Installation and maintenance manual
Manuel d’installation et de maintenance Installations- und Wartungshandbuch Manuale di installazione e di manutenzione Manual de instalación y de mantenimiento ROOFT@IR 40 ÷ 110 English 40 108 kW 38 107 kW Français Deutsch Roof-mouted air conditioning unit Unite d'air conditionne de toiture…
-
INSTALLATION INSTRUCTION
NOTICE D’INSTALLATION INSTALLATIONSHANDBUCH ISTRUZIONI INSTALLAZIONE INSTRUCCIONES DE INSTALACIÓN
-
POWER SUPPLY MUST BE
SWITCHED OFF BEFORE STARTING TO WORK IN THE ELECTRIC CONTROL BOX GENERAL RECOMMENDATIONS Please read the following safety precautions very carefully before installing the unit. SAFETY DIRECTIONS Follow the safety rules in forces when you are working on your appliance. The installation, commissioning…
-
EQUIPMENT SAFETY DATA
Safety Data R410A Toxicity Low In contact with skin Skin contact with the rapidly evaporating liquid may cause tissue chilblains. In case of skin contact with the liquid, warm the frozen tissue with water and call a doctor. Remove contaminated clothing and footwear. Wash the clothing prior to…
-
INSPECTION AND STORAGE
At the time of receiving the equipment carefully cross check all the elements against the shipping documents in order to ensure that all the crates and boxes have been received. Confirmation of the type of unit ordered can be obtained by reading the maker’s plate (capacity, type and air blowing…
-
TECHNICAL SPECIFICATIONS
Models Compressor type Compressor quantity Number of circuit Refrigerant Charge of circuit kg Number of blower Type Nominal indoor airflow m3/h Number of outdoor fans Type Nominal external total airflow m3/h 40 Scroll Tandem Scroll Tandem Scroll Scroll Scroll Scroll Scroll R410A SEE NAME PLATE…
-
The unit is also designed to be lifted by slings
The rings mounted rigidly on the unit’s base frame enable lifting in complete safety. A spreader must be used to avoid damaging the casing of the machine. 60-110 2420 32 22 3328 36 36 C A B C 40-50 Ø30 A B NET WEIGHT Models Weight Kg 1085 1125 THE LIFTING POINT MUST SUIT THE UNIT’S CENTRE OF GRAVITY…
-
ELECTRICAL SPECIFICATIONS
UNIT WITHOUT HEATING Models PE GE PE GE PE GE PE GE PE GE PE GE PE GE Power supply 3+N /400 /50Hz Maximum current A Total starting current A Fuse rating FFG aM A UNIT WITH HEATING TYPE CH1 Models PE GE PE GE PE GE PE GE PE GE PE GE PE GE Power supply 3+N /400 /50Hz Capacities KW Maximum current A…
-
CLEARANCE
The drawing below illustrates the minimum service clearances to be provided around the unit to guarantee access and proper operation. Take particular care not to obstruct the outdoor coil in order to ensure proper air circulation through the appliance. In addition to the service clearances stated on…
-
ROOF CURB
The main purpose of the roof curb is to provide weatherproof passage, supply and return air down to the building from the ROOFT@IR. In this way, all connections (air, electricity) to the building are not free above the roof. The curb provides a perfect roofing thermal insulation and weight…
-
CONFIGURATION OF THE UNIT
GENERALITES The unit is designed to be connected to a duct work. Should it not be the case, a discharge protection grille and a device creating sufficient pressure drop must be supplied by the installer to avoid excess current draw generated at the motor (see blower curves in the appendix) 4…
-
ECONOMISER
The economiser is a set of two dampers driven by one actuator. The quantity of outdoor air introduced into the building varies according to the room set point and provides energy savings in both modes. Economiser is used to modulate the return and outdoor air volumes. It also provides an antifreeze…
-
WIRING DIAGRAM AND LEGEND
WIRING DIAGRAM SEE APPENDIX LEGEND N766 SE3377 models 40/50 Control 230V 50Hz +/- 10% SE33781 models 40/50 Power Tri 400V+N 50Hz +/- 10% SE33782 models 40/50 Power Tri 400V+N 50Hz +/- 10% SE3380 models 60/70/80 Control 230V 50Hz +/- 10% SE3563 models 100/110 Control 230V 50Hz +/- 10% SE33791 models…
-
AS
Soft start motor – three phase model (option) M3 : Indoor fan motor M4 : Extractor fan motor CV : Extractor fan motor condenser MV1/2/3/4 : Outdoor fan motor CV1/2/3/4 : Outdoor fan motor condenser Q5/6 : Heating elements magnetic circuit breakers (option) K5/6 : Heating elements power contactors…
-
SWS
-
ELECTRICAL CONNECTIONS
WARNING BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, MAKE SURE THAT THE ELECTRICAL POWER SUPPLY IS DISCONNECTED AND THAT THERE IS NO POSSIBILITY OF THE UNIT BEING STARTED INADVERTENTLY. NON-COMPLIANCE WITH THE ABOVE INSTRUCTIONS CAN LEAD TO INJURY OR DEATH BY ELECTROCUTION. The electrical…
-
The electric connection of range RT is done in a single point on the level of the principal circuit breaker (copper wire cable recommended). RT40 - 50 RT60 - 70 - 80 RT100 - 110 These units are equipped with a local switch used as general terminal board. The switch can be padlocked. A circuit…
-
COMMISSIONING
PRE-START CHECK LIST ELECTRICAL CHECK 1. Electrical installation has been carried out according to unit wiring diagram and the Supply Authority Regulations. 2. size fuses or circuit breaker has been installed at the main switchboard. 3. Supply voltages as specified on unit wiring diagram. 4. All…
-
AIR BALANCING
A variable pulley is fitted to the motor shaft in order adjust to the blower performance to the pressure drop at the duct work. The pulley must be adjusted when the measured external static pressure and air volume (motor current draw) differ from the nominal values at the unit. CASE N°1: There is…
-
OPERATING CHECK LIST
GENERAL Cheek for any unusual noises or vibration in the running components, particularly at the main blower. PHASE ROTATION PROTECTION If the phase at the power supply are not correct, the phase rotation protection device will prevent the machine from starting. ELECTRICAL SET POINTS 1. Set point of…
-
FINAL CHECK
1. All panels and fan guards are in place and secured. 2. .Unit clean and free of remainder installation material. FINAL TASKS Place the plugs back on the valves and check that they are properly tightened. If needed, fix the cables and the pipes on the wall with clamping collars. Operate the air…
-
OPENING OF ACCESS PANELS
All access panels are removable by unscrewing the self tapping retaining screws. BLOWER DRIVE SYSTEM blower shaft and motor bearings are of permanently lubricated, sealed type and require no regular maintenance other than a check on their general condition. The blower belt tension should be checked…
-
SERVICING CHECKLIST
CASING 1. Clean the outer panels. 2. Remove the panels. 3. Check that the insulation is not damaged. Repair as required. CONDENSATE DRAIN PAN 1. Check that the drainage orifices, conduits and syphon are not blocked. 2. Eliminate all accumulated dirt. 3. Check that no traces of rust are present.…
-
TROUBLE SHOOTING
Problem Unit operates continuously but without performing Frozen suction line Evaporator freezing Probable cause Solution Insufficient refrigerant charge. Top up the refrigerant fluid charge. Clogged filter dryer. Replace the filter. Reduced output from one or both circuits Check the 4-ways valves…
-
Problem
Fans do not operate. Fan surging Reduced output in both Heating and Cooling mode Electric heater is not operating. Probable cause Solution Electrical circuit problems. Check the connections. Internal circuit thermal cut-out activated. Contact an approved Service Centre. Duct network pressure too…
-
APPENDIX
ANNEXE ANLAGE ALLEGATO ANEXO
-
таблицы и схемы — в просмотре
-
DIMENSIONS
-
таблицы и схемы — в просмотре
-
900 651.50 RT100 - RT110 3400 3328 3326 1813 1777 2200 2308 V
-
ATTACHMENT TO THE GROUND
-
ROOF CURB
COSTIERE DACHRAHMEN SCANALATURA PERIMETRALE PETO C 400 A 102 D B G 96,50 F H E 96,50 A B C D E F G H 40-50 1726 1837 1956 2069 1182 60-70-80 100-110 2061 2172 2273 2384 1458 ADJUSTABLE VERSION VERSION REGLABLE 5° VERSTELLBARE AUSFÜHRUNG VERSIONE REGOLABILE VERSIÓN AJUSTABLE 2 RIGIDLY WELD PART 2 TO…
-
X
-
207 RETURN AIR COUPE A-A SUPPLY AIR 48 80 COUPE D-D 293.5 SUPPLY AIR 103 1185 INT. RETURN AIR 841 INT. 1975 D C 153 2135 A RETURN AIR A C D 1740 1836 80 180 512.5 COUPE C-C 550 48 SUPPLY AIR int. 420 int. 1900 180 180 XI 1242 VUE DE DESSOUS Ø7 115 115 RETURN AIR Ø7 SUPPLY AIR 28.5 477 2078 APPENDIX…
-
1900 23.50 310 2135 39 364 RETURN AIR SUPPLY AIR AIR FLOW AIR RETURN APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO XII
-
48 372 COUPE G-G RETURN AIR SUPPLY AIR 48 COUPE E-E 243 110 COUPE D-D A 1375 int. G RETURN AIR 1090 int. SUPPLY AIR 487 int. 78.50 414 211 D E TOP VIEW 2297 2457 G RETURN AIR SUPPLY AIR 80 80 E D 2080 2176 180 180 XIII 1147 AIR SUPPLY 230 RETURN AIR 230 1432 115 Ø 7 Ø 7 RETURN AIR 180 180 2400 DOWN…
-
AIR FLOW
18.50 RT 100 AIR RETURN RT 110 2240 18.50 890.5 2457 52.5 372 XIV RT 60 RT 70 RT 80 RETURN AIR SUPPLY AIR AIR FLOW AIR RETURN APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO
-
DUCT OUTLET DIMENSIONS
-
S3
-
B
-
REFRIGERANT CIRCUIT DIAGRAM
-
RTH40 - RTH50
-
WIRING DIAGRAM
SCHEMAS ELECTRIQUES STROMLAUFPLANS SCHEMA ELETRICO ESQUEMA ELECTRICO TAKE CARE! These wiring diagrams are correct at the time of publication. Manufacturing changes can lead to modifications. Always refer to the diagram supplied with the product. ATTENTION Ces schémas sont corrects au moment de la…
-
RT40 - RT50
pCO1 < > XXII > < > > > > CONTROL
-
L3
-
0 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO XXIV
-
RT60 - RT70 - RT80
pCO1 < > > > < > < > > > > > CONTROL XXV
-
RT100 - RT110
pCO1 < > < > < > > > > > CONTROL XXVI
-
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO XXVIII
-
XXIX
-
XXX
-
AERAULIC ADJUSTMENT
-
RT60 - RT70
ADH450 7(%%, $)!-%4%2 MM r +G M )-0%,,%2 4/4!, %&& +7 20- ,2 0A .M 4/4!, 02%3352% + "%!2).' 0/7%2 + + + 7 7 ,2 7 ,7! IN D"! M S 6OLUME 8 !IR OUTLET VELOCITY 6ELOCITY 0RESSURE M H MS 0A .M Performance shown is for installation type B, free inlet - ducted outlet, and doesn't include the effects of…
-
RDH450
MM 7(%%, $)!-%4%2 + +G M , 2 )-0%,,%2 4/4!, %&& 0A . M +7 4/4!, 02%3352% + "%!2).' 0/7%2 20 - , 2 + + ,7 ! IN D" ! M S M H MS 0A . M 6OLUME 8 !IR OUTLET VELOCITY 6ELOCITY 0RESSURE 0ERFORMANCE SHOWN IS FOR INSTALLATION TYPE " FREE INLET DUCTED OUTLET AND DOESNT INCLUDE THE EFFECT OF APPUNTENANCES IN…
-
RT80 - RT100 - RT110
ADH500 MM 7(%%, $)!-%4%2 r +G M )-0%,,%2 4/4!, %&& +7 ,2 + + + ,2 20- + 0A .M 4/4!, 02%3352% + "%!2).' 0/7%2 + ,7! IN D"! M S M H MS 6OLUME 8 !IR OUTLET VELOCITY 6ELOCITY 0RESSURE 0A .M Performance shown is for installation type B, free inlet - ducted outlet, and doesn't include the effects of…
-
RDH500
MM 7(%%, $)!-%4%2 + 4/4!, 02%3352% 0A .M + + G M + , 2 )-0%,,%2 4/4!, %&& +7 "%!2).' 0/7%2 20- ,2 + + + ,7 ! IN D" ! M S M H 6OLUME 8 !IR OUTLET VELOCITY 6ELOCITY 0RESSURE MS 0A .M 0ERFORMANCE SHOWN IS FOR INSTALLATION TYPE " FREE INLET DUCTED OUTLET AND DOESNT INCLUDE THE EFFECT OF APPUNTENANCES IN…
-
XXXVI
-
START UP FORM / FICHE DE DEMARRAGE
This Appliance has been handed-over Site: User: by (Name of Technician): Company: Date: Signature ALL OPERATIONS, SAFETY MAINTENANCE AND RECOMMANDATIONS HAVE BEEN EXPLAINED TO THE USER Please, return one Copy of this Form to our ASTS department THIS DOCUMENT IS MANDATORY TO START UNIT WARRANTY SIZE…
-
COOLING MODE
-
EC Compliance declaration
Under our own responsibility, we declare that the product designated in this manual comply with the provisions of the EEC directives listed hereafter and with the national legislation into which these directives have been transposed. Déclaration CE de conformité Nous déclarons sous notre…
-
ACE INDUSTRIE
Route de Verneuil 27570 Tillières-sur-Avre FRANCE : +33 (0)2 : +33 (0)2 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Dans un souci d’amélioration constante, nos produits peuvent être modifiés sans préavis.…