TECNAIR LV
“C” series Close control air conditioners with direct expansion coil with chilled water coil
-
Main features
Designed for electronic and comfort applications Minimum foot print and front maintenance “C” series close control air conditioners are available in the following versions: Space inside technological rooms is always a precious thing. This is why Tecnair LV's close control air conditioners are…
-
Silent functioning, energy efficiency and ecological impact
• The scroll compressors of “C” series air conditioners with direct expansion coil are more silent than the alternative ones. • The scroll compressors have energy consumptions much lower than the others, so limiting the ecological impact. • The cold coils of the downflow units (UC), both in chilled…
-
Features and performance
Microprocessor regulation The μAC microprocessor allows managing all the typical air-conditioning functions: cooling, heating, humidification, dehumidification, and filtering, very accurately and timely. It assures a regular and optimised functioning as to both performance and consumption; it also…
-
One or two completely independent
compressors • Sizes 21, 31, 41, 51, 71, 81, 101, 131 and 151 are equipped with one scroll compressor connected with a single cooling circuit. • Sizes 72, 102, 142, 162, 202, 262 e 302 are equipped with two scroll compressors and two independent cooling circuits, which assure the utmost working…
-
Fan section
Standard fans The standard fan section is made up by one or more backward curved, free running impeller, radial fans (plug fan) with single speed motors which offer a particularly low noise level as well as a high efficiency. The free running impeller assures a very high efficiency and a easy…
-
Special versions
“Water to air free cooling”: using renewable energy sources “Two seasons”, using excess of energy or for the maximum security of the system. OCW…/FC, UCW…/FC air conditioners are equipped with a “Free cooling” system consisting of an additional chilledwater cooling coil integrated in the aluminium…
-
Fittings
• Electronic immersed-electrode modulating humidifier and dehumidification control. • Two row hot water heating/reheating coil with throttling three-way regulating valve. • One or two steps low thermal inertia heater/rehater. • Welded plate built in water cooled condensers. • Pressostatic two-way…
-
Upflow air conditioners
technical characteristics OCA: direct expansion with air or water cooled condensers and upflow air discharge 71-H 81-H 101-L 101-H 131-L 131-H 151-L 151-H Total cooling cap.:kW 21.4 23.3 28.3 32.5 38.8 43.3 42.9 47.3 Sens cooling cap.:kW 21.4 21.7 23.9 30.7 33.6 40.5 35.3 42.1 Airflow: m3/h 6910…
-
downflow air conditioners