Installation and maintenance manual
VLS / VLC / VLH / VLR 524 ÷ 1204 English 137 308 kW Air cooled water chillers, air cooled condensing units and air-to-water reverse cycle heat pumps 150 336 kW IOM VL410-N.1GB Date : July 2007 Supersedes : None
-
Pagina 1 English Table of contents Table of contents 1 FOREWORD 5 START-UP 1.1 Introduction 3 5.1 Preliminary check 21 1.2 Warranty 3 5.2 Start-up 21 1.3 Emergency stop/Normal stop 3 5.3 Checking the operation 22 1.4 An introduction to this manual 3 5.4 Delivery to the customer 22 2 SAFETY 6 CONTROL…
-
Pagina 2 Table of contents 9 MAINTENANCE 9.1 General requirements 77 9.2 Planned maintenance 77 9.3 Refrigerant charge 78 9.4 Compressor 78 9.5 Condenser 78 9.6 Fans 78 9.7 Dehydrating filter 79 9.8 Sight glass 79 9.9 Thermostatic expansion valve 79 9.10 Evaporator 10 TROUBLESHOOTING SPARE PARTS…
-
Pagina 3 1 FOREWORD 1.1 Introduction Itelco-Industry units, manufactured to state-of-the-art design and implementation standards, ensure top performance, reliability and fitness to any type of airconditioning systems. Failure to comply with any of these conditions will automatically void the…
-
Pagina 4 Safety 2 SAFETY 2.1 Foreword These units must be installed in confor mity with the provisions of Machiner y Directive 98/37/EC, Low Voltage Directive 73/23/EC, Pressure Vessels Direc t i v e 9 7 / 2 3 / E C , E l e c t r o m a g n e t i c I n t e r ference Directi ve 89/336/EC, as well as…
-
Pagina 5 OPERATOR: means a person authorised by the owner to do on Itelco-Industry unit all the regulation and control operations expressly described in this manual, that must be strictly complied with, without exceeding the scope of the tasks entrusted to him. ENGINEER: means a person authorised…
-
Pagina 6 Safety I periodically check the board’s internal wiring I do not use cables having an inadequate section or flying connections, even for limited periods of time or in an emergency Prevention of other residual risks I make sure that the connections to the unit conform to the instructions…
-
Pagina 7 English Safety 2.7 Safety labels The labels below will be affixed to each unit in the indicated point: KEEP LIFT HOOK ON THIS LINE TENERE SU QUESTA LINEA GANCIO DI SOLLEVAMENTO Identification of the refrigerant - External door Gravity centre - Base Identification of the unit Outside, on the…
-
Pagina 8 ATTENZIONE INSERIRE LE RESISTENZE DI RISCALDAMENTO OLIO ALMENO 12 ORE PRIMA DI OGNI AVVIAMENTO (SE PREVISTE). 881000215/B Safety PRIMA DELLA MESSA IN TENSIONE ASSICURARSI CHE LE VITI DEI CIRCUITI ELETTRICI SIANO SERRATE COMPLETAMENTE. WARNING ENERGIZE THE CRANCKCASE HEATER FOR AT LEAST 12…
-
Pagina 9 2.8 English Safety Safety regulations Refrigerant data Safety data: R410A Toxicity Low Contact with skin If sprayed, the refrigerant is likely to cause frost burns. If absorbed by the skin, the danger is very limited; it may cause a slight irritation, and the liquid is degreasing. Unfreeze…
-
Pagina 10 Safety General precautions Do not inhale concentrated vapours. Their concentration in the atmosphere should not exceed the minimum preset values and should be maintained below the professional threshold. Being more weighty than the air, the vapour concentrates on the bottom, in narrow…
-
Pagina 11 English Safety Lubricant oil data Safety data: Polyester oil (POE) Classification Not harmful Contact with skin May cause slight irritation. Does not require first aid measures. It is recommended to follow usual personal hygiene measures, including washing the exposed skin with soap and…
-
Pagina 12 Transpor t, Lifting and Positioning 3 TRANSPORT, LIFTING AND POSITIONING It is recommended to use a spacer to prevent cables from damaging the unit (see the figure). Refrigerators are supplied assembled (apart from standard antivibrating rubber supports, that will be installed on site).…
-
Pagina 13 English Transpor t, Lifting and Positioning For lifting operations, use only tools and material fit for this purpose, in accordance with accident-prevention regulations. During the lifting and handling of the unit, be careful not to damage the finned pack of the coils positioned on the…
-
Pagina 14 Installation 4 INSTALLATION 4.1 Positioning of the unit DANGER Before installing the unit, make sure that the structure of the building and/or the supporting surface can withstand the weight of the appliance. The weights of the units are listed in Chapter 8 of this manual. 4.2 Spring…
-
Pagina 15 2) Fit the jack in the threaded housing on the upper plate of the antivibration mount. Next fit the jack mounted on the antivibration mount in the hole in the machine base. I A membrane expansion vessel provided with safety valve with vent, that must be visible. The capacity of the…
-
Pagina 16 Installation Then: I Provide the evaporator with a by-pass circuit equipped with a valve to wash the plant. I Insulate the piping, to prevent the risk of heat loss. I Position a filter on the suction side of the evaporator of the heat recovery condenser. Installation Flow Switch Unit…
-
Pagina 17 4.6 Power supply Before carr ying out any operations on the electrical system, make sure that the unit is deenergised. DANGER It is impor tant that the appliance is groun ded. DANGER The company in charge of the installation shall conform to the standards applicable to outdoor electrical…
-
Pagina 18 Installation VLS/VLH/VLC Version – Electrical Connections Page 18
-
Pagina 19 English Installation VLR Version – Electrical Connections QG - Y1 REMOTE START/STOP SWITCH (SRS) (COMMON) FLOW SWITCH (SF) EXTERNAL INTERLOCK (OPTIONAL) CIRC PUMP ETC EXTERNAL INTERLOCK HEAT RECOVERY QG - Y2 GENERAL ALARM SYSTEM 1 GENERAL ALARM SYSTEM 2 REMOTE INDICATION COMPRESSOR 1 ON…
-
Pagina 20 Installation 4.8 Connecting plate-type evaporator temperature sensors VLS and VLH units are provided with fittings for hydraulic connections between heat exchangers and plant. Each fittings is complete with sensor well to fasten temperature sensor (BT-IN and BT-OUT). Fittings are supplied…
-
Pagina 21 5 START-UP The unit must be started for the first time by personnel suitably trained by one of ItelcoIndustry’s Authorised Service Centre. Failure to meet this requirement will immediately void the warranty. The operations carried out by Itelco-Industry personnel are limited to the…
-
Pagina 22 Star t-up 5.3 Checking the operation Check the following: I The temperature of the water entering the evaporator. I The temperature of the water leaving the evaporator. I The level of the water flow rate in the evaporator, if possible. I The current absorption upon the start of the…
-
Pagina 23 6 GENERAL INFORMATION Introduction This document contains the information and the operating instructions for VLS-VLH-VLC 4 compressors & electronic control. This information is for the after-sales service and the production operators, for the end-of-line testing. Main Characteristics…
-
Pagina 24 Control Access to the “display mask” of the machine status. 6.2 Display Utente Costruttore Manutenzione In/Out Setpoint Versione Fasce orarie Esc key: allows you to move from one mask to another. Alarm key: used to display the alarms, to reset them in manual. Press it one to display the…
-
Pagina 25 I English Control Alarms Code Alarm unit description Comp Status Fan Status Pump Status Aut/Man Reset Delay AL00 Automatic alarm on on on Aut 0 AL01 Efficiency alarm CPS Off Off Off Man 30 sec AL02 Flow meter alarm Off Off Off Man Parameter AL03 Sys 1 High pressure “manual reset” Off Sys 1…
-
Pagina 26 Control I Code Alarm driver description CIRC 1-EEV 1 Status CIRC 2-EEV 2 Status Notes AL34 Epron failure driver 1 Off Run Man AL35 Epron failure driver 2 Run Off Man AL36 Cable motor EVV driver 1 Off On Man AL37 Cable motor EVV driver 2 On Off Man AL38 Timeout MOP driver 1 0% - Auto AL39…
-
Pagina 27 6.4 Protection and Safety Equipment Defrosting System (only for VLH models) The VLH units are provided with an automatic defrosting system, which prevents the formation of excessive ice banks on coolant/air exchangers during heat pump operation. This system, which is part of the electronic…
-
Pagina 28 Control 6.5 SIF version configuration Units equipped with special inverter fans (SIF) can be set-up on the field to give the unit a specific static pressure. By entering parameter in service level - Max Speed (Vdc) - it is possible to modify high static pressure. Size VLS 524 VLS 604 VLS…
-
Pagina 29 7 English General Description GENERAL DESCRIPTION 7.1 Introduction The VLS/VLH units are water chillers /air-water heat pumps provided with hermetic scroll compressors with two refrigeration circuits. These units are fit for cooling and heating intermediate Version (STD/HSE1) VLS/VLH Base…
-
12:10 Pagina 30 General Description 7.7 The hydraulic connections to the evaporator are of 2” 1 /2 Victaulic type on 504 – 804 units and 3” Victaulic type on 904 – 1204 units. Fans Fans are of directly coupling propeller type, provided with aluminium blade with wing profile. Each fan is provided…
-
12:10 Pagina 31 English General Description VLC refrigeration diagram AT G 2 A S S A 1 1 OIL EQUAL. OIL EQUAL. A AT A G 3 3 S 2 S BT BT D D S S 3 3 Components: 1) Compressor Tandem Scroll Type 2) Air cooled condenser 3) Globe valve 3 3 Safety /control devices: A - High Pressure switch (42 bar) AT…
-
Pagina 32 General Description 7.8 Electric power supply and control system RS-485 serial card (for MODBUS or LONWORK or BACNET ) The control compartment contains and electronic card with keyboard and a display for working parameters, alarms, if any, and operating blocks. It is complete with remote…
-
Pagina 33 8 English 50 Technical data TECHNICAL DATA 8.1 Pressure drops PRESSURE DROP IN THE EVAPORATOR VLS 524 VLS 604 VLS 704 VLS 804 VLS 904 VLS 1004 VLS 1104 VLS 1204 kPa/(l/s)^2 0,66 0,66 0,66 0,54 0,19 Min. water flow rate l/s 4,1 4,6 5,3 5,9 6,8 7,5 8,3 9,2 Nominal flow rate l/s 6,5 7,4 8,5…
-
Pagina 34 Technical data 8.2 Technical data VLS BLN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet…
-
Pagina 35 VLS BLN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet diameter Weights…
-
Pagina 36 Technical data VLS LN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet…
-
Pagina 37 VLS LN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet diameter Weights…
-
Pagina 38 Technical data VLS ELN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet…
-
Pagina 39 VLS ELN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet diameter Weights…
-
Pagina 40 Technical data VLS HT Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet…
-
Pagina 41 VLS HT Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet diameter Weight…
-
Pagina 42 Technical data VLH BLN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet…
-
Pagina 43 VLH BLN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet diameter Weights…
-
Pagina 44 Technical data VLH LN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet…
-
Pagina 45 VLH LN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet diameter Weights…
-
Pagina 46 Technical data VLH ELN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet…
-
Pagina 47 VLH ELN Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet diameter Weights…
-
Pagina 48 Technical data VLH HT Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet…
-
Pagina 49 VLH HT Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Condenser Type Hydraulic connections Type Inlet diameter Outlet diameter Weights…
-
Pagina 50 Technical data VLC BLN Power supply Number of circuits Capacity steps Refrigerant Type Compressor Type Number Start-up type N° of loading stages Condenser 524 V/ph/Hz % 2 25-50-75-100 (±10%) / 3 / 28-57-78-100 20-50-70-100 804 2 25-50-75-100 R410A Scroll 0/100 0/100 Direct 0/100 0/100 Type…
-
Pagina 51 VLC BLN Power supply Number of circuits Capacity steps Refrigerant Type Compressor Type Number Start-up type N° of loading stages Condenser 904 V/ph/Hz % 2 28-50-78-100 1004 1104 400 (±10%) / 3 / 25-50-75-100 23-50-73-100 1204 2 25-50-75-100 R410A Scroll 0/100 0/100 Direct 0/100 0/100 Coil…
-
Pagina 52 Technical data VLC LN Power supply Number of circuits Capacity steps Refrigerant Type Compressor Type Number Start-up type N° of loading stages Condenser 524 V/ph/Hz % 2 25-50-75-100 (±10%) / 3 / 28-57-78-100 20-50-70-100 804 2 25-50-75-100 R410A Scroll 0/100 0/100 Direct 0/100 0/100 Coil…
-
Pagina 53 VLC LN Power supply Number of circuits Capacity steps Refrigerant Type Compressor Type Number Start-up type N° of loading stages Condenser 904 V/ph/Hz % 2 28-50-78-100 1004 1104 400 (±10%) / 3 / 25-50-75-100 23-50-73-100 1204 2 25-50-75-100 R410A Scroll 0/100 0/100 Direct 0/100 0/100 Coil…
-
Pagina 54 Technical data VLC ELN Power supply Number of circuits Capacity steps Refrigerant Type Compressor Type Number Start-up type N° of loading stages Condenser 524 V/ph/Hz % 2 25-50-75-100 (±10%) / 3 / 28-57-78-100 20-50-70-100 804 2 25-50-75-100 R410A Scroll 0/100 0/100 Direct 0/100 0/100 Coil…
-
Pagina 55 VLC ELN Power supply Number of circuits Capacity steps Refrigerant Type Compressor Type Number Start-up type N° of loading stages Condenser 904 V/ph/Hz % 2 28-50-78-100 1004 1104 400 (±10%) / 3 / 25-50-75-100 23-50-73-100 1204 2 25-50-75-100 R410A Scroll 0/100 0/100 Direct 0/100 0/100 Coil…
-
Pagina 56 Technical data VLC HT Power supply Number of circuits Capacity steps Refrigerant Type Compressor Type Number Start-up type N° of loading stages Condenser 524 V/ph/Hz % 2 25-50-75-100 604 Page 25-50-75-100 R410A Scroll 0/100 0/100 Direct 0/100 0/100 Coil Type Refrigerant connections Inlet…
-
Pagina 57 VLC HT Power supply Number of circuits Capacity steps Refrigerant Type Compressor Type Number Start-up type N° of loading stages Condenser 904 V/ph/Hz % 2 28-50-78-100 1004 1204 2 25-50-75-100 R410A Scroll 0/100 0/100 Direct 0/100 0/100 Coil Type Refrigerant connections Inlet diameter…
-
Pagina 58 Technical data VLR Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Hydraulic connections Type Inlet diameter Outlet diameter Recovery…
-
Pagina 59 VLR Power supply Number of circuits Capacity steps Refrigerant Type Charge (1) Compressor Type Number Start-up type N° of loading stages Evaporator Type Number Water flow rate Pressure drop Water volume Hydraulic connections Type Inlet diameter Outlet diameter Recovery condenser Type…
-
Pagina 60 Technical data 8.3 Unit Electrical Data 524 VLS/VLH/VLC/VLR BLN Rated voltage 1004 1104 1204 400 (±10%) /3/50 V/ph/Hz Max. absorbed power kW 60,0 69,6 80,8 96,4 105,2 112,0 130,0 148,0 Rated current A 88,0 100,0 112,0 120,0 142,0 160,0 172,0 184,0 Max. current FLA A 148 156,0 186,0 172,0…
-
Pagina 61 English 50 Technical data 524 VLS/VLH/VLC/VLR HSE BLN Rated voltage 1004 1104 1204 400 (±10%) /3/50 V/ph/Hz Max. absorbed power kW 60,4 70,2 81,4 97,0 106,0 112,8 130,8 148,8 Rated current A 87,4 99,1 114,1 119,1 140,8 158,8 170,8 182,8 Max. current FLA A 147,4 155,1 185,1 171,1 191,8…
-
Pagina 63 English 50 Technical data Fans Electrical Data VLS/VLH/VLC/VLR BLN Power supply V/ph/Hz Number 804 904 1004 1104 1204 (±10%)/3/50 Rated power kW 2,0 2,0 2,0 2,0 2,0 2,0 2,0 2,0 Absorbed rated current FLA A 4,0 4,0 4,0 4,0 4,0 4,0 4,0 4,0 1004 1104 1204 VLS/VLH/VLC/VLR LN/ELN Power supply…
-
Pagina 68 Technical data 8.5 Overall dimensions VLS/VLH 524-604 BLN/LN/ELN/HT 2 FANS size 524 3 FANS size D * C 1761 LIFT 1029 A 682 934 B 576 1044 3300 396 2200 396 1100 (*) Only with 2 pumps 2300 WATER CONNECTIONS 1179 LIFT 1249 Page 68 WATER OUTLET “A” 2” 1/2 M WATER INLET (with pump) “B” 2” 1/2…
-
Pagina 70 Technical data VLC 524-604 BLN/LN/ELN/HT 2 FANS size FANS size 604 1761 LIFT 3300 396 2200 2300 1100 1179 LIFT 1249 Page suction line : 1"5/8 ODS 80 circ.1 liquid line : 7/8" ODS 324 1044 circ.2
-
Pagina 72 Technical data VLR 524-604 BLN/LN/ELN/HT 2 FANS size 524 C B A D FANS size 604 1761 LIFT 172 355 1044 3300 396 2200 396 2300 1100 WATER CONNECTIONS WATER OUTLET “A” 1179 LIFT 1249 Page 72 2” 1/2 M WATER OUTLET (recover) “B” 2” 1/2 M WATER INLET “C” 2” 1/2 M WATER INLET (recover) “D” 2” 1/2…
-
Pagina 74 Technical data VLS/VLH 524-604 with hydrokit 2 FANS size 524 3 FANS size 604 130 B 193 934 A 1029 285 250 D 2208 LIFT 1044 4260 2200 883 480 2300 1100 WATER CONNECTIONS 1179 LIFT 1275 Page 74 WATER OUTLET “A” 2” 1/2 M WATER INLET (with pump) “B” 2” 1/2 M DESUPERHEATER IN/OUT “D” 4x 1” M
-
Pagina 77 MAINTENANCE Planned maintenance DANGER Do not throw away the waste oil of the compressor, because it contains refrigerant in solution. The waste oil must be returned to the manufacturer. Unless otherwise specified, the operations described below may be carried out only by a trained…
-
Pagina 78 Maintenance 9.3 Refrigerant charge Do not inject refrigerant liquid into the LP side of the circuit. Be ver y careful, and charge the circuit properly. If the charge is insufficient, the efficiency of the unit will be lower than expected. In the worst of cases the LP pressure switch may be…
-
Pagina 79 9.7 Dehydrating filter The refrigeration circuits are provided with dehydrating filters. The filter clogging is marked by the presence of air bubbles in the sight glass, or by the difference between the temperatures measured downstream from and upstream of the drying filter. If, once the…
-
Pagina 80 Troubleshooting 10 TROUBLESHOOTING The table below lists the anomalies of operation of the unit, the relevant causes and the corrective measures. For anomalies of any other type or not listed, contact one of Itelco-Industry’s Service Centre for technical assistance. Anomaly Cause Operation…
-
Pagina 81 Anomaly Cause Operation One or both compressors are not working. Breaking of the electric circuit. Check the electric circuit and detect any ground dispersions and short circuits. Check fuses. Inter vention of the HP pressure switch. Reset the pressure switch and the control panel and…
-
Pagina 82 Spare parts 11 SPARE PARTS 11.1 Spare part list The table below shows the list of spare parts recommended during the first two years of operation. Component HP pressure switch LP pressure switch Gas filter Thermostatic valve Auxiliary relays Fan’s fuses Compressor’s fuses Auxiliary fuses…
-
Pagina 83 12 DISMANTLING, DEMOLITION AND SCRAPPING DANGER During the draining of the refrigeration circuits, do not let the refrigerant overflow in the surrounding atmosphere. The circuit must be drained using suitable recovery equipment. Do not disperse the waste oil of the compressors in the…
-
As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Your distributor : ITELCO-INDUSTRY Via XXV Aprile, 29 20030 BARLASSINA (MI) - ITALY : +39 0362 6801 : +39 0362 680281