u Air Cooled Water Chillers
-
Specifications
The Aqu@Logic air cooled water chillers comprises 10 models covering a nominal cooling capacity range of from 42 to 131 kW. Energy savings all year round Aqu@Logic represents a new generation of innovative water chillers, integrating components using the very latest technological advances. Thanks to…
-
Specifications (continued)
Refrigerant circuit Other standard equipment The refrigerant circuit comprises all the required components such as filter-dryer, sight glass with moisture indicator and thermostatic expansion valve. It also comprises high and low pressure sensors, as well as sensors for inlet and outlet water…
-
ILTC control system
Condensing pressure control is included as standard, thus enabling all Aqu@Logic units to operate between - 10 °C and + 46 °C. Condensing pressure control is provided by an algorithm, automatically managing the fan speeds operation. In partial load or low ambient outdoor temperature conditions…
-
Refrigerant flow diagrams
Models 40 to FH1 FPC CPT DIS P P P T C1 FPE EPT P P EWT 6 T P C2 T LWT components 1 C1/C2 compressors 2 Condenser 3 Filter dryer 4 Sight glass with moisture indicator 5 Expansion valve 6 Plate heat exchanger FS Water inlet/outlet control and safety components CPT Condenser pressure tapping point DIS…
-
Operating limits and correction factors
Ambient air temperature (°C) Operating temperature ranges Standard unit operating range Outlet water temperature (°C) Operating limits (*) Altitude correction factors Temperature min. max Inlet water at start-up °C 10 30 Altitude (m) Cooling capacity correction factors Power consumption correction…
-
Hydraulic circuit water volume
Minimum volume for comfort air conditioning applications sizes Volume * (litres) (*) Volumes calculated for Eurovent operating conditions (air : 35 °C, water 12/7 °C) with a 2.5 l/kW ratio. For other nominal operating conditions, recalculate the minimum volume by multiplying the corresponding…
-
Technical data
AQL sizes Power supply (V/Ph/Hz) 70 80 400/3+N/50 Cooling capacity * kW 42.0 46.5 56.9 67.3 75.4 Total power consumption with pump kW 16.1 19.4 23.9 28.1 30.7 Total power consumption kW 15.4 18.7 22.8 27.0 29.6 2.9 2.6 2.7 2.7 2.7 COP Refrigerant charge Lw sound power levels kg dB(A) Compressors…
-
Technical data (continued)
AQL sizes Power supply (V/Ph/Hz) 120 130 400/3/50 Cooling capacity * kW 86.4 98.0 112.0 122.2 131.0 Compressor power consumption kW 31.0 35.7 39.8 44.4 43.0 Total power consumption kW 43.2 48.4 54.9 60.1 62.0 2.8 2.7 2.8 2.8 3.0 kg dB(A) COP Refrigerant charge Lw sound power levels Compresseurs Type…
-
Technical data (continued)
Protection devices aql sizes Fan thermal protection yes Compressors thermal protection yes Ancillaries / Fan circuit breakers yes Compressors circuit breakers Water pressure differential pressostat Water flow switch yes HP pressostat yes Evaporator antifreeze protection yes HP transducer yes LP…
-
Electrical data
Unit with hydraulic module aql sizes Supply voltage (V / Ph / Hz) Permissible voltage Nominal power consumption Maximum power consumption Nominal current Maximum current Maximum starting current External fuse (aM) Cable section (100 m max.) / 3+N / 50 16.1 20.1 31.0 38.5 19.4 25.3 36.0 46.5 / 3+N /…
-
Performance data
AQL sizes outdoor air temperature (°C) LCWT (°C) Pf Pabs Pf Pabs Pf Pabs Pf Pabs Pf Pabs Pf Pabs Pf Pabs 5 41.9 12.7 40.8 14.0 40.3 14.5 39.5 15.3 36.6 16.7 34.8 17.6 33.0 18.7 6 43.2 12.8 42.0 14.1 41.5 14.6 40.7 15.4 37.7 16.9 35.9 17.8 34.1 18.8 7 44.6 12.8 43.4 14.2 42.8 14.7 42.0 15.5 38.9 17.0…
-
Performance data (continued)
aql sizes outdoor air temperature (°C) LCWT (°C) Pf Pabs Pf Pabs Pf Pabs Pf Pabs Pf Pabs Pf Pabs Pf Pabs 5 87.6 28.3 84.7 30.3 83.4 31.2 81.4 32.5 75.4 35.8 71.7 37.9 68.1 40.2 6 90.2 28.6 87.2 30.7 85.8 31.5 83.8 32.8 77.6 36.2 73.9 38.3 70.1 40.6 7 92.9 28.9 89.8 31.0 88.5 31.8 86.4 33.2 80.0 36.6…
-
Unit external static pressure
Models 40, 50, 60, 70 & kPa 0.00 1.00 2.00 3.00 60 4.00 70 80 5.00 6.00 Water flow (l/s) water flow (l/s) Nominal (1) Minimal (2) Maximal (3) Model 40 2.01 1.34 3.34 Model 50 2.22 1.48 3.70 model 60 2.72 1.81 4.53 Model 70 3.22 2.14 5.36 Model 80 3.60 2.40 6.00 (1) Eurovent conditions, water : 12/7…
-
Heat exchanger water pressure drop
Models 40, 50, 60, 70 & 80 140.00 40 120.00 100.00 kPa 80.00 80 60.00 40.00 20.00 0.00 0.00 1.00 2.00 3.00 4.00 5.00 6.00 Water flow (l/s) Models 90 to 130 1000 kPa Water flow (l/s) Page 15
-
Dimensions - AQL sizes 40 and 50
Front view Side view B 1374 1634 1737 C A D 288 1201 1719 Top view 1155 (*) A B C D 23 Water inlet Ø2" gas Water outlet Ø2" gas Ancillary electric cables entry Power supply cables entry 1559 (*) 1719 (*) Location of 4 anti-vibration mounts. Dimensions in mm. Page 16.5
-
Dimensions - AQL sizes 60, 70 and 80
Front view Side view 1374 B C A D 279 16.5 1201 288 Top view 1155 (*) A B C D 23 2151 Water inlet Ø2" gas Water outlet Ø2" gas Ancillary electric cables entry Power supply cables entry 995.5 (*) 995.5 (*) 2151 (*) Location of 6 anti-vibration mounts. 80 1634 2168 Dimensions in mm. Page 17
-
Dimensions - AQL sizes 90 and 100
1374 C Front view 1634 Side view D 16.5 1201 2523 Side view Top view 1155 (*) 23 B C A 273 A B C D Water inlet Ø2" gas Water outlet Ø2" gas Ancillary electric cables entry Power supply cables entry 80 1181.5 (*) D 1181.5 (*) 80 23 (*) Location of 6 anti-vibration mounts. Dimensions in mm. Page 18
-
Dimensions - AQL sizes 110, 120 and 130
C 1374 Front view 1634 Side view D 16.5 1201 2865 Side view Top view 1155 (*) 23 B 1352.5 (*) 80 23 C A A B C D Water inlet Ø2" gas Water outlet Ø2" gas Ancillary electric cables entry Power supply cables entry 80 1352.5 (*) D (*) Location of 6 anti-vibration mounts. Dimensions in mm. Page 19
-
224 and 294-litre water tank kit (optional)
The optional water tank kit, designed to be installed underneath the Aqu@Logic units, is a complete kit where all the hydraulic and electric elements necessary to the correct startup of the system are provided. This optional water tank kit is completely assembled and tested in factory, and is ready…
-
Dimensions - 224-litre water tank kit for AQL 40 and 50
Side view 16.5 274 82 C 63 563 B 194 200 A Front view 1201 246 83 1559 83 23 1155 23 Top view notes A Water inlet from the system Ø2" GAS M B Water outlet to the chiller Ø2" GAS M C Water filling Ø 1/2" GAS M Dimensions - 294-litre water tank kit for AQL 60 to 80 Side view 16.5 274 82 Front view C…
-
Dimensions - 294-litre water tank kit for AQL 90 and 100
Side view 82 274 16.5 63 563 C B 194 200 A Front view 1201 246 1155 23 Top view 83 notes A Water inlet from the system Ø2" GAS M B Water outlet to the chiller Ø2" GAS M C Water filling Ø 1/2" GAS M 23 2363 83 2529 Dimensions - 294-litre water tank kit for AQL 110 to 130 Side view 82 274 16.5 63 1201…
-
Minimum clearance around the unit
-