TECHNICAL CATALOGUE RESIDENTIAL AIR CONDITIONING 2021-2022 · WALL MOUNTED AC · MULTI VARIABLE SERIES · HIGH POWER MULTI SYSTEM · UNI SPLIT SERIES · HIGH STATIC PRESSURE DUCT UNIT · PORTABLE DEVICES AIR CONDITIONING
-
T E C H N I C A L C ATA L O G U E R E S I D E N T I A L A I R C O N D I T I O N I N G - CONTENT SPECTRUM+ SERIES 3 TERREL SERIES 6 KEYON SERIES 9 RAY SERIES 12 CONSOLE SERIES 16 MULTI VARIABLE SERIES 19 HIGH POWER MULTI SYSTEM SERIES 37 UNI SPLIT SERIES 44 HIGH STATIC PRESSURE DUCT UNIT 61 TOWER…
-
SPECTRUM PLUS SERIES
MODEL ASH-09BIS2/W ASH-13BIS2/W ASH-18BIS2/W ASH-24BIS2/W kW 2,7 (0,7-5,0) / 3,5 (0,7-5,5) 3,6 (0,9-5,0) / 4,2 (0,9-7,2) 5,3 (1,2-7,2) / 6,2 (1,2-9,2) 7,1 (2,0-9,0) / 7,1 (2,0-9,5) Power supply Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 Power supply - outdoor…
-
3.1 lndoor Unit
-
SPECTRUM PLUS SERIES
-
TERREL SERIES
MODEL SIH+SOH-09BIT SIH+SOH-13BIT SIH+SOH-18BIT SIH+SOH-24BIT kW 2,7 (0,8-3,8 ) / 3,0 (0,9-4,2) 3,5 (1,0-3,8) / 3,8 (0,9-4,7) 5,2 (1,0-6,1) / 5,3 (1,1-6,0) 7,0 ( 2,0 - 8,5) / 7,4 ( 2,2-9,0) Power supply Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 Power supply…
-
W
-
KEYON SERIES
MODEL SIH+SOH-09BIK SIH+SOH-12BIK SIH+SOH-18BIK SIH+SOH-24BIK kW 2,7 (0,6-3,4) / 2,8 (0,6-3,7) 3,2 (0,9-3,7) / 3,4 (0,9-4,1) 4,6 (1,0-5,3) / 5,2 (1,0-5,65) 6,2 (1,8-6,4) / 6,5 (1,6-6,6) Power supply Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 Power supply - outdoor…
-
O������������������������
�O������������������������ APPEARANCE AND DIMENSIONS OF OUTDOOR UNIT KEYON PLUS SERIES SOH-09BIK SOH-12BIK SOH-09BIK SOH-12BIK SOH-09BIK 550 550 SOH-12BIK SOH-18BIK 285 SOH-18BIK 675 SOH-18BIK 285 SOH-18BIK SOH-18BIK 316,5 555 SOH-24BIK 376 873 348,6
-
RAY SERIES
MODEL SIH+SOH-09BIR SIH+SOH-12BIR SIH+SOH-18BIR SIH+SOH-24BIR kW 2,7 (0,5-3,25) / 2,8 (0,5-3,5) 3,2 (0,9-3,6) / 3,4 (0,9-4,0) 4,6 (1,0-5,3) / 5,2 (1,0-5,6) 6,2 (1,8-6,9) / 6,5 (1,3-7,0) Power supply Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 Power supply - outdoor…
-
2XWOL�H�'LPH�VLR��'LDJUDP
-
550 APPEARANCE AND DIMENSIONS OF OUTDOOR UNIT RAY SERIES SOH-09BIR, SOH-12BIR SOH-18BIR 310 455 SOH-24BIR units: mm 14
-
RAY SERIES
-
CONSOLE SPLIT AIR CONDITIONERS
CONSOLE SERIES MODEL ASP-09BI ASP-12BI ASP-18BI kW 2,7 (0,7-3,4) / 2,9 (0,6-3,5) 3,5 (0,8-4,4) / 3,8 (1,1-4,4) 5,2 (1,3-6,6) / 5,3 (1,1-6,8) Power supply Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 Power supply - outdoor outdoor outdoor Power input cooling/heating 1) W 720 / 730…
-
ce Manual Service Manual 2 Outdoor 3.2 Outdoor Unit Unit ASP-12BIASP-12BI units: mm ASP-09BI 286 CONSOLE SERIES 286 DIMENSIONS OF OUTDOOR UNIT Service Manual 3.2 Outdoor Unit Unit:mm Unit:mm 540 ASP-12BI ASP-12BI Unit:mm Unit:mm Unit:mm Unit:mm 510 Unit:mm ASP-09BI ASP-18BI ASP-09BIASP-09BI Unit:mm…
-
INDOOR UNIT
-
WALL MOUNTED AIR CONDITIONERS TERREL
MULTI VARIABLE SERIES MODEL Capacity cooling/heating 1) SIH-09BIT SIH-13BIT SIH-18BIT SIH-24BIT 2,7 (0,8-3,8 ) / 3,0 (0,9-4,2) 3,5 (1,0-3,8) / 3,8 (0,9-4,7) 5,2 (1,0-6,1) / 5,3 (1,1-6,0) 7,0 ( 2,0 - 8,5) / 7,4 ( 2,2-9,0) Nominal (min-max) kW Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 /…
-
WALL MOUNTED AIR CONDITIONERS KEYON
-
WALL MOUNTED AIR CONDITIONERS RAY
MULTI VARIABLE SERIES MODEL Capacity cooling/heating 1) SIH-09BIR SIH-12BIR SIH-18BIR SIH-24BIR 2,7 (0,5-3,25) / 2,8 (0,5-3,5) 3,2 (0,9-3,6) / 3,4 (0,9-4,0) 4,6 (1,0-5,3) / 5,3 (1,0-5,6) 6,2 (1,8-6,9) / 6,5 (1,3-7,0) Nominal (min-max) kW Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240…
-
CONSOLE INDOOR UNITS
MULTI VARIABLE SERIES MODEL Capacity cooling/heating 1) Nominal Power supply MV-P09BI MV-P12BI kW 2,7 / 2,8 3,5 / 3,75 MV-P18BI 5,2 / 5,33 Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 Airflow of ID SH/MH/H/M/L/ML/SL m³ / h 500 / 430 / 410 / 370 / 330 / 280 / 250 600 / 520 / 480 / 440…
-
MODEL
-
CASSETTE INDOOR UNITS
MULTI VARIABLE SERIES MODEL Capacity cooling/heating 1) Nominal Power supply MV-C12BI2 MV-C18BI2 kW 3,5 / 4,0 5,0 / 5,5 MV-C24BI2 7,0 / 8,0 Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 1100 / 950 / 870 / 800 Airflow of ID SH/H/M/L m³ / h 560 / 490 / 420 / 350 650 / 490 / 420 / 350…
-
MV-C12BI2
-
CASSETTE INDOOR UNITS
-
MODEL
-
таблицы и схемы — в просмотре
-
MODEL
-
MODEL
MV-E14BI MV-E18BI MV-E21BI 1-2 1-2 2-3 2-3 kW 4,1 (2,1-4,4) / 4,4 (2,5-5,4) 5,2 (2,1-5,8) / 5,4 (2,6-5,9) 6,1 (2,2-7,3) / 6,5 (3,6-8,5) 7,1 (2,3-8,5) / 8,5 (3,7-8,8) Power supply Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 Power input cooling/heating 1) W 1200 /…
-
таблицы и схемы — в просмотре
-
ENERGY CLASS INFORMATION
-
APPEARANCE AND DIMENSIONS OF OUTDOOR UNIT
-
MV-E21BI Power supply Power supply Indoor unit Indoor unit MV-E24BI Power supply Outdoor unit Indoor unit MV-E28BI Power supply Outdoor unit Indoor unit MV-E36BI Outdoor unit Power supply Indoor unit D Indoor unit C Indoor unit B Indoor unit A 34
-
MV-E42BI
Outdoor unit Indoor unit E Indoor unit D Indoor unit C Indoor unit B Indoor unit A 35 Power supply
-
COMBINATION TABLES
-
MODEL
MS-E48AIN Qty of connectable indoor units MS-E56AIN - 2-8 2-9 kW 14,0 (1,0-16,0) / 16,0 (1,2-17,4) 16,0 (1,0-18,0) / 18,0 (1,2-19,0) Power supply Hz / V 3~ / 50 / 380-415 3~ / 50 / 380-415 Power input cooling/heating 1) W 4600 / 4250 5200 / 4700 Maximal power input 2) W 6000 6500 Power current…
-
LLOWED LENGTH AND DROP HEIGHT OF CONNECTION PIPE
5 APŘIPOJENÍ TRUBEK CHLADIVA HIGH POWER MULTI SYSTEM SERIES 5.1 Přípustná délka a výškový rozdíl propojovací trubky Venkovní jednotka Outdoor unit 2. rozbočovač 1. rozbočovač 1st branch pipe 2nd branch pipe DB1 DB2 Vnitřníunit jednotka Indoor DB3 DB: distribution box box) DB: rozdělovač (distribuční…
-
APPEARANCE AND DIMENSIONS OF DISTRIBUTION BOXES
HIGH POWER MULTI SYSTEM SERIES DB2-19SB DB3-19SB DB5-16AF units: mm Indoor unit Vnitřní jednotka Napájecí kabel pro venkovní jednotku a rozbočovací box (3 vodiče) Cassette Kazetová unit jednotka Propojovací trubka Komunikační kabel (2 vodiče) ELECTRICAL WIRING DIAGRAM Duct Kanálová unit jednotka…
-
HIGH
POWER MULTI SYSTEMWork SERIES 7. Electrical Wiring 7. Electrical Wiring Work 7.1 Wiring Connection OPTION 1 7.1 Wiring Connection Outdoor unit Power supply Indoor unit 1A /Dbox Dbox /Dbox Dbox Indoor unit 1B Dbox Dbox Dbox /Dbox distribution box 1 Indoor unit 1C Dbox /Dbox Indoor unit 2A Indoor unit…
-
OPTION 3
Outdoor unit Power supply distribution box 1 distribution box 2 Power supply of distribution box 1 Indoor unit 1A Indoor unit 1B Indoor unit 1C Indoor unit 1D Indoor unit 1E Indoor unit 2A Indoor unit 2B Indoor unit 1C Power supply of distribution box 2 REQUIREMENTS OF POWER CIRCUIT AND CABLE…
-
COMBINATION TABLE
(unit: x1000Btu/h) MS-E48AIN 2 UNITS 7+18 9+18 12+12 7+24 9+24 12+18 7+7+12 7+9+18 7+18+18 7+7+18 7+9+24 7+18+24 7+7+24 7+12+12 7+9+9 12+24 18+18 18+24 24+24 9+9+18 9+12+24 12+12+12 12+18+24 9+9+24 9+18+18 12+12+18 12+24+24 7+24+24 9+12+12 9+18+24 12+12+24 18+18+18 7+12+18 9+9+9 9+12+18 9+24+24…
-
COMBINATION TABLE
(unit: x1000Btu/h) MS-E56AIN 2 UNITS 7+18 9+18 12+18 7+24 9+24 12+24 7+7+18 7+12+12 7+24+24 9+12+12 7+7+24 7+12+18 9+9+12 9+12+18 7+9+12 7+12+24 9+9+18 7+9+18 7+18+18 7+9+24 7+18+24 7+7+7+7 18+18 18+24 24+24 9+18+24 12+12+24 18+18+18 9+24+24 12+18+18 18+18+24 9+12+24 12+12+12 12+18+24 18+24+24…
-
4-WAY CASSETTE INDOOR UNITS
UNI SPLIT SERIES MODEL Capacity cooling/heating 1) Nominal (min-max) ASC-12BI / ASGE-12BI ASC-18BI / ASGE-18BI ASC-24BI / ASGE-24BI ASC-30BI / ASGE-30BI ASC-36BI / ASGE-36BI kW 3,5 (0,4-3,7) / 4,0 (0,8-4,1) 5,0 (0,6-5,3) / 5,5 (1,2-5,7) 7,0 (0,8-7,3) / 8,0 (1,6-8,4) 8,5 (1,0-8,9) / 8,8 (2,0-9,1)…
-
4-WAY CASSETTE INDOOR UNITS
UNI SPLIT SERIES MODEL ASC-36BI / ASGE-36BI-3 ASC-42BI / ASGE-42BI-3 ASC-48BI / ASGE-48BI-3 ASC-60BI / ASGE-60BI-3 kW 10,0 (1,17-10,59) / 12,0 (2,61-12,42) 12,1 (1,5-12,7) / 13,5 (3,1-14,0) 13,4 (1,7-14,1) / 15,5 (3,2-16,0) 16,0 (2,0-15,2) / 17,0 (3,5-17,6) Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240…
-
APPEARANCE AND DIMENSIONS OF CASSETTE INDOOR UNITS
-
MODEL
Capacity cooling/heating 1) Nominal (min-max) Power supply ASF-12BI / ASGE-12BI ASF-18BI / ASGE-18BI ASF-24BI / ASGE-24BI ASF-30BI / ASGE-30BI ASF-36BI / ASGE-36BI kW 3,5 (0,3-3,7) / 4,0 (0,7-4,1) 5,0 (0,6-5,3) / 5,5 (1,2-5,7) 7,0 (0,7-7,4) / 8,0 (1,8-8,3) 8,5 (1,0-8,9) / 8,8 (2,0-9,1) 10,0…
-
MODEL
Capacity cooling/heating 1) Nominal (min-max) Power supply ASF-36BI / ASGE-36BI-3 ASF-42BI / ASGE-42BI-3 ASF-48BI / ASGE-48BI-3 ASF-60BI / ASGE-60BI-3 kW 10,0 (1,2-10,5) / 12,0 (2,5-12,4) 12,1 (1,6-12,7) / 13,5 (3,0-14,0) 13,4 (1,6-14,1) / 15,5 (3,4-16,0) 16,0 (2,0-16,8) / 17,0 (3,7-17,6) Hz / V 1~…
-
APPEARANCE AND DIMENSIONS OF FLOOR-CEILING INDOOR UNITS
-
MODEL
Capacity cooling/heating 1) Nominal (min-max) Power supply ASD-12BI / ASGE-12BI ASD-18BI / ASGE-18BI ASD-24BI / ASGE-24BI ASD-30BI / ASGE-30BI ASD-36BI / ASGE-36BI kW 3,5 (0,7-3,7) / 4,0 (0,8-4,1) 5,0 (0,6-5,3) / 5,5 (1,1-5,7) 7,0 (0,8-7,6) / 8,0 (1,7-8,3) 8,5 (1,0-8,9) / 8,8 (2,0-9,1) 10,0…
-
MODEL
Capacity cooling/heating 1) Nominal (min-max) Power supply ASD-36BI / ASGE-36BI-3 ASD-42BI / ASGE-42BI-3 ASD-48BI / ASGE-48BI-3 ASD-60BI / ASGE-60BI-3 kW 10,0 (1,2-10,6) / 12,0 (2,5-12,4) 12,1 (1,6-12,7) / 13,5 (3,0-14,0) 13,4 (1,6-14,1) / 15,5 (3,4-16,0) 16,0 (2,0-16,8) / 17,0 (3,7-17,6) Hz / V 1~…
-
APPEARANCE AND DIMENSIONS OF DUCT INDOOR UNITS
UNIVnitřní SPLIT SERIES 3.1.3.1 jednotka 3.1.3.1 Vnitřní jednotka POZNÁMKA Vrtání otvorů do stropu a instalaci klimatizačního zařízení musí provádět odborníci! POZNÁMKA Jednotka: mm Dimensions Rozměry Vrtání otvorů do stropu a instalaci klimatizačního odborníci! A B C zařízení D musí provádět E F…
-
WALL MOUNTED INDOOR UNITS
UNI SPLIT SERIES MODEL Capacity cooling/heating 1) Nominal (min-max) Power supply ASH-24BIH ASH-36BIH kW 7,0 (0,7-7,4) / 8,0 (1,8-8,3) 10,0 (1,2-10,5) / 12,0 (2,5-12,4) Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 Energy class cooling 3) Pdesign cooling A++ A++ kW 7,0 10,0 6,8 6,1 kWh / annum 359 573…
-
ASH-24BIH
-
MODEL
ASGE-12BI ASGE-18BI ASGE-24BI ASGE-30BI kW 3,5 / 4,0 5,0 / 5,5 7,0 / 8,0 8,5 / 8,8 10,0 / 12,0 Power supply Hz / V 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 1~ / 50 / 220-240 Power input cooling/heating 1) W 950 / 1050 1550 / 1450 2100 / 2450 2800 / 2650 3300 / 3600…
-
MODEL
ASGE-36BI-3 ASGE-42BI-3 ASGE-48BI-3 kW 10,0 / 12,0 12,1 / 13,5 13,4 / 15,5 16,0 / 17,0 Power supply Hz / V 3~ / 50 / 380-415 3~ / 50 / 380-415 3~ / 50 / 380-415 3~ / 50 / 380-415 Power input cooling/heating 1) W 3300 / 3500 4050 / 4150 4700 / 4450 5450 / 5400 Maximal power input 2) W 4650 5300 5950…
-
APPEARANCE AND DIMENSIONS OF OUTDOOR UNIT
-
Outdoor unit Indoor unit Wired controller Breaker Power Breaker Power Outdoor unit Indoor unit Wired controller Breaker Power 1 Outdoor unit power supply 2 Indoor unit power supply Power 3 Communication cable 4 Communication cable 58
-
ASGE-36BI
Outdoor unit Indoor unit Wired controller Breaker Breaker Power Power Outdoor unit Indoor unit Wired controller Breaker Power 1 Outdoor unit power supply 2 Indoor unit power supply Power 3 Communication cable 4 Communication cable 59
-
Outdoor unit Indoor unit Wired controller Breaker Power Breaker Power Outdoor unit Indoor unit Wired controller Breaker Power 1 Outdoor unit power supply 2 Indoor unit power supply Power 3 Communication cable 4 Communication cable 60
-
SPLIT AIR CONDITIONER
HIGH STATIC PRESSURE DUCT UNIT MODEL Capacity cooling/heating 1) ASDH-96AI Nominal kW 28,0 / 31,5 Hz / V 1~ / 50 / 220-240 Power supply OD - 3~ / 50 / 380-415 Power input cooling/heating 1) W 9000 / 8500 Maximal power input 2) W 11700 Nominal current cooling/heating of ID A 4,5 Nominal power current…
-
APPEARANCE AND DIMENSIONS OF UNITS
HIGH STATIC PRESSURE DUCT UNIT 1558 272 272 1558 6. ELECTRIC WIRE DIAGRAM 1138 1138 390 390 CCM 1120 1120 units: mm Branch Box 6. ELECTRIC WIRE DIAGRAM ELECTRICAL WIRING DIAGRAM POWER SUPPLY 380-415V ~50HZ Outdoor unit Circuit breaker Circuit breaker Power supply Outdoor unit Indoor unit Indoor unit…
-
SPLIT AIR CONDITIONER
APPEARANCE AND DIMENSIONS OF UNITS TOWER SERIES MODEL Capacity cooling/heating 1) AST-24BI Nominal kW 7,2 / 7,9 Frequency/Voltage Hz / V 1~ / 50 / 220-240 Power input cooling/heating 1) W 2050 / 2330 Maximal power input 2) W 3900 Power current cooling/heating A 10,0 / 11,0 Maximal power current 2) A…
-
WINDOW MONOBLOCK AIR CONDITIONERS
-
VEHICLE AIR CONDITIONERS
-
APPEARANCE, DIMENSIONS AND WIRING OF UNITS
BOAT SERIES units: mm ASB-05A A B C D E F 91,5 16 19 ASB-09A 91,5 16 19 ASB-12A 119,4 16 19 ASB-16A 119,4 16 19 ASB-24A 119,4 16 19 ELECTRICAL WIRING DIAGRAM PE L N N Water pump P N1 Mainboard L CN71 Wired controller PACKAGE CONTENTS Package Include Wired Controller Remote Controller …
-
COMMUNICATION MODULE SCMI-01.4 LOW GOAL TEMPERATURE UP TO -10°C · SCMI-01.4 offers 3 basic operation modes: · Autonomous temperature control mode: The system changes its performance in order to achieve set temperature measured with T2 sensor. You can set temperature from -10 °C to +55 °C · Slave…
-
outdoor unit AUTONOMOUS TEMPERATURE CONTROL MODE FOR COOLING AND HEATING Performance of the outdoor unit compressor is controlled to keep the temperature set for cooling/heating/ mode combi. The room temperature is measured with the resistance thermometer T2. It is necessary to set the requested…
-
SOFTWARE FOR SCMI-01.4 CONTROL · · · · · FMD MODULES FMD modules are used to control speed of DC fan motors. FMD-01 FMD-01T Designed to control fan motors of indoor units from UNI SPLIT series*. The fan speed is controlled via SCMI-01.4 module. Designed to control fan motors of indoor units from UNI…
-
HEALTH FILTERS FOR WALL MOUNTED UNITS
SAF-OPWC4 SAF-OPWP4 CATECHIN FILTER PHOTOCATALYST FILTER Catechin is a green tea extract added to the filters for its oxidizing and sterilizing effects. Active enzymes form a benzene nucleus which absorbs odors and harmful substances in the air. Catechin filter effectively captures and sterilizes…
-
WIRED CONTROLLERS
XK19 WIRED CONTROLLER Standard accessory for duct, cassette and floor-ceiling MULTI VARIABLE units. Optionally can be connected to the indoor units of MULTI VARIABLE, FOCUS, FOCUS PLUS, SPECTRUM, SPECTRUM PLUS, SPLIT CONSOLE series. It is necessary to order communication cable SC-H01 or SC-CDF for…
-
TECHNICAL PARAMETERS
WIRED CONTROLLERS MON MON $ $ SET SET AUTO AUTO Model XK19 SWC-02 XK117 SWC-03 On/Off Mode selection Temperature setting Fan control Swing louver Save function setting Room temperature display Buttons lock Function lock On/Off…
-
CENTRAL CONTROLLERS
SCC-16 CENTRAL CONTROLLER AND WEEKLY TIMER This central controller allows you to control up to 16 unit simultaneously and set the weekly timer. It can be used with UNI SPLIT series (has to be connected via modbus gateway SMG01 – each indoor unit needs to have one SMG-01) or when connected via wired…
-
CENTRAL CONTROLLERS
CENTRAL CONTROLLER AND WEEKLY TIMER SCC-36 · · · · · Stylish central controller with 7" touch screen Connects up to 36 indoor units User friendly interface Weekly timer Single, group or all units control It can be used with UNI SPLIT series (has to be connected via Modbus gateway SMG-01 – each…
-
OTHER ACCESSORIES
SBG-01 BACNET GATEWAY Bacnet gateway allows external control via Bacnet protocol. One gateway can communicate with up to 255 indoor units. The connection is done via SWC-02 or SMG-01, so the gateway is compatible with UNI SPLIT series and with all indoor units that allow connection of SWC-02 wired…
-
OTHER ACCESSORIES
G2S-T GSM MODULE FOR TEMPERATURE MONITORING G2S-T module is used for remote monitoring of room temperature. When the set temperature is exceeded, the module sends an information to user’s mobile phone. Hence the module has to be equipped with a mini SIM card in order to secure the operation. G2S-T a…
-
DIAGNOSTIC TOOLS
SYSTEM ERROR DIAGNOSTICS SDT-ASH DIAGNOSTIC TOOL FOR SPLIT WALL MOUNTED AC · · · · · · · · · SDT-MV Indoor and outdoor unit diagnostic Running parameters Simulation run of indoor or outdoor unit Test of indoor and outdoor mainboard during communication malfunction IR receiver (can be used during…
-
RESIDENTIAL AIR CONDITIONING
GENERAL OVERVIEW OF ERROR CODES APPLIES TO WALL MOUNTED SPLIT UNITS AND TO MULTI VARIABLE SERIES ERROR Others E0 Start-up protection to adjust the frequency when the power input is low AL X-fan E1 High pressure protection C5 Malfunction of jumper cap E2 Freeze protection C6 Ground wire missing E3…
-
SCMI-01.4 MODULE
GENERAL OVERVIEW OF ERROR CODES Module SCMI-01.4 error Error T1 open Open circuit of temperature sensor T1 Error T2 open Open circuit of temperature sensor T2 Error T1 short Short circuit of temperature sensor T1 Error T2 short Short circuit of temperature sensor T2 Error P open Open circuit of…
-
AIR CONDITIONING
sinclair-world.com | sinclair-solutions.com