Инструкция на Чиллеры Airwell MQL/ MQH с воздушным охлаждением
Модели MQH 06-18. Чиллеры с воздушным охлаждением конденсатора. Руководство по монтажу и эксплуатации.
Смотрите также: Техническое описание →
Загружаем документ…
Текст инструкции
-
Zertifizierungsstelle / Organismo Notificado No. 0035
-
Foreword
1 FOREWORD 1.1 Introduction The units, manufactured to state-of-the-art design and implementation standards, ensure top performance, reliability and fitness to any type of air-conditioning system. These units are designed for cooling water* or glycoled water (and for water heating in heating mode)…
-
SAFETY 2.1 Foreword These units must be installed in conformity with the provisions of Machinery Directive 2006/42/EC, Low Voltage Directive 2006/95/EC, Pressure Vessels Directive 97/23/ EC, Electromagnetic Interference Directive 89/336/EC, as well as with other regulations applicable in the country…
-
ENGINEER: means a person authorised directly by the
agent or, in all EC countries, excluding Italy, under his full responsibility, by the distributor of the unit, to perform any routine and extraordinary maintenance operations, as well as any regulation, control, servicing operations and the replacement of pieces, as may be necessary during the life…
-
Prevention of other residual risks
make sure that the connections to the unit conform to the instructions provided in this manual and on the unit's panelling if you have to disassemble the unit, make sure that it has been properly mounted again before restarting the unit do not touch the delivery pipes from the compressor, the…
-
2.7 Safety regulations
Refrigerant data Safety data: R410A Toxicity Low Contact with skin R410A vapors can irritate the skin and eyes. In liquid form, it can freeze skin on contact. If contact with skin occur, flush the exposed area with lukewarm water until all of the chemical is removed. If there is evidence of…
-
General precautions
Do not inhale concentrated vapours. Their concentration in the atmosphere should not exceed the minimum preset values and should be maintained below the professional threshold. Being more weighty than the air, the vapour concentrates on the bottom, in narrow areas. Therefore, the exhaust system must…
-
Refrigerant oil data
Safety data:Polyvinylether oil (PVE) Classification Not harmful Contact with skin May cause slight irritation. Does not require first aid measures. It isrecommended to follow usual personal hygiene measures, including washing the exposed skin with soap and water several times a day. It is also…
-
Safety Label
Caution Attention Vorsicht Attenzione Precaución C26081700/02 ʽ Do not insert any object into fan grille Ne pas insérer d’objets dans la grille du ventilateur Führen Sie keine Gegenstände in das Ventilatorgitter ein Non intodurre alcun oggetto nella griglia del ventilatore No introduzca objetos en…
-
Transport, Lifting and Positioning
3 TRANSPORT, LIFTING AND POSITIONING Air conditioners are supplied assembled. The equipment are full of refrigerant and oil (except the condensing unit), in the quantity required for a proper operation. The unit cannot be transported at ambient temperature lower than -30°C. 3.1 Inspection When the…
-
INSTALLATION 4.1 Installation advices Unit placement When fixing the unit, a slope of 1 cm/m is recommended to allow draining of rain water. MQH06 and MQH08M/T and MQH10M/T cannot be installed with advanced inclination to 10°. The MQH air-to-water heat pumps must be installed in the open air, in an…
-
Fixing dimensions
The fixing dimensions of the unit are shown on picture 3. Vibration isolators are recommended for all roof mounted installation or wherever vibration transmission is a consideration. Picture 3 Maintenance access w easy access for periodic maintenance works. After installation, each side of the unit…
-
Water connections Safety Differential Pressure Switch Water Piping Local authorities can supply the installer with the proper building and safety codes required for safe and proper installation. Install piping with minimum bends and changes in elevation to minimize pressure drop. Consider the…
-
4.3 Pressure Drop in Tubes and
Accessories To determine the appropriated pipe section, see table 1 which shows the values of pressure drop for various water flows and the diameter of standard copper pipes for hydraulic installations. 4.4 Hydraulic connection The water inlet/outlet fittings shall conform to the instructions…
-
Power supply 4.8 Before carrying out any operations on the electrical system, make sure that the unit is deenergised. It is important that the appliance is grounded. The company in charge of the installation shall conform to the standards applicable to outdoor electrical connections. The…
-
Start-up
5 START-UP On MQH heat pump unit the first start up must be done by an authorized technician. Following suggestions should be applied in order to do the operation properly. 5.1 Preliminary check The checks listed below shall be performed before starting the unit . 5.2 Start-up Start-up sequence…
-
5.3 Checking the operation
Check the following: The temperature of the water entering the evaporator. The temperature of the water leaving the evaporator. The level of the water flow rate in the evaporator, if possible. The current absorption upon the start of the compressor and in case of stabilised operation. The fan's…
-
Control System
6 MINICHILLER CONTROL 6.1 Operating instructions 6.1.1 Before start-up 4) During the normal operation the current value of entering water temperature is displayed flashing alternatively with the current status. To display other useful data, go to level l, use the ^ button to scroll the menu, and use…
-
For 3 phase unit, check the phase monitor
If the green LED light is on, means that the phase connection is reverse, need to exchange any two phase connection of three. When the red LED light is on, the compressor can start up normally. Table 5 List of standard parameters Min Value Display Meaning OPER Cooling/Heating mode selection COOL CSP…
-
General Description
7 GENERAL 7.1 Introduction MQH units are air - cooled heat pumps with a refrigerant circuit equipped with rotary compressors for size 6 to 10 and with scroll compressors for size 12 to 18. MQH units are designed for outdoor installation to ensure highly reliable and efficient performance. These…
-
General Description
Refrigerant Flow Diagrams - MQH 6 /8/10/14/16 Refrigerant Circuit: 1 Compressor 2 4 Way Valve 3 Coil + Fan 4 Main Capillary 5 Bypass Capillary 6 1 Way Drier Filter 7 Liquid Receiver 8 Heat Exchanger 9 Check Valve 10 Accumulator Hydraulic Circuit: 11 Drain Valve 12 Safety Valve 13 Water Manometer 14…
-
8 TECHNICAL DATA
8.1 Technical data Power supply V/ph/Hz Number of circuits Number of steps Refrigerant Type Charge(l) Compressors 1.80 2.20 2.20 2.84 2.75 Type Number Start-up type Rotary Rotary Rotary Rotary Rotary 152 152 Direct Evaporator Type Plate Number Condenser Type Coil Hydraulic connections Type Female…
-
Power supply
Number of circuits Number of steps Refrigerant Type Change(l) Compressors Type 3.60 3.53 4.63 5.65 Scroll Scroll Scroll Scroll Number Start-up type Direct Evaporator Type Plate Number Condenser Type Hydraulic connections Type Coil Female Inlet diameter Inch Outlet diameter Inch Weights Weight of…
-
Unit Electrical Data Rated voltage V-Ph-Hz Max. absorbed power kW Rated current 2.5 9.3 11.1 37.0 20.0 A Max. current(FLA) A Max. start-up current(LRA) A External Fuses A 3.5 13.0 15.6 83.0 25.0 3.3 4.8 5.5 36.0 12.0 4.4 16.4 19.8 96.0 16.0 4.1 5.8 7.0 55.0 12.0 5.7 8.1 9.7 66.0 16.0 6.0 8.5 10.2…
-
English Technical data Overall dimensions MQH 06/08M/08T FRONT VIEW SIDE VIEW DETAIL A TOP VIEW Water pressure gauge Air vent valve Elcctrica power supply Water outlet 3/4" gas fcmalc Water inlet 3/4" gas female LP tap Water drain valve HP tap Water drain valve MQH 10M/10T/12 FRONT VIEW SIDE VIEW…
-
MQH 14/16/18
FRONT VIEW SIDE VIEW DETAIL A TOP VIEW Electrical power supply Water pressure gauge HP tap LP tap 8.4 Clearences MQH 06 to 18 26 Air vent valve Water inlet 1" gas female Water outlet 1" gas female Water drain valve
-
MAINTENANCE
Planned maintenance Check the temperature of the leaving fluid Do not throw away the waste oil of the compressor, because it contains refrigerant in solution. The waste oil must be returned to the manufacturer. Check the pressure drops in the heat exchanger Check for electric absorption Unless…
-
Maintenance
9.3 Refrigerant charge Do not inject refrigerant liquid into the LP side of the circuit. Be very careful, and charge the circuit properly. If the charge is insufficient, the efficiency of the unit will be lower than expected. In the worst of cases the LP pressure switch may be activated, resulting…
-
9.8 Evaporator
Check at regular intervals that the water side of the heat exchanger is perfectly clean. To do this, measure the pressure drop, water side (see Section 8) or measure the temperature of the liquid leaving and entering the heat exchanger, and compare it to the evaporation temperature. To obtain an…
-
Troubleshooting
10 TROUBLESHOOTING The table below lists the anomalies of operation of the unit, the relevant causes and the corrective measures. For anomalies of any other type or not listed, contact one of the Authorised Service Centre for technical assistance. Abnormality Cause Operation The unit continues to…
-
Anomaly
Activation of the LP alarm, stop of the unit Activation of the HP alarm, stop of the unit The liquid line is too hot Operation Cause Gas leak Identify and remove the leak Insufficient charge Refill Failure of the pressure switch Replace the pressure switch Failure of the pressure switch Check the…
-
Spare parts
11 SPARE PARTS 11. 1 Spare part list Exploded view please see appendix B. SPL for MQH 06/08 No. MQH 06 Description MQH 08M QTY QTY MQH 08T QTY top plate condenser assembly fan motor fan base plate left front plate compressor right front plate compressor crank heater 4-way reversing valve air outlet…
-
top plate
fan motor fan guard net assembly capillary assembly HP transducer controller compressor capacitor fan motor capacitor phase protector transformer display panel differential pressure switch twater outlet temperature water inlet temperature OCT OAT dry filter ritht side plate 2 heater exchanger right…
-
Dismantling, Demolition and Scrapping
12 DISMANTLING, DEMOLITION AND SCRAPPING During the draining of the refrigeration circuits, do not let the refrigerant overflow in the surrounding atmosphere. The circuit must be drained using suitable recovery equipment. Do not disperse the waste oil of the compressors in the environment, since it…
-
Wiring Diagram
-
C02
-
Field Wired
-
CP
-
Field Wired
-
C02
-
Field Wired
Field Wired C27019300/04 MQH 10T/12/14/16/18 VII
-
C02
-
Appendix B
-
таблицы и схемы — в просмотре
-
Electra Air-Conditioning(shenzhen)Co., Ltd
2 Wuhe Avenue S., Bantian,Buji shenzhen, China
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.