Water Cooled Water Chillers
-
Specification
General characteristics Condensers The water-cooled water chillers RWC and remote air-cooled water chillers RWR are a compact design suitable for chilled water or glycol cooling. They are designed to be located in a plant room. The condenser shall be a cleanable shell and tube type with a built in…
-
Refrigerant Flow Diagrams
RWC units COMPONENTS Compressor Discharge valve PED safety valve Condenser Liquid valve Filter SAFETY DEVICES Sight glass Solenoid valve Thermal expansion valve Evaporator PED safety valve Pressure tapping points and refrigerant charge/discharge points � HP pressure switch � LP pressure switch…
-
Refrigerant Flow Diagrams (cont'd)
RWR units COMPONENTS SAFETY DEVICES 1 Compressor 8 Solenoid valve 2 Discharge valve 9 Thermal expansion valve 5 Liquid valve 10 Evaporator � HP pressure switch 6 Filter 11 PED safety valve � LP pressure switch 7 Sight glass Pressure tapping points and refrigerant charge/discharge points Cooling mode…
-
Control
Main features - Microprocessor control - User-friendly keyboard - Proportional and integral control of the return water temperature (RWT) - Hysteresis control of the leaving water temperature (LWT) - Access code to enter the Manufacturer’s Level - Access code to enter the Assistance Level - Alarm…
-
Operating Limits
170 RWC / RWR Liquid leaving temperature Evaporator Condenser (2) Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Water °C +6 to +15 Water with glycol °C -5 to +15 °K 3 to 7 Water temp. difference Water flow (1) l/s 5.5 12.8 6.4 14.9 17.2 16.8 9.0 26.0 9.7 23.0 10.7 25.0 Pressure drop…
-
Water Flow and Water Pressure Drop
Water flow is calculated as follows : Water pressure drop is calculated as follows : P x 860 Q= (∆T x 3600) with Q : ∆T : P : K x Q2 ∆P= 10 Water flow (l/s) Temperature difference (K) Heat exchanger capacity (kW) with ∆P : K : Pressure drop (kPa) Pressure drop coefficient EVAPORATOR PRESSURE DROPS…
-
Physical Data - RWC 170 to 360
RWC MODELS Cooling capacity (1) kW 160.8 186.5 210.6 263.6 283.7 312.3 Power input (1) kW 45.8 52.6 56.8 73.0 81.7 90.5 Heat rejection kW 205.7 238.4 267.4 336.6 365.4 402.8 Number of refrigerant circuits Number of capacity steps Power supply V(%)-Ph-Hz 400 (±10%)/3/50 Starting type Direct…
-
Physical Data - RWR 170 to 360
RWR MODELS Cooling capacity (1) kW 160.8 186.5 210.6 263.6 283.7 312.3 Power input (1) kW 45.8 52.6 56.8 73.0 81.7 90.5 Heat rejection kW 205.7 238.4 267.4 336.6 365.4 402.8 Number of refrigerant circuits Number of capacity steps Power supply V(%)-Ph-Hz 400 (±10%)/3/50 Starting type Direct…
-
Electrical Data - RWC/RWR
MODELS UNIT Nominal supply voltage V(%)-Ph-Hz 400(±10%)/3/50 Max. power input kW Nominal current A Max. current FLA A Max. starting current LRA A Max. power input kW 16.4 x Max. current FLA A 28 x 4 Max. starting current LRA A 198 x 4 Crankcase heater W 70 COMPRESSORS Quantity 4 16.4 x 3 + 28.1…
-
Performance Data - RWC 170 to 360
Condenser leaving water temperature (°C) Sizes RWC 170 RWC 200 RWC 240 RWC 280 RWC 320 RWC 360 LWT (°C) Cool. Power Heat Cool. Power Heat Cool. Power Heat Cool. Power Heat Cool. Power Heat cap. input reject. cap. input reject. cap. input reject. cap. input reject. cap. input reject. (kW) (kW) (kW)…
-
Performance Data - RWR 170 to 360
Condensing temperature (°C) Sizes RWR 170 RWR 200 RWR 240 RWR 280 RWR 320 RWR 360 LWT (°C) 162.2 41.0 202.3 154.6 198.9 146.9 49.4 195.6 139.3 53.5 192.2 131.6 55.9 188.2 7 168.7 41.5 209.3 160.8 45.8 205.7 153.0 49.9 202.1 145.1 54.0 198.5 137.2 56.5 194.4 10 178.9 43.1 220.8 170.8 47.2 217.1 162.9…
-
Dimensions - RWC 170 to 360
LEGEND Evaporator water in Evaporator water out Condenser water in Condenser water out Sizes 280-360 A B C D 1-2 DN 100 (4") DN 100 (4") DN 100 (4") DN 100 (4") 3-4 2" female gas 2" female gas 2" 1/2 female gas 2" 1/2 female gas Condenser Manifold Kit (Optional) Water out 4" Victaulic Sensor pocket…
-