a c e b oil er Re www.tica.pro 90°C A on s hot water pp lic ab le t o i dit various con Technology license of MAYEKAWA (Japan) NATURAL REFRIGERANT CO2 HEAT PUMP HIGH TEMPERATURE HOT WATER UNIT 5.0 Highest energy efficiency ratio 80kW Largest heating capacity Japanese original design
-
Established in 1991
TICA is a professional enterprise specialized in R&D, manufacturing, sales and services of environment cleaning and thermal energy utilization. TICA is a national high-tech enterprise, a single leading enterprise cultivated by the Ministry of Industry and Information Technology, a national brand…
-
NATURAL REFRIGERANT CO 2 HEAT
PUMP HIGH TEMPERATURE HOT WATER UNIT Contents Product Overview 2 Product Features 3 Comparison of OPEX 5 Core Technologies 6 Typical Applications 9 Specifications 12 Use Conditions 13 Performance Curve under Variable Operating Conditions 14 Appearance 16 Installation Diagram 17 Wiring and Piping 18…
-
90°C hot water
Product Overview TICA heat pump high temperature hot water unit (hereinafter referred to as “the unit”) is manufactured under license by MAYEKAWA JAPAN. The unit adopts the natural working medium CO2 as the refrigerant, and boasts a water outlet temperature of up to 90°C, unrivaled in the industry.…
-
HOT WATER UNIT
Product Features Providing 90°C hot water Optimum alternative for small boilers Adopting the natural working medium CO 2 as the refrigerant, the unit heats up water by absorbing heat from the air through a transcritical cycle. The water outlet temperature can reach as high as 90°C, making it a…
-
All year round hot water
supply Cooling lgP No electric heating compensation required in low temperature condition 3 T=const Throttling With CO 2 transcritical cycle, the unit can provide 90°C hot water all year round without electric heating compensation. The energy efficiency is as high as 3.1 even at 5°C ambient…
-
HOT WATER UNIT
Comparison of OPEX Efficient heating performance to reduce OPEX Taking a user in eastern China who uses 20 tons of 90°C hot water per day as an example, if the tap water inlet temperature is 20°C, a heat consumption of 1,400,000 kcal (5,880,000 kJ) is required for heating 20 tons of water from 20°C…
-
NATURAL REFRIGERANT CO 2 HEAT
PUMP HIGH TEMPERATURE HOT WATER UNIT Core Technologies Founded in 1924, MAYEKAWA JAPAN is mainly engaged in refrigeration engineering and compressor manufacturing, and has been leading the world in the R&D, manufacturing and application of CO2 compressors. The heat pump hot water unit manufactured…
-
Re
-
Efficient air-cooled heat exchanger
Independent R&D by MAYEKAWA, efficient and safe The high-efficiency air-cooled heat exchanger independently developed by MAYEKAWA adopts copper pipes for refrigerant and water flow. These specially-shaped pipes are closely connected to increase the heat exchange efficiency and operating safety.…
-
HOT WATER UNIT
Typical Applications Sanitary hot water for luxury hotels Industrial hot water for food, slaughtering, electroplating, rubber, leather, and chemical industries The heat pump water heaters using chemical synthetic refrigerants (R22, R410A, etc.) have an actual water supply temperature lower than…
-
KOA Corporation Nishiyama Factory In the production process of electronic component manufacturing plants, a large amount of pure water is required for cleaning products, while making pure water needs to increase the water refill temperature, which consumes a large amount of heat. Introduction to the…
-
Hokuriku MEYITO Corporation Hakusan Factory Unattended operation & high efficiency Introduction to the system: 1 set of heat pump unit; heating capacity: 93 kW Benefits to users During the processing of dairy products, a large amount of hot water is required to clean and sterilize the raw materials.…
-
HOT WATER UNIT
Specifications Model TCAH200HH Type Natural Refrigerant CO2 Heat Pump Hot Water Unit Three-phase AC 380 V 50 Hz Power supply Heating capacity (kW) 80 Power input (kW) 15.96 Water flow (m3/h) 1.38 Heating capacity (kW) 79 Power input (kW) 17.35 Water flow (m3/h) 0.92 Standard 65°C water outlet…
-
HOT WATER UNIT
Water Quality Standards Use Conditions The direct water inlet of the heat pump and the water refill through the hot water storage tank are all required to meet the water quality standards in the table below. Whether it is municipal tap water or other water sources, the water quality shall be…
-
Performance Curve under
Variable Operating Conditions NATURAL REFRIGERANT CO 2 HEAT PUMP HIGH TEMPERATURE HOT WATER UNIT 65°C supply water Standard mode Power consumption (RSO1N) Power Consumption (kW) Heating capacity (kW) Heating capacity 120 Water inlet 5°C 110 Water inlet 9°C Water inlet 17°C Water inlet 24°C 100 Water…
-
90°C supply water
Standard mode Power consumption (RSO1N) Power consumption (kW) Heating capacity (kW) Heating capacity 110 Water inlet 5°C Water inlet 9°C 100 Water inlet 17°C Water inlet 24°C Water inlet 29°C 90 Water inlet 40°C Water inlet 60°C 80 Water inlet 65°C Frosting period Winter 70 Intermediate period…
-
HOT WATER UNIT
Appearance Water inlet (Rc3/4) Connection hole Water return (Rc3/4) Water outlet (Rc3/4) Drainage outlet (Rc1 1/2) Front view Side view Installation space >1000 Maintenance space Pipe 16 www.tica.pro Rear view
-
HOT WATER UNIT
Installation Diagram Hoisting Diagram Steel rope Steel rope Support Support Steel rope Use cloth or other protective pads to avoid scratch Steel rope Hoisting requirements: 1. The machine shall be well-packaged during the transportation from the factory to the site and before hoisting; 2. Handle the…
-
HOT WATER UNIT
Wiring and Piping Wiring Wiring requirements Power supply wiring Control wiring Power source specification Power capacity Startup mode Maximum current Dimension of main power cable I/O wiring dimension and type Three-phase AC 380 V 50 Hz 42.8 (kVA) Variable-frequency startup (compressor, fan) 65 (A)…
-
HOT WATER UNIT
Typical System Principle Application of Sanitary Hot Water Water outlet Return water Replenish water From the water use site Water outlet Return water Replenish water To t h e w a t e r use site Heat insulation water tank Replenish water From water softening device Notes 1. Stainless steel pipes are…
-
HOT WATER UNIT
Operation & Maintenance Components Check items (criterion) Unit Check whether the heat pump surface is rusted, damaged, or smudged. Check whether the surface is rusted or damaged. Compressor Check whether there is abnormal sound or vibration during operation. Measure whether the insulation…
-