Системы нержавеющих труб Uponor INOX
Системы нержавеющих труб Uponor INOX. Техническая документация (февраль 2021).
Загружаем документ…
Текст каталога
-
Uponor INOX
EN Technical information
-
1 System description
The stainless steel press fitting system Uponor INOX is the ideal solution to distribute drinking water, since stainless steel guarantees a high level of hygiene and significant resistance to corrosion. Joints produced in this way are extremely strong, but flexible enough to withstand the stresses…
-
2 Planning/design
2.1 General information 2.2 Fitting the system Corrosion resistance Minimum space allowance for pressing Caution! Avoid chloride-containing insulating materials, sealants or plastic tapes.Use only insulating materials or insulating tubes with a mass fraction of max. 0.05% of watersoluble chloride…
-
Chased pipe
There are two types of collars: • fixed, which lock pipes firmly (A) • sliding, wich allow axial movement (B) A A B SD0000096 A pipe with no changes of direction or expansion compensators must have only one fixed collar (A). In case of long pipes place this collar towards the centre of the section…
-
Pipe expansion
Compensating expansion Metal pipes can expand or shrink in length depending on material and temperature, which must be considered when planning the installation. U-shaped compensator Determin the compensation length with an U-shaped compensator for the estimated expansion. Follow these three rules…
-
Z-shaped compensator
-
3 Prepare for installation
3.1 Transport, storage and withdrawl Caution! Take suitable precautions to avoid damage and contamination through dirt and humidity during the transport and storage of pipes and fittings. Pay attention to temperature variations that may cause condensation. Caution! Avoid putting heavy materials on…
-
4 Installation
4.3 Leak test 4.1 General information Caution! Note This is an electrically conductive system! Legal notice: Potential equalisational parts of metal water pipe must be included in the main potential equalisation of a building. This work must be carried out by trained personel. Pressure tests are…
-
4.4 Flushing of Uponor drinking
water distribution Note Uponor tap water lines must be flushed with the local supply pressure and in accordance with DIN EN 806-4, Section 6.2.2, unless a different flushing procedure is contractually agreed or required. The tap water used for flushing must be filtered (filter according to DIN EN…
-
5 Technical data
5.1 Uponor INOX Zeta-values DN 12 DN 15 DN 20 DN 25 DN 32 DN 40 DN 50 Pipe outer diameter [mm] Branch run at flow split TA 1.2 1.2 1.2 1.2 1.2 1.2 1.2 Branch run at flow split TD 0.2 0.2 0.2 0.1 0.1 0.1 0.1 Branch reverse run at flow split TG 1.1 1.1 1.1 1.1 1.1 1.1 1.2 Branch reverse run at flow…
-
Nominal size
-
таблицы и схемы — в просмотре
-
5.3 Uponor INOX Pipes
Description Value Material Austenitic stainless steel 1.4404 (X2CrNiMo 17-12-2, AISI 316L) Tensile strength 490 - 690 N/mm² Yield resistance ≥ 190 N/mm² Longitudinal lengthening ≥ 40 % Bending radius ≥ 3.5 x d (≤ 28 mm) Pipe roughness 0.0015 mm Thermal conductivity 15 W/(m x K) Linear expansion…
-
Uponor GmbH
Industriestraße 56, D-97437 Hassfurt, Germany 1119962 v1_02_2021_EN Production: Uponor/DCO Uponor reserves the right to make changes, without prior notification, to the specification of incorporated components in line with its policy of continuous improvement and development. www.uponor.com