Service Manual
Split-Type Air Conditioner J-SMART On/Off 1
-
This manual is for professional
maintenance personnel only 2
-
Part I : Technical Information
1. Summary 1-1 Appearance Indoor Unit JO Outdoor Unit Note: The outdoor grille can be replaced. 4
-
1-2 Model List
-
2. Outline Dimension Diagram
The following data is for reference only and the actual size may vary.) 2-1 Indoor Unit(Unit: mm) 09 12K 18K 6
-
24K
-
3. Specification sheet
Product Model Rated Capacity Rated Power Consumption Rated Running Current Nameplate Parameter ASW-H09B5A4/JAR1-B7 Cooling Heating Dehumidifying Cooling Heating Cooling Heating Electric heating power Max. Input Power Max. Input Current EER Cooling COP Heating Power supply source Refrigerant…
-
Rated Power Consumption
Rated Running Current Nameplate Parameter Indoor unit configuration ASW-H12C1A4/JAR1-C0 Cooling Heating Dehumidifying Cooling Heating Cooling Heating Electric heating power Max. Input Power Max. Input Current EER Cooling COP Heating Power supply source Refrigerant Refrigerant Charged Max. Discharge…
-
Rated Power Consumption
Rated Running Current Nameplate Parameter Indoor unit configuration ASW-H18D8A4/JAR1-B8 Cooling Heating Dehumidifying Cooling Heating Cooling Heating Electric heating power Max. Input Power Max. Input Current EER Cooling COP Heating Power supply source Refrigerant Refrigerant Charged Max. Discharge…
-
Rated Power Consumption
Rated Running Current Nameplate Parameter Indoor unit configuration ASW-H24F0D4/JAR1-B9 Cooling Heating Dehumidifying Cooling Heating Cooling Heating Electric heating power Max. Input Power Max. Input Current EER Cooling COP Heating Power supply source Refrigerant Refrigerant Charged Max. Discharge…
-
Container Loading 20/40/40HC
Set 157 4. Function and Control 4-1 T-Style 1) Remote Controller Introductions ● Carefully read this “instructions” for safe and correct use of the air-conditioner. ● carefully keep the “instructions” manual as it can be referred to at any time. Buttons description 13
-
1. ON/OFF Button
* Press this button to turn on/off the unit. * This will clear the existing timer and SLEEP settings. 2. MODE Button * Press this button, you can select the running mode as follows: Note: HEAT mode is not available for cool only units. 3. TIMER Button * With the unit ON, press this button to set OFF…
-
each time the “ - ” is pressed, it will decrease by 1℃(1℉)
* The temperature setting ranges from 16℃ (60℉)~32℃(90℉). Note: The temperature cannot be set in AUTO or Fan mode. 8. MENU & OK Button * Press MENU button to enter the function selection mode. Then press and , , to choose the function which you want. After, press OK button, turn on this function. *…
-
Note: The electricity consumption is affected by the ambient temperature and the
house structure etc., and when the ambient temperature is high or the house has a large area, be cautious to use the ECO mode. 13. SLEEP * When the unit is on, press MENU button ,then press , , and to choose the “SLEEP” character, when the “SLEEP” character will blink, and press the “OK” button to…
-
evaporator, so as to prevent the accumulation of bacteria on the evaporator, which
causes fungus and strange smell and is harmful to the health. * When the unit is off, press the “MENU” button, then press , , and to choose the “Anti-F” character , when the “Anti-F” character will blink, and press the “OK” button to highlight (not highlight) the “Anti-F” character , which will…
-
* Anti-F function: When the unit is closed under the modes of cooling, dry or auto (cooling), it will continue to operate for about 3 minutes to dry the moisture on the evaporator, so as to prevent the accumulation of bacteria on the evaporator, which causes fungus and strange smell and is harmful…
-
(60℉)~32℃(90℉), the display changes as you touch the button
3. By pressing the “SPEED” button, you can select the motor speed from LOW, MID, HIGH, TURBO ,AUTO. 4. Press the “ON/OFF” button, the air-conditioner starts to operate. 5. Press the “ON/OFF” button again, the air-conditioner stops. Note: The cold wind type has no heating function. ★ Fan operation…
-
5. Refrigerant System Diagram
5-1 Cooling Only Cooling Mode Indoor Unit Outdoor Unit 20
-
Cooling Cycle
Indoor heat exchanger (Evaporation) Steam-gas of low pressure Compressor (Compression) Liquid of low pressure (also a little gas) Capillary (Throttling) Gas of high pressure & temperature Super cooled liquid of high pressure Outdoor heat exchanger (Condensation) 5-2 Cooling & Heating Cooling Mode…
-
Cooling Cycle
Indoor heat exchanger (Evaporation) Steam-gas of low pressure Compressor (Compression) 4-way valve (Heat pump only) Liquid of low pressure (also a little gas) Gas of high pressure & temperature Capillary (Throttling) Super cooled liquid of high pressure Outdoor heat exchanger (Condensation) …
-
Heating Cycle
Indoor heat exchanger (Evaporation) Gas of high pressure & temperature Compressor (Compression) 4-way valve (Heat pump only) Super cooled liquid of low pressure Steam-gas of low pressure Capillary (Throttling) Super cooled liquid of high pressure 23 Outdoor heat exchanger (Condensation)
-
6. Electrical Part
The diagrams listed below for reference only, please refer to the actual product. 6-1 Electrical Wiring Diagram Indoor Unit 09K 12K 18K 24K 24
-
outdoor Unit
-
Part II : Installation and Maintenance
7. Main Tools for Installation and Maintenance 27
-
8. Installation
8-1 Notes for Installation Important Notices Before installation, please contact with local authorized maintenance center, if unit is not installed by the authorized maintenance center, the malfunction may not solved, due to discommodious contact. The air…
-
The normal operating range is 90%-110% of the local rated voltage. The minimum clearance between the air conditioner and the combustibles is 1.5 m. The power cable enables communication between the indoor and outdoor units. You must first choose the right cable size before preparing it…
-
Mounting plate 1. The wall for installation of the indoor unit shall be hard and firm, so as to prevent vibration. 2. Use the "+" type screw to fasten the peg board, horizontally mount the peg board on the wall, and ensure the lateral horizontal and longitudinal vertical. 3. Pull the peg board by…
-
stock and then run the power cord through the hole, keeping the remaining part as
a protection from rodents. Drain pipe connection 1. Remove the mountings and pull the indoor unit pipe out of the housing. 2. Connect the connecting pipe to the indoor unit: Aim at the pipe center, tighten the Taper nut with fingers, and then tighten the T nut with a torque wrench, and the…
-
Electric Connection Requirement
● Loosen the screws and remove from the unit. ● Connect the cables respectively to the corresponding terminals of the terminal board of the indoor unit (see the wiring diagram), and if there are signals connected to the plug, just conduct butt joint. ●Ground wire: Remove the grounding screw out of…
-
Connecting pipe Plastic Strap Pipe Protection Ring Luting (putty) PC ROLL Set PACKET Selection of Installation location Install the connection pipe Connect the Outdoor Unit with Connecting Pipe: Aim the counter-bore of the connecting pipe at the stop valve, and tighten the Taper nut with…
-
Wiring diagram
Wiring Diagram NOTE: ※ This manual is usually includes the wiring mode for the different kind of A/C. We cannot exclude the possibility that some special type of wiring diagrams are not included. ※ The diagram are for reference only. If the entity is difference with this wiring diagram, please refer…
-
After the pipe side connection is complete, proceed as follows
★Vacuum Pumping Method (R410A refrigerant evacuation must use the vacuum pumping method) Before working on the air conditioner, remove the cover of the stop valve(gas and liquid valves)and be sure to retighten it afterward.(to prevent the potential air leakage) 1. To prevent air leakage and spilling…
-
8-4 Check after installation and test operation
1. Check after installation ★ Electrical Safety Check ① If the supply voltage is as required. ② If there is any faulty or miss connection in each of the power, signal and grounding wires. ③ If the grounding wire of the air conditioner is securely grounded. ★ Installation Safety Check ① If the…
-
9. Maintenance
9-1 Troubleshooting Guide Many error codes many appears on this air conditionor, and this troubleshooting guide is prepared for the maintenance personnel to detect the error position and the parts to be replaced during the troubleshooting process. In this Guide, the Troubleshooting Method is guided…
-
Example
Explanation of error Cause: explain the principle of the specific error. Inspection path: The basic order of troubleshooting. Related key position Tools required Tools that should be carried for such troubleshooting, and for inspection replacing parts that may be necessary for such error. Frequent…
-
(1)E0 - Overcurrent Protection of Indoor Unit
Cause: The main PCB detects that the working current of the system exceeds the upper limit of protection, and will indicate "indoor unit Explanation of overcurrent protectin:. The air conditioner stopps running for error protection and displays the failure code E0. Inspection path: current…
-
(2)E1- Indoor Unit temperature sensor error
Explanation of error Cause: The detection of short circuit or open circuit of Indoor Unit temperature sensor during the inspection of main PCB in the Indoor Unit machine, indicated by “Indoor Unit temperature sensor error”. Inspection path: Sensor→Sensor wire→Connectors→Indoor Unit main PCB Tools…
-
15KΩ
Do not use improper sensor during repairing and maintenance, or it may led to the wrong temperature sensing of the machine, the start error or shutdown error. You can switch the air conditioner to the “Blowing” mode, and judge the accuracy of sensor though environmental temperature displayed on the…
-
20KΩ
Do not use improper sensor during repairing and maintenance, or it may led to the start of protection mode due to wrong temperature sensing of the machine, or the protection error. In case a sensor with the resistance value over 20KΩ is used, the detected temperature will be much lower than the…
-
20KΩ
Do not use improper sensor during repairing and maintenance, or it may led to the start of anti-frosting or overheat protection mode due to wrong temperature sensing of the machine. In case a sensor with the resistance value over 20KΩ is used, the detected temperature will be much lower than the…
-
( 5 ) E4 -Indoor Unit motor error of wall mounted air conditioner ( PG
motor) Cause: PG motor is equipped with speed feedback signal line. When the feedback signal of speed is not received by the Indoor Unit main PCB, it has no way to recognize the rotating speed of motor, which Explanation of will be indicated as “Indoor Unit motor error”. Main causes for the…
-
(6) E4- Indoor Unit motor error of wall mounted air conditioner (DC motor)
Explanation of error Cause: The Indoor Unit motor of some highly energy efficient models is DC motor using a green plug through which the Indoor Unit main PCB can drive the motor and sense the current rotational speed feedback. When the Indoor Unit main PCB cannot receive the rotational speed…
-
Five lead wires division: Count from the outermost side of the four
wires of the DC motor terminal, the first blue wire is the speed feedback wire with a voltage of 0.5-5V when the motor rotates; the second yellow wire is the motor driving wire with a voltage of 2.07.5V when the motor rotates; the second white wire is 15V power cord with a voltage of 15V in normal…
-
(8) P2- High-pressure protection
Explanation of error Cause: In standby state or when the equipment is running, the Highpressure switch is disconnected three times (within 20 minutes) and reported as " High-pressure protection"; Inspection path: High-pressure switch cable → connector → Highpressure switch → main PCB Tools required…
-
The reason why High-pressure switches are often disconnected is the
leakage of equipment. When the high voltage switch is off, first check whether the air conditioner's pressure is normal. If it is normal but the failure is still displayed aftere replacing the Outdoor Unit main PCB, it is possible that the connecting pipe may be too long or the Outdoor Unit ambinet…
-
9-2 Troubleshooting for Normal Malfunction
The Foremost Inspecting Items ① The input voltage must be within +10% tolerance of the rated Voltage. If it is not the case, the air-conditioner will probably not work normally. ② Check the connecting cord between indoor unit and outdoor unit to see if it is properly connected. The connecting must…
-
The compressor stops running but the indoor Motor keeps working when it is at cooling mode with the indoor temperature higher than set temperature. If you turn off the air-conditioner and restart it immediately, it will return to normal in 3 minutes, after that, the airconditioner will automatically…
-
②The Indoor Motor Does Not Work
-
(2) Trouble shooting procedure
③The Outdoor Unit Does Not Work (1) Items a) Check if the input voltage is correct? b) Check if the wire connection of the outdoor connecting terminal is correct? (2) Trouble shooting procedure 52
-
④The Step Motor Does Not Work
(1) Items a) Check if the input voltage is correct? b) Check if the step motor controlling the up-down movement firmly connected to Cn2? 53
-
(2) Trouble shooting procedure
⑤Heating Mode Can Work, But No Hot Air Blow (1) Check if the set temperature is lower than the indoor temperature? (2) Check if the indoor PCB is connected to the terminal correctly? 54
-
⑥ Remote Control Can Not Work
Trouble shooting procedure 55
-
10. Exploded Views and Parts List
10-1 Indoor Unit Exploded View 57
-
Part List
NO. 1 Part Name panel Quantity 1 NO. 13 Part Name Evaporator assembly Quantity 1 2 Display board 1 13.1 Evaporator left side carriage Air louver Filter 1 2 13.2 13.3 Evaporator part A Evaporator part B Medium frame decorative strip 1 14 Motor cover 1 6 Left side panel 1 15 IDU Motor 1 7 Medium frame…
-
10-2 Outdoor Unit
Exploded View 59
-
Part List
NO. Part Name Quantity NO. Part Name Quantity 1 Right side board 1 17 Condenser assembly 1 2 E-parts cover 1 17.1 Condenser assembly 1 3 Valve plate 1 17.2 Capillary assembly 1 4 Stop valve 1 18 Top cover 1 5 Stop valve 1 19 4-way valve tubing assembly 1 6 Compressor assembly 1 19.1 4-way valve 1 7…
-
11. Removal Procedure
Stop operation of the air conditioner and remove the power cord before repairing the unit. 11-1 Indoor Unit Parts Procedure Front Panel 1) Turn off the power, hold the middle panel with the middle finger, 2) open the panel upwards, remove the panel fixing shaft, and remove the panel. air louver…
-
Medium
frame wiring cover Loosen the screws of the medium frame wiring cover with screwdriver , remove the electric box cover. medium frame Loosen the clasps of the medium frame , remove the medium frame. Electrical Parts (Main PCB) 1) Take all the connector of PCB upper side out.(Including Power cord) 2)…
-
Motor press
plate Remove the screw of the motor press plate and then remove the press plate. Motor & Cross Motor 1) Loosen fixing screws and detach the motor holder. 2) Loosen fixing screw of motor. (with a M6 wrench) 3) Detach the motor from the motor. 4) Detach the motor from the left holder bearing. volute…
-
11-2 Outdoor Unit
Part Procedure Diagram top cover Turn off the power , remove connection screws among top cover plate, front panel and right side panel, then remove the top cover. panel grille Remove connection screws between the front grille and the front panel .Then remove the front grille. Front panel Remove…
-
E-part cover
Remove connection screws Connecting the right side panel, then remove the Epart cover. Right side panel Remove connection screws connecting the right side panel with the valve support and electric box, then remove the right side panel. Axial flow blade Remove the nut fixing the blade and then remove…
-
Motor
support Remove the tapping screws fixing the motor support . Lift motor support to remove it. Electric box assy Loosen the wire and disconnect the terminal. Lift to remove the electric box assy. Partition board Loosen the screws of the partition board , then lift and pull the partition board to…
-
Pipeline
assembly After the unit is discharged, Unscrew the fastening nut of the 4-way Valve Assy coil and remove the pipeline assembly. Stop valve assembly 1) Remove the screws fixing the gas 2) valve. Unsolder the welding spot connecting gas valve and air return pipe and remove the gas valve. 3) Remove the…
-
condenser
Loosen fixing screws Connecting chassis, and remove the condenser. Last remaining chassis. 69
-
Appendix
AUX Common Sensor R-T Analysis Table Temperature sensor R-T analysis table (15K ) Sensor standard resistance:15KΩ±3% B:B(25/50)=3950K±2%Reference temperature:25(℃) MCU_A/D exchange ±3LSB(at10bit) Series (sampling) resistor:10(KΩ)±1% (except disk sensor) Single chip (A/D reference voltage) supply…
-
MCU_A/D exchange ±3LSB(at10bit) Series(sampling)resistor:10(KΩ)±1% Single chip (A/D reference voltage) supply voltage:5V Temp (℃) -30 -29 -28 -27 -26 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 Resistance(KΩ) MIN TYP MAX 318.3 347.0 377.6 299.6 326.2…
-
Sensor standard resistance:50KΩ±2% B:B(25/50)=3950K±2% reference temperature:25(℃) MCU_A/D exchange ±2LSB(at8bit) Series(sampling)resistor:5.1(KΩ)±1% Single chip (A/D reference voltage) supply voltage:5V Temp (℃) -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 Resistance(KΩ)…
-
2.143 2.08 2.02 1.961 1.905 1.85 1.797 1.746 1.696 1.648 1.602 1.556 1.513 1.471 1.43 1.39 1.351 1.314 1.278 1.243 1.209 1.176 1.144 1.113 1.083 1.054 1.026 0.9986 0.9721 0.9463 0.9213 0.897 0.8734 0.8505 0.8283 0.8068 0.7858 0.7655 0.7458 2.255 2.19 2.127 2.066 2.007 1.95 1.895 1.841 1.789 1.739…
-