TECHNICAL CATALOGUE HEAT PUMPS 2025/2026 · S-THERM HEAT PUMPS · WATER HEATERS · BUFFER TANKS · DHW TANKS · ACCESSORIES AIR CONDITIONING
-
CONTENT S-THERM ONTARIO - MONOBLOC 4TH GENERATION 2 - MONOBLOC 5TH GENERATION 9 - SPLIT 19 - HYDROBOX 27 - ALL IN ONE 37 S-THERM YUKON - MONOBLOC R32 47 - MONOBLOC R290 55 - COMMERCIAL SERIES 63 - COMMERCIAL SERIES R290 67 - SPLIT 71 - HYDROBOX 75 - ALL IN ONE 77 - SPLIT WATER HEATERS 124 - MONOBLOC…
-
MODEL
Suitable for building heat loss Capacity*1 Power Input*1 SMH-40IRB SMH-60IRB SMH-80IRB SMH-100IRB2 SMH-100IRB2-3 3 - 5 kW 4 - 6 kW 6 - 8 kW 7 - 9,5 kW 7 - 9,5 kW 8,8 Cooling (floor heating) kW 3,8 5,8 6,8 8,8 Heating (floor heating) kW 4 6 7,5 10 10 Cooling (floor heating) kW 0,82 1,32 1,55 1,96…
-
MODEL
Suitable for building heat loss Capacity*1 Power Input*1 SMH-120IRB2-3 SMH-140IRB2-3 SMH-160IRB2-3 SMH-120IRB2 SMH-140IRB2 10 - 12 kW 11 - 14 kW 12 - 15 kW 10 - 12 kW 11 - 14 kW 12,5 Cooling (floor heating) kW 11 12,5 14,5 11 Heating (floor heating) kW 12 14 15,5 12 14 Cooling (floor heating) kW…
-
MODEL
SMH-160IRB2 Suitable for building heat loss Capacity*1 Power Input*1 12 - 15 kW Cooling (floor heating) kW 14,5 Heating (floor heating) kW 15,5 Cooling (floor heating) kW 3,82 Heating (floor heating) kW 3,6 EER*1 (floor cooling) - 4 COP*1 (floor heating) - 4,35 Capacity*2 Power Input*2 Cooling (fan…
-
SMH-100IRB2, SMH-120IRB2, SMH-140IRB2, SMH-160IRB2
SMH-100IRB2-3, SMH-120IRB2-3, SMH-140IRB2-3, SMH-160IRB2-3 SMH-100IRB, SMH-160IRB SMH-100IRB-3 5
-
SMH-40IRB, SMH-60IRB, SMH-80IRB
-
2-way valve
Other heat source 1-phase contactor 3-way valve Additional water pump 7 Gate controller
-
3-phase contactor
Controller connection External thermostat T-sensor for e-heater Room temperature sensor DHW sensor Attention: You can find a detailed wiring diagram in the installation manual. 8
-
MODEL
Suitable for building heat loss Capacity*1 SMH-40IRBC SMH-60IRBC SMH-80IRBC SMH-100IRBC2 3 - 5 kW 4 - 6 kW 6 - 8 kW 7 - 9,5 kW Cooling (floor cooling) kW 5 6,5 8,3 10,2 Heating (floor heating) kW 5 6 8,2 10,2 Cooling (floor cooling) kW 0,962 1,275 1,56 2 Heating (floor heating) kW 0,926 1,111 1,54…
-
MODEL
Suitable for building heat loss Capacity*1 SMH-100IRBC2-3 SMH-120IRBC2-3 SMH-140IRBC2-3 SMH-160IRBC2-3 7 - 9,5 kW 10 - 12 kW 11 - 14 kW 12 - 15 kW Cooling (floor cooling) kW 10,2 12 13,9 15,4 Heating (floor heating) kW 10,2 12 14,2 15,7 Cooling (floor cooling) kW 2,13 2,61 3,32 4,05 Heating (floor…
-
SMH-40IRBC
-
SMH-120IRBC2-3/SMH5-120B(C)-3
-
2-way valve
3-way valve Other heat source Gate controller External thermostat Additional water pump Controller connection 13
-
T-sensor for Other thermal
Room temperature sensor DHW sensor Attention: You can find a detailed wiring diagram in the installation manual. 14
-
MODEL
Suitable for building heat loss Capacity*1 Power Input*1 GSH-40ERB2 GSH-60ERB2 GSH-80ERB2 GSH-100ERB2 3 - 5 kW 4 - 6 kW 6 - 8 kW 7 - 9,5 kW 9,35 Cooling (floor cooling) kW 3,9 5,8 7,7 Heating (floor heating) kW Cooling (floor cooling) kW 0,68 1,14 1,72 2,36 Heating (floor heating) kW 0,77 1,23 1,61…
-
MODEL
Suitable for building heat loss Capacity*1 Power Input*1 GSH-40ERB GSH-60ERB GSH-80ERB GSH-100ERB GSH-120ERB 3 - 5 kW 4 - 6 kW 6 - 8 kW 7 - 9,5 kW 10 - 12 kW 11 Cooling (floor cooling) kW 3,8 5,8 7 8,5 Heating (floor heating) kW 9,5 12 Cooling (floor cooling) kW 0,8 1,32 1,75 2,24 2,5 Heating (floor…
-
MODEL
GSH-140ERB GSH-160ERB GSH-80ERB-3 GSH-100ERB-3 GSH-120ERB-3 Suitable for building heat loss 11 - 14 kW 12 - 15 kW 6 - 8 kW 7 - 9,5 kW 10 - 12 kW 11 Capacity*1 Power Input*1 Cooling (floor cooling) kW 12,6 13 8,5 10 Heating (floor heating) kW 14 15,5 Cooling (floor cooling) kW 3,41 3,6 1,74 2,33 2,5…
-
MODEL
Suitable for building heat loss Capacity*1 GSH-140ERB-3 GSH-160ERB-3 11 - 14 kW 12 - 15 kW Cooling (floor cooling) kW 12,6 13 Heating (floor heating) kW 14 15,5 Cooling (floor cooling) kW 3,41 3,6 Heating (floor heating) kW 2,98 3,44 EER*1 (floor cooling) - 3,7 3,6 COP*1 (floor heating) - 4,7 4,51…
-
GSH-40ERB2, GSH-60ERB2
GSH-40ERB, GSH-60ERB 23
-
GSH-80ERB-3, GSH-100ERB-3
GSH-80ERB, GSH-100ERB, GSH-80ERB2, GSH-100ERB2 24
-
GSH-80ERB-3, GSH-100ERB-3
GSH-80ERB, GSH-100ERB, GSH-80ERB2, GSH-100ERB2 25
-
GSH-120ERB-3, GSH-140ERB-3, GSH-160ERB-3
GSH-120ERB, GSH-140ERB, GSH-160ERB 26
-
MODEL
GSH-40IRB Power supply Connecting pipe (refrigerant) Gas Liquid Connecting pipe (water) Inlet Outlet Safety valve Leaving water temperature GSH-60IRB GSH-80IRB V/Ph/Hz 1/2" inch Heating GSH-120IRB 5/8" 1/4" (vnější) 1" (outer) inch 3 bar Cooling GSH-100IRB 220-240/1/50 7-25 °C 20-60 MAIN COMPONENTS…
-
MODEL
GSH-140IRB Power supply Connecting pipe (refrigerant) Gas Liquid Connecting pipe (water) Inlet Outlet Safety valve Leaving water temperature GSH-160IRB V/Ph/Hz Heating GSH-100IRB-3 5/8" inch GSH-120IRB-3 380-415/3/50 1/2" 5/8" 1/4" 1"1"(vnější) (outer) inch 3 bar Cooling GSH-80IRB-3 220-240/1/50…
-
GSH-40IRB, GSH-60IRB, GSH-80IRB, GSH-100IRB, GSH-120IRB
GSH-140IRB, GSH-160IRB, GSH-80IRB-3, GSH-100IRB-3, GSH-120IRB-3 GSH-140IRB-3, GSH-160IRB-3 WATER IN DRAIN PIPE GAS LIQUID DWH HEATING 29
-
Additional water pump control (PWM)
for 1-phase units 4-10 kW 2-way valve for 1-phase units 4-6 kW Additional water pump control (PWM) for 3-phase units 8&10 kW and all units 12-16 kW 2-way valve for 3-phase units 8&10 kW and all units 12-16 kW Thermostat for 1-phase units 4-10 kW Gate contoller for 1-phase units 4-10 kW Thermostat…
-
ODU-IDU communication for one phase units (ODU GSH-40-60ERB2)
ODU-IDU communication (ODU GSH-80-100ERB(2), GSH-120-140-160ERB) ODU-IDU communication (ODU GSH-80-160ERB-3) ODU-IDU communication (ODU GSH-40-60ERB) 31
-
Other for 3-phase units 8&10
kW and all units 12-16 kW Other thermal for 1-phase units 4-10 kW Room temperature sensor DHW sensor Attention: You can find a detailed wiring diagram in the installation manual. 32
-
MODEL
GSH-40TRB2 Power supply Connecting pipe (refrigerant) Gas Liquid Connecting pipe (water) Inlet Outlet Safety valve Leaving water temperature GSH-60TRB2 GSH-80TRB2 V/Ph/Hz 1/2" inch Heating GSH-120TRB2 5/8" 1/4" 1" (vnější) 1" (outer) inch 3 bar Cooling GSH-100TRB2 220-240/1/50 7-25 °C 20-60 MAIN…
-
MODEL
GSH-140TRB2 Power supply Connecting pipe (refrigerant) V/Ph/Hz Gas Liquid Connecting pipe (water) Inlet Outlet Safety valve Leaving water temperature GSH-160TRB2 Heating GSH-100TRB2-3 5/8" inch GSH-120TRB2-3 380-415/3/50 1/2" 5/8" 1/4" 1" (outer) (vnější) inch 3 bar Cooling GSH-80TRB2-3 220-240/1/50…
-
GSH-40TRB2, GSH-60TRB2, GSH-80TRB2, GSH-100TRB2, GSH-120TRB2
GSH-140TRB2, GSH-160TRB2, GSH-80TRB2-3, GSH-100TRB2-3, GSH-120TRB2-3 GSH-140TRB2-3, GSH-160TRB2-3 LIQUID 1/4 GAS 4-10 kW - 1 2 12-16 kW - 5 8 DWH TAP WATER HEATING WATER RETURN HEATING WATER OUTPUT
-
ALL IN ONE
Additional heat pump (PWM signal) 2-way valve Gate controller Additional heat source External thermostat ODU-IDU (ODU GSH-40-60ERB2) ODU-IDU communication (ODU GSH-80-100ERB(2), GSH-120-140-160ERB) 40
-
ALL IN ONE
ODU-IDU communication (ODU GSH-80-160ERB-3) ODU-IDU communication (ODU GSH-40-60ERB) Room temperature sensor Attention: You can find a detailed wiring diagram in the installation manual. 41
-
3WV - three way valve
-
таблицы и схемы — в просмотре
-
3WV - three way valve
-
таблицы и схемы — в просмотре
-
OUTDOOR UNIT BASE
ase for outdoor and monobloc units ase for outdoor and monobloc units Pedestals for outdoor units Outdoor and monobloc unit mŽĚĞů '^,ͲϰϬZ͕'^,ͲϰϬZϮ͕'^,ͲϲϬZ͕'^,ͲϲϬZϮ Outdoor and monobloc unit mŽĚĞů '^,ͲϴϬZ͕'^,ͲϴϬZϮ͕'^,ͲϴϬZͲϯ͕'^,ͲϭϬϬZ͕'^,ͲϭϬϬZϮ͕'^,ͲϭϬϬZͲϯ '^,ͲϰϬZ͕'^,ͲϰϬZϮ͕'^,ͲϲϬZ͕'^,ͲϲϬZϮ…
-
MODEL
Power supply Heating (A7/W35) SMHM-80B/3 SMHM-100B/3 4- 6 kW 6 - 8 kW 7 - 9,5 kW 220-240/1/50 10 - 12 kW 380-415/3/50 Capacity kW 4,20 6,35 8,40 10,0 12,1 kW 0,82 1,28 1,63 2,02 2,44 5,10 4,95 5,15 4,95 4,95 Capacity kW 4,5 6,5 8,3 9,9 12 Rated input kW 0,82 1,35 1,64 2,18 3,04 5,5 4,8 5,05 4,55…
-
MODEL
Power supply Heating (A7/W35) SMHM-40B SMHM-60B SMHM-80B 12 - 15 kW 3 - 5 kW 4- 6 kW 6 - 8 kW 220-240/1/50 Capacity kW 14,5 15,9 4,20 6,35 8,40 Rated input kW 3,15 3,53 0,82 1,28 1,63 4,60 4,50 5,10 4,95 5,15 Capacity kW 13,50 14,2 4,5 6,5 8,3 Rated input kW 3,74 3,94 0,82 1,35 1,64 3,61 3,61 5,5…
-
MODEL
Power supply Heating (A7/W35) SMHM-140B SMHM-160B 10 - 12 kW 12 - 15 kW 12 - 15 kW 220-240/1/50 10 - 12 kW 380-415/3/50 Capacity kW 10,0 12,1 14,5 15,9 12,1 kW 2,02 2,44 3,15 3,53 2,44 4,95 4,95 4,60 4,50 4,95 Capacity kW 9,9 12 13,50 14,2 12 Rated input kW 2,18 3,04 3,74 3,94 3,04 4,55 3,95 3,61…
-
MODEL
Power supply Heating (A7/W35) 12 - 15 kW 380-415/3/50 Capacity kW 14,5 15,9 Rated input kW 3,15 3,53 4,60 4,50 Capacity kW 13,50 14,2 Rated input kW 3,74 3,94 EER Seasonal space heating energy efficiency class SMHM-160B-3 11 - 14 kW V/Ph/Hz COP Cooling (A35/W18) SMHM-140B-3 3,61 3,61 Water outlet at…
-
MONOBLOC 18-30 KW R32
MODEL Suitable for building heat loss Power supply Heating (A7/W35) SMHM-260B-3 SMHM-300B-3 18 - 22 kW 22 - 26 kW 26 - 30 kW 380-415/3/50 Capacity kW 30,1 Rated input kW 3,83 5 6,37 7,69 4,7 4,4 4,08 3,91 Capacity kW 18,5 Rated input kW 3,89 5 6,27 7,75 4,75 4,6 4,3 4 EER Seasonal space heating…
-
таблицы и схемы — в просмотре
-
MODEL
Suitable for building heat loss Power supply Heating (A7/W35) SMHM-350P-3 SMHM-400P-3 26 - 30 kW 30 - 35 kW 35-39 kW 380-415/3/50 Capacity kW Rated input kW 5,45 6,67 8,4 9,75 4,77 4,5 4,17 Capacity kW Rated input kW EER Seasonal space heating energy efficiency class 5,6 6,8 8,5 9,85 4,64 4,41 4,12…
-
SMHM-260P-3
-
MODE NAME
Suitable for building heat loss Power supply Heating (A7/W35) SMHM-80P/3 SMHM-100P/3 4 - 6 kW 6 - 8 kW 7 - 9,5 kW 220-240/1/50 kW 4,5 6,2 8,40 10,0 12 kW 0,874 1,26 1,68 2,12 2,5 4,8 5,15 4,9 5 4,7 Capacity kW 4,5 6,5 8,3 10 12 Rated input kW 0,81 1,27 1,61 2,1 2,66 5,5 5,1 5,15 4,75 4,5 Water…
-
MODE NAME
Suitable for building heat loss Power supply Heating (A7/W35) SMHM-40P SMHM-60P SMHM-80P 12 - 15 kW 3 - 5 kW 4 - 6 kW 6 - 8 kW 380-415/3/50 220-240/1/50 Capacity kW 14 15 4,5 6,2 8,40 Rated input kW 3,11 3,4 0,874 1,26 1,68 4,5 4,4 5,15 4,9 5 Capacity kW 14 16 4,5 6,5 8,3 Rated input kW 3,33 4,1…
-
MODE NAME
SMHM-100P SMHM-120P SMHM-140P SMHM-160P Suitable for building heat loss 7 - 9,5 kW 10 - 12 kW 11 - 14 kW 12 - 15 kW Power supply Heating (A7/W35) V/Ph/Hz Capacity kW kW 2,12 2,5 3,11 3,4 2,5 4,8 4,7 4,8 4,5 4,4 Capacity kW Rated input kW 2,1 2,66 3,33 4,1 2,66 4,75 4,5 4,2 3,9 4,5 EER Seasonal space…
-
MODE NAME
Suitable for building heat loss Power supply Heating (A7/W35) 12 - 15 kW 380-415/3/50 Capacity kW 14 15 Rated input kW 3,11 3,4 4,5 4,4 Capacity kW 14 16 Rated input kW 3,33 4,1 EER Seasonal space heating energy efficiency class SMHM-160P-3 11 - 14 kW V/Ph/Hz COP Cooling (A35/W18) SMHM-140P-3 4,2…
-
MODEL
SMHM-650B-3 Power supply Cooling (A35W7) Heating (A7W45) Heating (A7W35) Compressor Water side heat exchanger Refrigerant SMHM-750B-3 SMHM-750BH-3 SMHM-1100B-3 380-415/3/50 Capacity kW 57 56,7 70 69,29 100 Input kW 19 19,8 26,80 28,26 32,8 EER - 3 2,86 2,61 2,45 3,05 SEER - 5,00 4,92 5,00 4,85 4,80…
-
MODEL
SMHM-1100BH-3 Power supply Cooling (A35W7) Heating (A7W45) Heating (A7W35) Compressor Water side heat exchanger Refrigerant SMHM-1400BH-3 380-415/3/50 Capacity kW 99,3 130 129,29 Input kW 34,1 50 52,01 EER - 2,91 2,60 2,49 SEER - 4,78 4,80 4,77 Capacity kW 110,7 140 140,94 Input kW 31,2 44,73 47,10…
-
APPEARANCE AND DIMENSIONS OF OUTDOOR UNIT
-
MODEL
SMHM-500P-3 Power supply Cooling (A35W7) Heating (A7W45) Heating (A7W35) Compressor Water side heat exchanger kW Input kW 15,15 20 23,21 EER - 3 3,00 2,80 SEER - 4,85 4,80 4,70 Capacity kW Input kW 13,15 17,04 20,89 3,35 COP - 3,80 3,52 Capacity kW Input kW 10,63 13,95 17,5 COP - 4,70 4,30 4,00 SCOP…
-
MODEL
SMHM-500PH-3 Power supply Cooling (A35W7) Heating (A7W45) Heating (A7W35) Compressor Water side heat exchanger kW Input kW 15,15 20 23,21 EER - 3,3 3 2,8 SEER - 4,85 4,8 4,7 Capacity kW Input kW 13,16 17,05 20,9 3,35 COP - 3,8 3,52 Capacity kW Input kW 10,64 13,95 17,5 COP - 4,7 4,3 4 SCOP (W35…
-
APPEARANCE AND DIMENSIONS OF OUTDOOR UNIT
-
MODEL
MSH-40EB MSH-60EB MSH-80EB MSH-100EB Suitable for building heat loss 3 - 5 kW 4 - 6 kW 6 - 8 kW 7 - 9,5 kW Compatible hydronic box MSH-60IB MSH-60IB-3 Power supply Heating (A7/W35) 220-240/1/50 V/Ph/Hz kW 4,25 6,20 8,30 10,0 12,1 Rated input kW 0,82 1,24 1,60 2,00 2,44 5,20 5,00 5,20 5,00 4,95…
-
MODEL
MSH-140EB MSH-160EB MSH-120EB-3 MSH-140EB-3 MSH-160EB-3 Suitable for building heat loss 11 - 14 kW 12 - 15 kW 10 - 12 kW 11 - 14 kW 12 - 15 kW Compatible hydronic box MSH-160IB MSH-160IB/3 MSH-160IB-3/9 Power supply Heating (A7/W35) 220-240/1/50 V/Ph/Hz 380-415/3/50 Capacity kW 14,5 16,0 12,1 14,5…
-
SPLIT - INDOOR HYDROBOX UNIT MODEL MSH-60IB/3 MSH-100IB/3 MSH-100IB-3/9 MSH-160IB/3 MSH-160IB-3/9 Compatible Outdoor unit model MSH-40EB MSH-60EB MSH-80EB MSH-100EB MSH-80EB MSH-100EB MSH-120EB MSH-140EB MSH-160EB MSH-120EB-3 MSH-140EB-3 MSH-160EB-3 Topení and a Chlazení Heating Cooling Function…
-
SPLIT - INDOOR UNITS ALL IN ONE MODEL Compatible Outdoor unit model MSH-190TB/3 MSH-190TB-3/9 MSH-240TBL/3 MSH-240TB-3/9 MSH-40EB MSH-60EB MSH-80EB MSH-100EB MSH-40EB MSH-60EB MSH-80EB MSH-100EB MSH-120EB-3 MSH-140EB-3 MSH-160EB-3 Function Heating and Cooling Setting water temperature range Cooling…
-
MSH-240TBL/3, MSH-240TB-3/9, MSH-190TB-3/9, MSH-190TB/3
-
MSH-240TBL/3, MSH-240TB-3/9, MSH-190TB-3/9, MSH-190TB/3
HEATING WATER OUTPUT 1" HEATING WATER RETURN 1" TAP WATER 3/4" DWH CIRCULATION 3/4" DWH 3/4" GAS 5/8" LIQUID 3/8" M25x1,5 300 MSH-240TBL/3 79
-
R32
Internal backup heater Additional antifreeze tape Cascade communication Solar external input AHS (Additional heat source) SV1 (3-way valve for switching DHW and heating) SV2 (3-way valve for spliting heating and cooling part of system) SV3 (Mixing valve for zone 2) Water pump for zone 2 TBH…
-
R32
External Thermostat 24V (for two zones) External thermostat 230V (for two zones) External thermostat 24V (one zone) External thermostat 230V (one zone) External thermostat 24V (heating x cooling) External thermostat 230V (heating x cooling) External Thermostat 24 V connection terminal External…
-
IBH (Internal backup heater) 3 kW
IBH (Internal backup heater) 9 kW External thermostat (cooling x heating) SV1 (3-way valve for switching DHW and heating) Cascade communication 82
-
AHS (Additional heat source)
SV2 (3-way valve for spliting heating and cooling part of system) Solar external input SV3 (Mixing valve for zone 2) 83
-
Wired controller
TBH (E-heater inside DHW tank) Water pump for zone 2 84
-
DHW circulator pump
External Thermostat (for two zones) External thermostat (one zone) External water pump for zone 1 85
-
Solar water pump
Controller cabel type Sensors resistance Wiring for contactors and thermostats Output signal Alarm/Defrost Remote control 86
-
1 phase connection of main power supply and power
supply of e-heater 3 phase connection of main power supply and power supply of e-heater E-heater power supply 87
-
Electric connection
for 4-6 kW units Electric connection for 8-16 kW units Smart grid signal Connection of 4-6 kW units Connection of 8-16 kW units Attention: You can find a detailed wiring diagram in the installation manual 88
-
IBH (Internal backup heater)
External thermostat (cooling x heating) Cascade communication SV1 (3-way valve for switching DHW and heating) SV2 (3-way valve for spliting heating and cooling part of system) 89
-
Solar external input
AHS (Additional heat source) Wired controller 90
-
SV3 (Mixing valve for zone 2)
TBH (E-heater inside DHW tank) Water pump for zone 2 DHW circulator pump 91
-
External Thermostat (for two zones)
External water pump for zone 1 External thermostat (one zone) Controller cabel type 92
-
Solar water pump
Sensors resistance Wiring for contactors and thermostats Remote control Output signal Alarm/Defrost 93
-
Main power supply
Electric connection Connection Smart grid signal Attention: You can find a detailed wiring diagram in the installation manual. 94
-
YUKON SERIES - CASCADE DIMENSION
Recommended common pipe diameter DN at medium and short distances (up to 7 m) YUKON Number of units in cascade Yukon 12/14/16 kW Yukon mono 18/22/26/30/35/40 kW Recommended common pipe diameter DN at long distances (over 7 m) YUKON Number of units in cascade Yukon 12/14/16 kW Yukon mono…
-
MF
-
3WV - three way valve
-
таблицы и схемы — в просмотре
-
3WV - three way valve
-
таблицы и схемы — в просмотре
-
Base for outdoor
-
SPLIT WATER HEATERS MODEL Twater intlet 15°C Twater outlet 55°C T ambient 20°C SWH-35ERA2 Nominal heating power kW 3,5 (1,8-3,7) Nominal rated input kW 0,83(0,36-0,91) COP °C 4,1 Domestic hot water profile - L COP for DHW (A7/W10) - 3,08 Energy class - A+ Water heating effiency % ≤130 Annual…
-
SWH-35ERA2+SWH-200DE Insulation water tank Hot water outlet pipe Hot water supply point 1 Hot water supply point 2 Hot water supply point 3 Hot water supply point 4 Wired controller Temperature sensor Outdoor unit Refrigerant pipe or Temperature sensor Horizontal structure Cold water Power cord Cold…
-
MONOBLOC WATER HEATERS MODEL SWH-190IRE2 SWH-190IRES2 Mode SWH-300IRE2 SWH-300IRES2 Hybrid/E-heater Operating temperature range (Hybrid) °C -7 ~ 43 Operating temperature range (E-heater) °C -20 ~ 43 Output water temperature Power supply °C 38 ~ 70 V/Ph/Hz 220-240 / 1 / 50 Max. current A 9,1 9,8 Max.…
-
SWH-190IRE2, SWH-190IRES2 Prostor kompresoru 1 6 Provozní prostory 11 Solární výstup 3/4” F (pouze 190S) Compressor 2 1 Elektrický panelcompartment Functional spaces 7 6 Anoda Solar outletteplé 3/4” užitkové F (only 190S) 1211 Recirkulace vody (pouze 190S) Electric panel 3 2 Klávesnice jednotky…
-
SWH-300IRE2, SWH-300IRES2 1 Compressor compartment 6 Functional spaces 11 Solar outlet 3/4” F (pouze 300S) 2 1 Electric panel Prostor kompresoru 7 6 Anode prostory Provozní 12 11 Domestic hot water (only 300S) Solární výstup 3/4” Frecirculation (pouze 300S) 3 2 Unit keypad Elektrický panel 8 7 Water…
-
SWH-190IRE2, SWH-300IRE2 tive plumbing diagram ystem components must be defined by Designer and Installer (ex. expansion tanks, vents, taps, ation/safety valves etc.) plumbing diagram Indicative The system components must be defined by Designer and Installer (ex. expansion tanks, vents, taps…
-
SWH-190IRES2, SWH-300IRES2 Indicative plumbing diagram The system components must be defined by Designer and Installer (ex. expansion tanks, vents, taps, calibration/safety valves etc.) Indicative plumbing diagram 1 Pressurecomponents reducing valve must 2be defined Water treatment devices and…
-
MONOBLOC WATER HEATERS R290 MODEL NAME SWH-190P(M) SWH-300P(M) Power supply SWH-190PS SWH-300PS 220-240 / 1 / 50 Mode Heat pump / E-heater Running ambient temperature Heat pump °C -7 ~ 43 E-heater °C -20 ~ 46 Storage size l Maximum inlet water pressure Mpa 0,7 Net/gross weight kg 91 / 112 123 / 148…
-
SWH-190P(M), SWH-300P(M) connector Připojení spec. Rozměr hot waterVýstup outletvody R3/4” R3/4” connector Připojení Rozměr cold water inletvody spec. R3/4” Vstup R3/4” hot outlet R3/4” vody RC3/4” R3/4” PTRwater valveVýstup PTR ventil RC3/4” cold inletvodypotrubí R3/4” Vstup R3/4” drainwater pipe…
-
connector spec. hot water outlet R3/4” cold water inlet R3/4” connector spec. Rozměr connector spec. Připojení Připojení Rozměr PTR valve RC3/4” hot water outlet R3/4” Solar outlet R3/4” Výstup vody R3/4” Solár výstup R3/4” connector spec.Rozměr connector Připojení Připojení spec. Rozměr cold water…
-
SWH-190P(M), SWH-300P(M) User Condensate Outlet R3/4” RC3/4” Temp. Limiting Valve Water Outlet PTR Valve (recommended) RC3/4” R3/4” One Way Valve Water Inlet Shut Off Valve Tap Water Siphon Drain pipe Expansion Tank for pressure relief (recommended) Shut Off Valve NPT3/4” Barrel-drain Different ways…
-
SWH-190PS, SWH-300PS Užitková voda ●● Odtok kondenzátu RC3/4” PTR Ventil R3/4” Směšovací ventil Výstup vody R3/4” Vstup vody RC3/4” Jednocestný ventil Uzavírací ventil Studená voda Sifón Odtokové potrubí Uzavírací ventil NPT3/4” Expanzní nádoba Odtoková nádoba 136
-
AKU ST 300 S Deflector Deflector Deflector Deflector Earthing screw 140
-
ST-250DE
-
ST-300DE
-
ST- 500DE
-
MONOBLOC UNITS
ACCESSORIES MODEL EH-SMH Water connection inch 2 x 1", 1 x 3/8" Material - Stainless steel Korozivzdorná ocel Isolation Material - pěna NBR-PVC foam Isolation thickness mm 10 Protecting rating - IP45 Power supply V/f/Hz 400/3/50 Power input kW 9 Max. pressure MPa/bar 1/10 kg 3,13 - 9BBSI102ANEP002C…
-
APPEARANCE AND DIMENSIONS
-
ACCESSORIES MODEL TJ 6/4" 3,3 kW Connection inch Power input kW 6/4" 3,3 Power supply V/f/Hz 400/3/50 Set temperature range °C 5-47 Built-in body length mm 325 Weight kg 1,7 The specification of products is subject to change based on further development of the units by the producer and can be…
-
CONNECTION
-
ONTARIO
No. Full name Displayed name Error code 1 Ambient temperature sensor error Ambient sensor F4 2 Defrosting temperature sensor error Defrost sensor d6 3 Discharge temperature sensor error Discharge sensor F7 4 Suction temperature sensor error Suction sensor F5 5 Economizer inlet temperature sensor…
-
ONTARIO
No. Full name Displayed name Error code 40 The radiator of IPM or PFC temperature sensor error T mod. sensor P7 41 Charging circuit error Charge circuit Pu 42 AC input voltage error AC voltage PP 43 Ambient temperature sensor error at the drive board Temp driver PF 44 AC contactor protection or…
-
ONTARIO MONOBLOC 5TH GENERATION
Code Indication F4 d6 F7 Code Indication F5 EF E1 E3 E4 C5 E6 Error Name Source of Error Signal The plug on temperature sensor is not correctly connected to the Outdoor environment temp socket on mainboard. sensor error The resistance of temperature sensor is not correct. The plug on temperature…
-
E4
Comp Discharge temp protection ERROR CODES The electronic expansion valve is blocked. The system has leaked. Mainboard of outdoor unit is damaged. ONTARIO MONOBLOC 5TH GENERATION C5 Code Indication E6 Cpacity switch error Error Name Communication malfunction(between mainboard outdoor and indoor and…
-
F3
sensor inside refrigerant error ERROR CODES socket on mainboard. The resistance of temperature sensor is not correct. cleared after the failure is removed. The plug on temperature sensor ONTARIO MONOBLOC 5TH GENERATION is not correctly connected to the It will be automatically F0 Code Indication…
-
ERROR
CODE MALFUNCTION OR PROTECTION Water flow falut(after 3 times E8) FAILURE CAUSE AND CORRECTIVE ACTION 1.The wire circuit is short connected or open. Reconnect the wire correctly. 2.Water flow rate is too low. 3. Water flow switch is failed, switch is open or close continuously, change the water flow…
-
ERROR
CODE MALFUNCTION OR PROTECTION FAILURE CAUSE AND CORRECTIVE ACTION 1. The EEprom parameter is error, rewrite the EEprom data. Indoor unit EEprom failure 2. EEprom chip part is broken, change a new EEprom chip part. 3. main control board of indoor unit is broken, change a new PCB. 1.wire doesn’t…
-
ERROR
CODE MALFUNCTION OR PROTECTION Three times “PP” protection and Tw_out< 7℃ FAILURE CAUSE AND CORRECTIVE ACTION The same to "PP". 1.Check the resistance of the sensor. Buffer tank up temp.sensor(Tbt1) fault 2.The Tbt1 sensor connector is loosen,reconnect it. 3.The Tbt1 sensor connector is wet or there…
-
YUKON R290
Water circuit error Error code Description Displayed on E0 water flow failure (10 times of E8) User Interface and Main Control PCB E8 water flow protection User Interface and Main Control PCB Communication error Error code Description Displayed on E2 Communication fault between User Interface and…
-
Voltage error
ERROR CODES Error code YUKONE1R290Phase loss or phase reversal H7 Description Displayed on User Interface and Main Control PCB Power overvoltage and Power undervoltage protection For 3Ph models User Interface and Main Control PCB Protection code Error code Description Displayed on P0 Low pressure…
-
bA
PP ERROR CODES LC3 Hb T4 sensor out of operation range protection User Interface and Main Control PCB The protection for abnormal temperature difference between outlet User Interface and Main Control PCB water and inlet water YUKONLC4R290PFC power factor is less than 0.8between outlet water temp.…
-
YUKON SERIES MONOBLOC 26 - 40 KW R290
Water circuit error Error code Description Displayed on E0 water flow failure (10 times of E8) User Interface and Main Control PCB E8 water flow protection User Interface and Main Control PCB Communication error Error code Description Displayed on E2 Communication fault between User Interface and…
-
Voltage error
Error code ERROR CODES Description Displayed on E1 Phase loss or phase reversal. User Interface and Main Control PCB FE Lack of L2 phase fault. User Interface and Main Control PCB YUKONH7SERIES MONOBLOC - 40 KW R290 User Interface and Main Control PCB Power overvoltage and Power under26 voltage…
-
bA
PP ERROR CODES Hb T4 sensor out of operation range protection User Interface and Main Control PCB Protection for abnormal temperature difference between outlet User Interface and Main Control PCB water and inlet water PP occurs 3 times in heating/DHW mode User Interface and Main Control PCB YUKON…
-
YUKON COMMERCIAL SERIES R32
No. Code 2 Content Main control Model setting error (Other Model Main control EPROM error) E1 Phase sequence error of main control board check 3 E2 E3 Total water outlet temperature sensor failure (main unit valid) E4 Unit water outlet temperature sensor failure 1E5 condenser tube temperature sensor…
-
YUKON COMMERCIAL SERIES R32
No. Code 40 F4 41 F6 42 43 Fb Fd FF Content 1F4 module A L0 or L1 protection occursfor 3 times in 60 minutes Note Recovered by power off 2F4 module B L0 or L1 protection occursfor 3 times in 60 minutes Recovered by power off 1F6 A system bus voltage error (PTC) Recovered upon error recovery 2F6 B…
-
Ϭ
ϭ Ϯ ϮϮ ϯϮ ϯ ϰ ϭϱ ϲ ϳ ϴ ϵ ϭď Ϯď Ě & W h WϬ ϭWϬ Wϭ Wϯ Wϰ Wϳ Wϵ W W W W, W> ϭWh ,ϱ ϭ,ϵ , , ϭ&Ϭ &Ϯ &ϰ DĂŝŶŽŶƚƌŽůDŽĚĞůƌƌŽƌ WŚĂƐĞ^ĞƋƵĞŶĐĞ&ĂƵůƚ ,ŽƐƚtŝƌĞĚŽŶƚƌŽůůĞƌŽŵŵƵŶŝĐĂƚŝŽŶ&ĂƵůƚ;ĚŝƐƉůĂLJĞĚĨŽƌƚŚĞŚŽƐƚͿͬ,ŽƐƚĂŶĚ^ůĂǀĞŽŵŵƵŶŝĐĂƚŝŽŶ&ĂƵůƚ ;ĚŝƐƉůĂLJĞĚĨŽƌƚŚĞƐůĂǀĞͿ DĂŝŶŽŶƚƌŽůĂŶĚdžƉĂŶƐŝŽŶŽĂƌĚϲϬƐŽŵŵƵŶŝĐĂƚŝŽŶ&ĂƵůƚ…
-
&ϲ
&ď &Ě ϭ&& &W ϭď, ϭ>ϭϬ ϭ>ϭϭ ϭ>ϭϮ ϭ>ϮϬ ϭ>ϯϬ ϭ>ϯϭ ϭ>ϯϮ ϭ>ϯϰ ϭ>ϰϯ ϭ>ϰϱ ϭ>ϰϲ ϭ>ϰϳ ϭ>ϱϬ ϭ>ϱϭ ϭ>ϱϮ ϭ>ϲϬ ϭ>ϲϱ ϭ>ϲϲ ϭ>ϲ ϭ>ϲ ϭ>ϲ ϭ&ϲƵƐďĂƌsŽůƚĂŐĞ&ĂƵůƚŽĨ^LJƐƚĞŵ >ŽǁͲWƌĞƐƐƵƌĞWƌĞƐƐƵƌĞ^ĞŶƐŽƌ&ĂƵůƚ ZĞƚƵƌŶŝƌdĞŵƉĞƌĂƚƵƌĞ^ĞŶƐŽƌ&ĂƵůƚ &ĂƵůƚŽĨ&ĂŶϭ /ŶĐŽŶƐŝƐƚĞŶƚŝĂůŝŶŐŽĨDƵůƚŝƉůĞtĂƚĞƌWƵŵƉƐ &ĂƵůƚŽĨDŽĚƵůĞϭ…
-
ϭ>ϲ
ϭ>ϲ ϭ>ϲ& sͲWŚĂƐĞ>ŽǁĞƌdƵďĞKƉĞŶŝƌĐƵŝƚ;dŚĞĨĂƵůƚĐŽĚĞŝƐŽŶůLJĚŝƐƉůĂLJĞĚĨŽƌƚŚĞǁŝƌĞĚĐŽŶƚƌŽůůĞƌ͕ĂŶĚŶŽƚ ĚŝƐƉůĂLJĞĚĨŽƌƚŚĞŵĂŝŶďŽĂƌĚͿ tͲWŚĂƐĞhƉƉĞƌdƵďĞKƉĞŶŝƌĐƵŝƚ;dŚĞĨĂƵůƚĐŽĚĞŝƐŽŶůLJĚŝƐƉůĂLJĞĚĨŽƌƚŚĞǁŝƌĞĚĐŽŶƚƌŽůůĞƌ͕ĂŶĚŶŽƚ ĚŝƐƉůĂLJĞĚĨŽƌƚŚĞŵĂŝŶďŽĂƌĚͿ…
-
Symptom
Error Description The water heater stops operation and the wired controller displays E1. System high pressure protection. The water heater stops operation and the wired controller displays E3 Refrigerant-lacking protection The water heater stops operation and the wired controller displays C5…
-
Symptom
Error Description The water heater stops operation and the wired controller displays LF Power protection of inverter compressor The water heater stops operation and the wired controller displays Pc Detection circuit malfunction of driven circuit of inverter compressor The water heater stops…
-
Code
Description Solution E0 Error of sensor T5U (upper water temperature sensor) Maybe the connection between sensor and PCB has released or sensor has been broken. Contact a qualified person to service the unit. E1 Error of sensor T5L(lower water temperature sensor) Maybe the connection between sensor…
-
Code
Description Solution System high pressure protection: P1 P2 Maybe because of system blocked, air or water or more refrigerant in system (after repair), water temperature sensor malfunction, ect. Unit 190 : P1 error code never appear because pressure Contact a qualified person to service the unit.…
-
MONOBLOC WATER HEATERS R290
Code Content EH0b Tank and wired controller communication error. EH00 EEPROM chip error EH03 Dc fan fault PH15 Electric leakage protection EC54 Compressor discharge temperature sensor TP error. EH5H Compressor suction temperature sensor TH error EC53 Ambient temperature sensor T4 error. EC52…
-
WALL-MOUNTED MONOBLOC WATER HEATERS R290
Display Malfunction Description Corrective action EH0b Tank and LCD panel communication error. Maybe the connection between LCD panel and PCB has released or PCB has been broken. EH00 Machine working parameters are abnormal. Contact a qualified person to service the unit. EH03 Dc fan fault. Maybe…
-
DHW - Domestic hot water SEER/SCOP was calculated according to European standards contained in EN14825, based on part load classifying and testing conditions given by norm EN14511. Energy label can be downloaded from Sinclair product web page after B2B login. EER/COP - in accordance with EN14511.…
-