais e pCO compact TYPE B prevê 6 saídas digitais com relés eletromecânicos ou no estado sólido (SSR). Para facilitar a cablagem os bornes comuns de algumas saídas foram divididos em grupos de acordo com a distância de isolamento. No interior de um…
-
2.12 Tabelas resumidas
-
2.13 Tabela acessórios
-
4. DESCRIÇÃO DE BORNES
-
4.1 Ligações elétricas
-
Alimentação em contínua
-
Regras para a eliminação
• Não eliminar o produto como lixo sólido urbano. Deve ser eliminado nos órgãos de coleta específicos. • O produto contém uma bateria e, portanto, é necessário removê-la separando-a do resto do produto seguindo as instruções contidas a seguir antes de efetuar a sua eliminação. • Um uso inadequado ou…
-
1. INTRODUCTION
The new pCO compact series is the result of the need for a controller than can manage considerable information flows. This feature adds to the numerous advantages of a programmable controller. pCO compact is compatible with the pCO family at both a hardware and software level, the controller has…
-
1.2 Installation
Mechanical fastening The pCO compact is installed on a DIN rail. To fasten the unit to the DIN rail, press it lightly against the rail. The rear tabs will click into place, locking the unit to the rail. Removing the unit is just as simple, using a screwdriver through the release slot to lever and…
-
1.5 Connectors
Electrical specifications of the plug-in connectors used Step: 5.08 mm; Rated voltage: 250 V; Rated current: 12 A; Cable size: 0.25 mm2 - 2.5 mm2 (AWG: 24 to 12); Stripping length: 7 mm; Screw thread size: M3; Tightening torque: 0.5- 0.6 Nm Step: 3.81 mm; Rated voltage: 160 V; Rated current: 8 A…
-
2. TECHNICAL SPECIFICATIONS
2.1 Mechanical specifications dimensions assembly available in 6 DIN module format 105x115x60 mm DIN rail 2.2 Plastic case • Fitted on DIN rail as per DIN 43880 and IEC EN 50022 • Material: technopolymer • Flame retardance: V2 (UL94) and 960 °C (IEC 695) • Ball pressure test 125 °C • Resistance to…
-
2.4 SERIAL specifications
Item Type Reference Main specifications Serial ZERO PLAN J4, J5 Serial ONE Serial TWO • Integrated on main board • Not opto-isolated • HW driver: RS485 • Connectors: Telephone jack + 3-pin plug-in p. 3.81 Connector Shielded cable type J4 J4 J4 J5 Telephone AWG24 AWG20/22 AWG20/22 CABLE LENGHT Lmax…
-
2.6 tLAN network connection
Type Transmission speed Maximum number of units connectable Connector for tLAN network Asynchronous half duplex 0/5 Vdc, non-differential 9.6 Kbps or 19.2 Kbps selected via software Maximum 5 units allowed 2-pin plug-in connector, pitch 3.81 mm (J7) Tab. 2.d Note: • The tLAN serial (J7) can be used…
-
2.8 Digital inputs
Maximum lenght cable Type Power supply Models Multifunction analogue inputs (see note) Fast digital input Normal digital input 10 m Not optically isolated, voltage free contact Internal TYPE A B5, B6, B7, B8 ID1 ID2 B5, B6 ID1 ID2 Total 6 4 TYPE B Tab. 2.g Note: Multifunction analogue inputs: these…
-
2.10 Digital outputs
pCO compact TYPE A has 7 digital outputs, while pCO compact TYPE B has 6 digital outputs with electromechanical relays or Solid state relay (SSR). To simplify assembly, the common terminals of some relays have been grouped together based on the insulation distance. Within a group, the outputs have…
-
2.12 Summary tables
Hardware configurations available Models PWM output Y1 TYPE A TYPE B Y1 0...10 V output Y2 Analogue inputs B1, B2 B3, B4 B5, B6 B7, B8 Max 8 B1, B2 B3, B4 Y2, Y3, Y4 B5, B6 Max 6 Digital inputs ID1 (veloce) ID2 Max 6 ID1 (veloce) ID2 Max 4 Group 1 output Group 2 output Group 3 output Group 4 output…
-
2.13 Table of accessories
code description PCOXCON0A0 PCOXCON0B0 PCOS00AKY0 0907877AXX PSTCON01B0 PSTCON03B0 PSTCON05B0 S90CONN002 S90CONN000 S90CONN001 plug-in screw connector kit for pCO compact MEDIUM type A plug-in screw connector kit for pCO compact LARGE type B pCO sistema smart key external ferrite for pCO compact…
-
4. DESCRIPTION OF THE TERMINALS
-
4.1 Electrical connections
-
DC power supply
-
Guidelines for disposal