Installation and maintenance manual
SWS / SWR English 272 1148 kW Water cooled water chillers with screw compressors IOM SWS-N.2GB Date : July 2007 Supersedes : IOM SWS-N.1GB
-
Pagina 1 English Table of contents Table of contents 1 FOREWORD 5 START-UP 1.1 Introduction 3 5.1 Preliminary check 19 1.2 Warranty 3 5.2 Start-up 19 1.3 Emergency stop/Normal stop 3 5.3 Checking the operation 20 1.4 An introduction to the manual 3 5.4 Delivery to customer 20 2 SAFETY 6 OPERATION…
-
Pagina 2 Table of contents 9 MAINTENANCE 9.1 General requirements 74 9.2 Planned maintenance 74 9.3 Refrigerant charge 75 9.4 Compressors 75 9.5 Condenser 75 9.6 Dehydrating filter 76 9.7 Sight glass 76 9.8 Thermostatic expansion valve 76 9.9 Evaporator 76 10 TROUBLESHOOTING 77 11 SPARE PARTS 11.1…
-
Pagina 3 1 FOREWORD 1.1 Introduction Itelco-Industry units, manufactured to state-of-the-art design and implementation standards, ensure top performance, reliability and fitness to any type of airconditioning systems. These units are designed for cooling water or glycoled water (and for water…
-
Pagina 4 Safety 2 SAFETY 2.1 Foreword These units must be installed in conformity with the provisions of Machinery Directive 98/37/EC, Low Voltage Directive 73/23/EC, Pressure Vessels Directive 97/23/EC, Electromagnetic Interference Directive 89/336/EC, as well as with other regulations applicable…
-
Pagina 5 OPERATOR: means a person authorised by the owner to do on Itelco-Industry unit all the regulation and control operations expressly described in this manual, that must be strictly complied with, without exceeding the scope of the tasks entrusted to him. ENGINEER: means a person authorised…
-
Pagina 6 Safety I periodically check the board’s internal wiring I do not use cables having an inadequate section or flying connections, even for limited periods of time or in an emergency Prevention of other residual risks I make sure that the connections to the unit conform to the instructions…
-
Pagina 7 English Safety 2.7 Safety labels The labels below will be affixed to each unit in the indicated point: KEEP LIFT HOOK ON THIS LINE TENERE SU QUESTA LINEA GANCIO DI SOLLEVAMENTO Identification of the refrigerant - External door Gravity centre - Base Identification of the unit Outside, on the…
-
Pagina 8 ATTENZIONE INSERIRE LE RESISTENZE DI RISCALDAMENTO OLIO ALMENO 12 ORE PRIMA DI OGNI AVVIAMENTO (SE PREVISTE). 881000215/B Safety PRIMA DELLA MESSA IN TENSIONE ASSICURARSI CHE LE VITI DEI CIRCUITI ELETTRICI SIANO SERRATE COMPLETAMENTE. WARNING ENERGIZE THE CRANCKCASE HEATER FOR AT LEAST 12…
-
Pagina 9 2.8 English Safety Safety regulations Refrigerant data Safety data: R407C, R134a, R22 Toxicity Low Contact with skin If sprayed, the refrigerant is likely to cause frost burns. If absorbed by the skin, the danger is very limited; it may cause a slight irritation, and the liquid is…
-
Pagina 10 Safety General precautions Do not inhale concentrated vapours. Their concentration in the atmosphere should not exceed the minimum preset values and should be maintained below the professional threshold. Being more weighty than the air, the vapour concentrates on the bottom, in narrow…
-
Pagina 11 English Safety Lubricant oil data Safety data: Polyester oil (POE) Classification Not harmful Contact with skin May cause slight irritation. Does not require first aid measures. It is recommended to follow usual personal hygiene measures, including washing the exposed skin with soap and…
-
Pagina 12 Transport, Lifting and Positioning 3 TRANSPORT, LIFTING AND POSITIONING Refrigerators are supplied assembled (apart from standard antivibrating rubber supports, that will be installed on site). The equipment are full of refrigerant and oil, in the quantity required for a proper operation.…
-
Pagina 13 English Transport, Lifting and Positioning For lifting operations, use only tools and material fit for this purpose, in accordance with accident-prevention regulations. It is recommended not to remove the protective plastic envelope, tha should prevent scraps from penetrating into the…
-
Pagina 14 Installation 4 INSTALLATION 1) proceed with the assembly of the jack components 4.1 Positioning the unit Before installing the unit, make sure that the structure of the building and/or the supporting surface can withstand the weight of the appliance. The weights of the units are listed in…
-
Pagina 15 4.3 External hydraulic circuit The external hydraulic circuit must ensure the water flow to the evaporator under any working conditions and with any adjustment. The external hydraulic circuit should consist of the following elements: I A circulation pump which delivers a sufficient water…
-
Pagina 16 Installation Before filling the circuit, it is important to check that it is free from any foreign matter, sand, gravels, rust, welding deposits, waste and other materials that may damage the evaporator. When cleaning the lines, it is recommended to create a circuit by-pass. It is…
-
Pagina 17 Itelco-Industry may not be held liable for any damage and/or injury caused by failure to comply with these precautions. The unit conforms to EN 60204-1. The following connections shall be provided: I A 3-phase and grounding connection for the power supply circuit. I The electrical…
-
Pagina 18 Installation Terminal box QG - Y1 REMOTE START/STOP SWITCH (SRS) 01 01 (COMMON) 02 02 (SRHP) REMOTE SUMMER/WINTER SWITCH PHASE VOLTAGE CONTROL (ACCESSORY) (SQZ) DOUBLE SET-POINT (DAY/NIGHT) (SDN) FLOW SWITCH (SF) EXTERNAL INTERLOK (OPTIONAL) CIRC PUMP ETC (COMMON) (2-SLS/OFF) (SYS.1) 161…
-
Pagina 19 5 START-UP The unit must be started for the first time by personnel suitably trained by one of ItelcoIndustry ’s Authorised Service Centre. Failure to meet this requirement will immediately void the warranty. The operations carried out by Itelco-Industry personnel are limited to the…
-
Pagina 20 Start-up 5.3 Checking the operation Check the following: I The temperature of the water entering the evaporator. I The temperature of the water leaving the evaporator. I The level of the water flow rate in the evaporator, if possible. I The current absorption upon the start of the…
-
Pagina 21 6 OPERATION These chillers are equipped with a microprocessor control logic and regulation management system. The system consists of a unit logic board and a liquid crystal control panel which manages the control, starting, shutdown and display functions. 6.1 General Information I…
-
Pagina 22 Operation The connection between the terminal unit and the board is realized by a 6 ways phone cable. The connection between the terminal unit and the main board is not strictly necessary to the normal operation of the controller. menu I/O ? info on-off menu set alarm prog enter Access to…
-
Pagina 25 I Setpoint Pushing the “Set” key it is possible to access to user’s Setpoint level. The following table contains the deUser’s Setpoints Control of Low Limit – – Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet — OFF OFF –15 –15 1 1 ITA ENG System #1 ON/OFF System #2 ON/OFF Cooling…
-
Pagina 26 General Description 7 GENERAL DESCRIPTION 7.1 Introduction The water chillers with two refrigeration circuits of the SWS series have been designed for indoor installation. For heat dissipation purposes, the SWS units must be coupled to a cooling tower, or use well water. The series…
-
Pagina 27 7.4 Refrigerant circuits 7.5 Evaporator Every single SWS unit has two complete refrigerant circuits, one per compressor. Each refrigerant circuit includes: a service valve for refrigerant filling, shutoff valves for suction lines (on request), as well as for the delivery and liquid lines…
-
Pagina 28 General Description SWR refrigeration diagram Nota: the units are equipped with two refrigeration circuits. Only one circuit is illustrated for the sake of simplicity. Components: Screw compressor Screw compressor’s delivery cock Flexible hose - absorber (ELN version only) Silencer (ELN…
-
Pagina 29 I The display of the compressor’s working hours and the temperature of the water to the evaporator. I The anti-cycling and delay timing upon start-up. I The automatic advance/delay sequence for the compressor start-up. English General Description Reference and parameter control: I User…
-
Pagina 30 Technical data 8 TECHNICAL DATA 8.1 Pressure drops Evaporator SWS R407C 1002 1202 1402 1602 1902 2202 K 10 kPa/(m /s) 23.5 23.5 11.3 11.3 7.8 4.6 Min. water flow rate l/s 9.9 10.7 11.8 13.4 16.7 20.5 Max. water flow rate l/s 23.1 24.9 27.6 31.4 39.0 47.7 Min. pressure drops kPa 23.1 26.8…
-
Pagina English Technical data Condenser SWS R407C 2 1002 1202 1402 1602 1902 2202 K 10 kPa/(m /s) 55.7 55.7 53.0 43.1 32.4 16.5 Min. water flow rate l/s 6.3 6.8 7.6 8.6 10.7 13.0 Max. water flow rate l/s 14.8 15.9 17.7 20.1 24.9 30.3 Min. pressure drops kPa 22.4 26.0 30.5 32.1 36.8 27.8 Max.…
-
Pagina 32 Technical data 8.2 Technical data SWS 1002-2202 R407C SWS R407C Nominal voltage 1002 1202 1402 V/ph/Hz Number of circuits 1902 2202 400/3/50 2 Number of steps Capacity steps 1602 6 % 25/50/63/75/87/100 Refrigerant Type Charge (1) R407C kg Compressors Type Screw Number Start-up type…
-
Pagina 33 English Technical data SWS 2602-4402 R407C SWS R407C Nominal voltage 2602 3002 3402 V/ph/Hz Number of circuits 3802 4402 400/3/50 2 Number of steps Capacity steps 4202 6 % 25/50/63/75/87/100 Refrigerant Type Charge (1) R407C kg Compressors Type Screw Number Start-up type Y/∆ Evaporator…
-
Pagina 34 Technical data SWS 1602-2352 R134a SWS R134a Nominal voltage 1602 1902 2 2 2202 V/ph/Hz Number of circuits 2352 400/3/50 2 Number of steps Capacity steps 2212 6 % 25/50/63/75/87/100 Refrigerant Type Charge (1) R134a kg Compressors Type Screw Number TStart-up type 2 P/W Y/∆ Evaporator Type…
-
Pagina 35 SWS 2502-3202 R134a SWS R134a Nominal voltage 2502 2652 2 2 2802 V/ph/Hz Number of circuits 3202 400/3/50 2 Number of steps Capacity steps 3012 6 % 25/50/63/75/87/100 Refrigerant Type Charge (1) R134a kg Compressors Type Screw Number 2 Start-up type Y/∆ Evaporator Type Shell & Tube Number…
-
Pagina 36 Technical data SWS 3412-4802 R134a SWS R134a Nominal voltage 3412 3602 2 2 V/ph/Hz Number of circuits 4602 4802 400/3/50 2 Number of steps Capacity steps 4212 6 % 25/50/63/75/87/100 Refrigerant Type Charge (1) R134a kg Compressors Type Screw Number Start-up type 2 Y/∆ Evaporator Type Shell…
-
Pagina 37 SWR 1002-2202 R407C SWR R407C Nominal voltage 1002 1202 1402 V/ph/Hz Number of circuits 1602 2202 2 2 400/3/50 2 Number of steps Capacity steps 1902 6 % 25/50/63/75/87/100 Refrigerant Type R407C Compressors Type Screw Number 2 2 Start-up type Part-Winding 2 Y/∆ Evaporator Type Shell & Tube…
-
Pagina 38 Technical data SWR 2602-4402 R407C SWR R407C Nominal voltage 2602 3002 3402 V/ph/Hz Number of circuits 3802 4402 400/3/50 2 Number of steps Capacity steps 4202 6 % 25/50/63/75/87/100 Refrigerant Type R407C Compressors Type Screw Number Start-up type Y/∆ Evaporator Type Shell & Tube Number…
-
Pagina 39 SWR 1602-2352 R134a SWR R134a Nominal voltage 1602 1902 2 2 V/ph/Hz Number of circuits 2212 2352 2 2 400/3/50 2 Number of steps Capacity steps 2202 6 % 25/50/63/75/87/100 Refrigerant Type R134a Compressors Type Screw Number 2 Start-up type P/W 2 Y/∆ Evaporator Type Shell & Tube Number…
-
Pagina 40 Technical data SWR 2502-3202 R134a SWR R134a Nominal voltage 2502 2652 2 2 V/ph/Hz Number of circuits 3012 3202 400/3/50 2 Number of steps Capacity steps 2802 6 % 25/50/63/75/87/100 Refrigerant Type R134a Compressors Type Screw Number 2 2 Start-up type 2 Y/∆ Evaporator Type Shell & Tube…
-
Pagina 41 SWR 3412-4802 R134a SWR R134a Nominal voltage 3412 3602 2 2 V/ph/Hz Number of circuits 4602 4802 400/3/50 2 Number of steps Capacity steps 4212 6 % 25/50/63/75/87/100 Refrigerant Type R134a Compressors Type Screw Number 2 2 Start-up type 2 Y/∆ Evaporator Type Shell & Tube Number Water flow…
-
Pagina 44 Technical data SWS/SWR R134a Nominal voltage 3412 3602 V(%)-ph-Hz 4212 4602 4802 400 ±10% / 3 / 50 Nominal power input kW Max power input kW Nominal current A Max. current (FLA) A Max. start-up current (LRA) A External fuses (A) Wire cross area (1) (*) mm 2x185 2x185 2x185 2x240 2x240 2…
-
Pagina 63 English Technical data 8.5 Overall dimensions and maintenance space Overall dimensions SWS 1002 - 1902 STD R407C and SWS 1602 - 1902 STD R134a Legend: * Only for shipping 1 Evaporator water inlet 2 Evaporator water outlet 3 Condenser water inlet 4 Condenser water outlet 5 Power inlet…
-
Pagina 64 Technical data Overall dimensions SWR 1002 - 1902 STD R407C and SWR 1602 - 1902 STD R134a Legend: * Only for shipping 1 Evaporator water inlet 2 Evaporator water outlet 3 Condenser water inlet 4 Condenser water outlet 5 Power inlet Dimensions A B C D E F G 1-2 3 4 1002-1202 DN125 (5”) 1…
-
Pagina 65 English Technical data Overall dimensions SWS 2202 - 4402 STD R407C and SWS 2212 - 3012 STD R134a egend: * Only for shipping 1 Evaporator water inlet 2 Evaporator water outlet 3 Condenser water inlet 4 Condenser water outlet 5 Power inlet Dimensions A B C D E F G H 1-2 3-4 2202 1160 DN200…
-
Pagina 66 Technical data Overall dimensions SWR 2202 - 4402 STD R407C egend: * Only for shipping 1 Evaporator water inlet 2 Evaporator water outlet 3 Condenser water inlet 4 Condenser water outlet 5 Power inlet Dimensions A B C D E F G H 1-2 3 4 2202 1160 DN200 (8”) 2 1/8” 1 3/8” 2602-3002-3402 1160…
-
Pagina 67 English Technical data Overall dimensions SWS 3202 - 4802 STD R134a egend: * Only for shipping 1 Evaporator water inlet 2 Evaporator water outlet 3 Condenser water inlet 4 Condenser water outlet 5 Power inlet Dimensions A B C D E F G H L 1-2 3-4 3” GAS F 3202 2050 830 DN200 (8”)…
-
Pagina 68 Technical data Overall dimensions SWS 1002 - 1902 LN/ELN R407C and SWS 1602 - 1902 LN/ELN R134a SWR 1002 - 1902 LN/ELN ad R407C and SWR 1602 - 1902 LN/ELN R134a Legend: * Only for shipping Refer to the standard drawing for the dimensions of connections 5 Power inlet Page 68
-
Pagina 69 English Technical data Overall dimensions SWS 2202 - 4402 LN/ELN R407C and SWS 2202 - 3012 LN/ELN R134a SWR 2202 - 4402 LN/ELN R407C and SWR 2202 - 3012 LN/ELN R134a Legend: * Only for shipping Refer to the standard drawing for the dimensions of connections 5 Power inlet Page 69
-
Pagina 70 Technical data Overall dimensions SWS 3202 - 4802 LN/ELN R134a SWR 3202 - 4802 LN/ELN R134a Legend: * Only for shipping Refer to the standard drawing for the dimensions of connections 5 Power inlet Dimensions A 3202-3412-3602-4212 2130 4602-4802 Page 70 2190
-
Pagina 71 English Technical data Maintenance space SWS 1002 - 1902 R407C and SWS 1602 - 1902 R134a SWR 1002 - 1902 R407C and SWR 1602 - 1902 R134a Page 71
-
Pagina 72 Technical data Maintenance space SWS 2202 - 4402 R407C and SWS 2202 - 3012 R134a SWR 2202 - 4402 R407C and SWR 2202 - 3012 R134a Page 72
-
Pagina 73 English Technical data Maintenance space SWS 3202 - 4802 R134a SWR 3202 - 4802 R134a Dimensions H 3202 2050 3412-3602-4212 2050 4602-4802 2110 Page 73
-
Pagina 74 Maintenance Scheduled Maintenance Do not throw away the waste oil of the compressor, because it contains refrigerant in solution. The waste oil must be retur ned to the manu facturer. Check the temperature of the leaving fluid • Check the pressure drops in the heat exchanger • Check for…
-
Pagina 75 9.3 Refrigerant charge Do not inject refrigerant liquid into the LP side of the circuit. Be ver y careful, and charge the circuit properly. If the charge is insufficient, the efficiency of the unit will be lower than expected. In the worst of cases the LP pressure switch may be activated…
-
Pagina 76 Maintenance 9.6 Dehydrating filter The refrigeration circuits are provided with dehydrating filters. The filter clogging is marked by the presence of air bubbles in the sight glass, or by the difference between the temperatures measured downstream from and upstream of the drying filter.…
-
Pagina 77 English Troubleshooting 10 TROUBLESHOOTING The table below lists the anomalies of operation of the unit, the relevant causes and the corrective measures. For anomalies of any other type or not listed, contact one of Itelco-Industry ’s Service Centre for technical assistance. Anomaly Cause…
-
Pagina 78 Troubleshooting Anomaly Cause Operation One or both compressors are not working. Breaking of the electric circuit. Check the electric circuit and detect any ground dispersions and short circuits. Check fuses. Inter vention of the HP pressure switch. Reset the pressure switch and the…
-
Pagina 79 11 English Spare par t s SPARE PARTS 11.1 Spare part list The table below shows the list of spare parts recommended during the first two years of operation. Component HP pressure switch Gas filter Thermostatic valve Auxiliary relays Compressor’s fuses Auxiliary fuses Set of compressor…
-
Pagina 80 Dismantling, Demolition and Scrapping 12 DISMANTLING, DEMOLITION AND SCRAPPING During the draining of the refrigeration cir cuits, do not let the refrigerant over flow in the surrounding atmosphere. The circuit must be drained using suitable recover y e q u i p m e n t . Do not disperse…
-
As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Your distributor : ITELCO-INDUSTRY Via XXV Aprile, 29 20030 BARLASSINA (MI) - ITALY : +39 0362 6801 : +39 0362 680281