CATALOGUE
PRICE LIST 2019 REV 1
-
Via Zampeschi 119 – 47121 Forlì (FC) – Italy
Ph. +39 0543 723197 – Fax +39 0543 720413 www.fiorini-industries.com
-
Catalogue – Price List 2019 REV 1
-
Company Profile
pag. 4 Tailored Solutions pag. 12 Plate Heat Exchangers pag. 24 Cold Storage Tanks Water pag. 62 Hydronic Kits pag. 86 Cold Water Accessories pag. 126 Domestic Hot Water Storages pag. 134 Indirect Water Heater pag. 142 DHW Fast Heaters pag. 186 DHW Fresh Water Stations pag. 200 Hot Water Storage…
-
Paving the way
towards the future For over 40 years we have aimed to transfer our values to our clients by designing and realising high quality and trustworthy products for both the residential and the industrial sector. Our hard work has yielded us a leadership role in Italy and abroad. Especially, in designing…
-
Our certificates
An added value for our clients and partners To the Fiorini group, certificates are a proof of responsibility towards the clients, the partners, the community and the territory. It springs from the awareness that our activity cannot come before the guidelines and the expectations of the stakeholders.…
-
Certificate for
Quality management – ISO 9001 The system for quality management, which is certified in accordance with the ISO 9001 norm, has been in force in our company for years. It implicates a structured and complete analysis of every activity and the best planning and rationalizing of all operational…
-
Certificate for designing
and producing pressurized devices H1 In 2014 we have been awarded another certificate: the certificate for designing and producing pressurized devices conform to the 2014/68/UE directive (PED pressure equipment directive) which guarantees the ability of designing and producing: ✔ tanks ✔ heat…
-
Insulations
During the last two years, following the new ERP directive, we have updated our products, equipping them with advanced insulation and dedicated to the specific capacity. Thanks to this, we are now able to offer tanks and systems with higher energy classes using different combinations of insulating…
-
Energy label
Energy related Products (ErP) All of our products for heating and producing DHW meet the measures required for reducing energy consumption, as is established by Ecodesign Directive 2009/125/EC. This will help the European Union achieve the targets established in the 20-20-20 Plan: these aim to cut…
-
Energy label
Energy related Products Product and system label The energy label for the product indicates product performance in terms of consumption, and the system label identifies the efficiency specifications of the heating and/or cooling system based on a scale expressed in Energy Classes from A+ to F. This…
-
таблицы и схемы — в просмотре
-
Tailored solutions
Contents Tailored solutions Chiller Integrated Hydronic Kits pag. 16 Free Cooling Station pag. 17 Heat Pumps Test Bench pag. 18 Heat Recovery System pag. 20 Skid pag. 21 Powerful Hydronic Kits pag. 22 Large-Sized Tanks pag. 23 www.fiorini-industries.com 13
-
таблицы и схемы — в просмотре
-
A wealth of innovative capabilities and
customized solutions Since 1979, Fiorini Industries has aimed its development strategy towards an integrated policy of innovation and cutting-edge solutions and technologies, also investing in personalized solutions and customized components and systems. Today, the company is a reference point for…
-
Chiller Integrated Hydronic Kits
Hydronic kits for storing and distributing cooled water, designed to be installed inside refrigeration machines. The company designs and manufactures customized systems upon client specifications and industrialized solutions that are applied within numerous production processes. In addition to the…
-
Free Cooling Station
The types of applications for this system are numerous. One of the most important is aimed at cooling Data Centers and operation rooms that house servers, as well as powerful computing centers that need to be cooled on a continuous basis with specified parameters. The company develops specifically…
-
Heat Pumps Test Bench
One of the most qualifying aspects of the company’s “custom” design is the large number of stations for hydraulic “chiller” testing for large conditioning systems; produced on manufacturing specifications for major commissioners worldwide. These solutions, designed for testing the end of the factory…
-
Heat Pumps Test Bench
www.fiorini-industries.com 19
-
Heat Recovery System
Integrated systems for recovering the heat,developed and not used, by heating plants and production processes. “Extra” heat energy is recovered to heat domestic or non-domestic water and “reused” when re quired. Designs are customized to meet all customer requests/needs. 20…
-
Skid
A wide range of solutions for industrial plants and processes. Small and medium-sized skid systems, equipped with electric panels and, where required, control units, all ready to be installed inside a single system through simple hydraulic and electrical connections. www.fiorini-industries.com 21
-
Powerful Hydronic Kits
Multiple pumps Hydronic kits for high power applications in heating and cooling plant, to optimize costs for first installation and subsequent maintenance. Pumps can work with on-off logic or driven by inverter. 22 www.fiorini-industries.com
-
Large-Sized Tanks
Production of large-sized tanks for external or “underground” installation. Available on vertical, horizontal execution and with fullest freedom regarding materials and connections. Can be EC marked, in compliance with Directive PED 2014/68/EU. www.fiorini-industries.com 23
-
таблицы и схемы — в просмотре
-
Gasketed and brazed
plate heat exchangers Contents Gasketed plate heat exchangers Range pag. 32 Fluid/material compatibility pag. 35 pag. 28 Accessories pag. 37 Brazed plate heat exchangers Range pag. 48 Accessories pag. 49 Tables for fast selection pag. 38 pag. 47 Tables for fast selection pag. 50 Installation…
-
Fiorini has supplied the plate
heat exchangers that equip the GST3 system aimed at the cooling of the transfer and launch stations of the Ariane Sud. www.fiorini-industries.com
-
Gasketed and brazed
plate heat exchangers Customized and efficient options for all your requirements for heat exchanging The gasketed plate heat exchangers (K and F series) and brazed plate heat exchangers (P and WP series) are the option for someone who demands efficiency and trustworthiness. Our thirty years’…
-
Gasketed plate heat exchangers
K and F series The heat exchangers (K and F series) are designed and manufactured with materials and applications which guarantee high, durable efficiency standards in residential applications as well as industrial processes. • The plates are made in high quality materials which makes it possible to…
-
Gasketed plate heat exchangers
K and F series Environment and sectors of application Wherever a heat exchange between two fluids takes place, the Fiorini plate heat exchangers guarantee a series of significant advantages: • high efficiency • long life span • low cost • compact dimensions • possibility to expand • easy maintenance…
-
Principles
Single passage In the version with a single passage the fluid which runs through the exchangers, goes through one canal (the space between two adjacent plates). This is the most commonly used layout. Multiple passage In this version the thermal length of the exchanger increases with the number of…
-
Main components
Legend 1. anterior plate 2. mid plate 3. posterior plate 4. fixed cover 5. movable cover 6. tie rod 7. coupling 8. gaskets Fiorini Plate heat exchangers are designed to ease access and maintenance. Furthermore, its modularity allows to increase number of the plates according to the heat exchange…
-
Gasketed plate heat exchangers
-
DN 200
-
Available materials
Plates Model K serie Gaskets AISI 304 AISI 316L TITANIO - ✔ ✔ Covers NBR EPDM VITON PAINTED STEEL ✔ ✔ - ✔ Tie rod AISI GALVANIZED AISI 304/316 STEEL 304/316 ✔ F serie (up to DN50) - ✔ ✔ ✔ ✔ ✔ ✔ F serie (from DN100) ✔ ✔ ✔ ✔ ✔ ✔ Legend: ✔ standard upon request - not available F…
-
Fluid/material compatibility
In the table, some guidelines for the correct combination of materials are outlined. Plates Fluid type WATER WATER & GLYCOL Fluid FOOD OTHER FLUID NBR EPDM STAINLESS NYLON STEEL (TMAX 50°C) ✔ ✔ ✔ ✔ ✔ ✔ ✔ water (tmax > 110°c) - ✔ ✔ - ✔ ✔ - ✔ water demineralized - sea water (NaCl) - chlorinated water…
-
Couplings
-
Insulation box, Condensate collection tub, Feet set
-
INSTANTANEOUS DHW with LOW temperature source
-
INSTANTANEOUS DHW with HIGH temperature source
-
Project conditions 1
-
Project conditions 2
-
HEATING with HIGH temperature endpoints
-
таблицы и схемы — в просмотре
-
HEATING with LOW temperature endpoints
-
HEATING for CHLORINATED pool
-
HEATING with Thermal Solar
-
Brazed heat exchangers
P and WP series The brazed plate heat exchangers (P and WP series) are used in heating, cooling and heat recuperation systems. The quality of the parts and the brazing process, which is carried out with care, make a trustworthy product. The plate design makes it possible to reach higher heat…
-
Brazed heat exchanger
-
Insulation, Couplings
-
INSTANTANEOUS DHW with LOW temperature source
-
INSTANTANEOUS DHW with HIGH temperature source
-
Project conditions 1
-
Project conditions 2
-
HEATING with HIGH temperature endpoints
-
таблицы и схемы — в просмотре
-
HEATING with LOW temperature endpoints
-
HEATING with Thermal Solar
-
Plant Solutions
Instantaneous DHW (see SET pag. 218) Legend 1. Fiorini Puffer PFA (see 240) 2. Expansion vessel 3. Dirt separator 4. Sanitary charging pump 5. Fiorini plate heat exchanger 6. Sanitary recirculation pump 7. ThermostaticDHWmixer 8. Bacteriostatic coldwater filter Hydraulic adduction net Thermal source…
-
Plant Solutions
Separation between thermal source and device (Closed expansion tank) Legend 1. Biomass heat generator 2. Primary circuit pump 3. Primary safety valve 4. Deaerator 5. Fiorini plate heat exchanger 6. Three way mixing valve 7. Dirt separator 8. Booster pump of the thermal device 9. Safety unit…
-
Plant Solutions
Systems for swimming pools Legend 1. Pool water filter 2. Pool pump 3. Pool regulation valve 4. Fiorini plate heat exchanger 5. Exchanger charging pump 6. Pool water treatment unit 7. Pool 8. Copper bypass Systems for solar thermal Legend 1. Fiorini Puffer PFA (see 240) 2. Expansion vessel 3.…
-
For the correct dimensioning of an exchanger, at least 5 data on 7 * are mandatory and meet the following conditions: • T.IN HOT > T.OUT COLD • T.IN COLD < T.OUT HOT • Temperatures and flow rates consistent with thermal power If you do not know all the required data, describe the type of application…
-
таблицы и схемы — в просмотре
-
Refrigeration and Heat Pumps
Integrated Solutions Cold Water Storage Tanks INERTIAL TANKS Contents pag. 66 MINI-HC (Hot & Cold) pag. 68 VKG-HC (Hot & Cold) pag. 70 VKG (carbon steel) pag. 72 VK (galvanized) pag. 74 VKT (enamelled) pag. 76 VKX (stainless steel) pag. 78 VKS (internal baffles) pag. 80 VKD (conveyors pipes) pag. 82…
-
www.fiorini-industries.com
-
Refrigeration and Heat Pumps
Integrated Solutions INERTIAL TANKS Efficiency and High-Performance: our goal Our line of refrigeration systems contains buffer tanks and hydronic kits, which are designed to improve the functioning and performance of even the most evolutionary air-conditioning systems. We have a broad range of…
-
Because of our broad range of buffer tanks, we can offer the best solution for every possible installation. We offer the following products: MINI40 - MINI80 Carbon steel External anti-rust painting Anti-condensate insulation Can contain hot and chilled water as well in heating or cooling devices…
-
INERTIAL
TANKS VKT Carbon steel Internal enamelling Anti-condensate insulation For devices which need anti-corrosive protection and which are also compatible with most antifreeze liquids. To be used in Layout 1 or Layout 2 (single and double loop) installations. VKX Stainless steel Anti-condensate insulation…
-
MINI-HC Serie (Hot & Cold wall-mounted)
The MINI-HC series includes heat sink tanks for "Hot & Cold" plants suitable for use with heat pumps, perform hydraulic circuit breaker functions (making the flows of the two circuits independent) and the thermal flywheel (to minimize the heat pump starts). The MINI-HC has two additional connections…
-
MINI-HC series
-
VKG-HC, VKGE-HC series (Hot & Cold)
1 The VKG-HC series contains insulated tanks for "HOT & COLD" applications, which are usually used to increase thermal inertia of the device. Suitable for heat pumps to avoid compressor/generator restarts. VKGHC have two additional couplings dedicated for an optional additional source. 2 Material…
-
VKG-HC, VKGE-HC series
-
VKG, VKGE series (carbon steel)
1 The VKG series includes insulated tanks for chilled water, normally used to increase the thermal inertia of the conditioning system. 2 Material: carbon steel External covering Model Type Usage VKG coloured PVC indoor VKGE embossed aluminium sheet outdoor 1 2 Insulation Capacity (l) Type Thick.…
-
Cold Water Storage Tanks: Dimensions VKG VKGE
-
VK, VKE series (galvanized)
1 The VK, VKE series has galvanized and insulated tanks for chilled water, which are usually used to increase the thermal inertia of the conditioning device. The galvanization offers protection against corrosion.. 2 Material: carbon steel Treatment: internal and external hot-dip galvanization…
-
Cold Water Storage Tanks: Dimensions VK VKE
-
VKT series (enamelled)
The tanks in the VKT series, which are internally enamelled and insulated for use with chilled water, are usually used to increase thermal inertia in Layout 2 plants. The internal enamelling ensures protection against corrosion. Material: carbon steel Treatment: Bluetech internal enamelling with…
-
VKT series
-
VKX series (stainless steel)
The VKX series includes insulated stainless steel tanks for chilled water, which are usually used to increase thermal inertia in single or double loop plants. The stainless steel protects the device against corrosion and makes it possible to use the tank in aggressive environments and in industrial…
-
VKX series
-
VKS series (internal baffles)
The VKS series includes insulated tanks for chilled water, which are usually used to increase thermal inertia in Layout 2 cooling devices. They are equipped with internal baffles which prevent preferential flow in the tank by creating perfect conditions for temperature distribution. They are…
-
VKS series
-
VKR series (conveyor pipes)
The insulated VKR tanks for chilled water are usually used to increase the thermal inertia of the Layout 2 conditioning device with a medium or high flow. They are equipped with the double loop cooling device which create a preferential circuit inside the tank. Material: carbon steel External…
-
VKR series
-
VKD series (diffusing pipes)
The insulated VKD tanks for chilled water are usually used to increase thermal inertia of the Layout 2 conditioning device. They are equipped with diffuser pipes which connect the two circuits linked to the tank. Energy is supplied or subtracted through the diffuser’s circumferential probes. In this…
-
VKD series
-
таблицы и схемы — в просмотре
-
Hydronic Kits
Contents pag. 66 Hydronic Kits pag. 86 HPT pag. 89 HP 2.0 pag. 106 VKB 2.0 pag. 118 Accessories pag. 126 www.fiorini-industries.com 87 HYDRONIC KITS Cold Water Storage Tanks
-
Hydronic kit
The VKB 2.0, HPT and HP 2.0 units are meant to optimize the performance of heating and cooling installations and to reduce the installation time. The units have an integrated system, which contains all the needed components for an efficient functioning of the hydraulic circuit (or for the…
-
Tank units for chilled water
Hydronic systems: HPT Carbon steel tank and tubes insulated with anticondensate elastomer HYDRONIC KITS The HPT units are hydraulic units with buffer tanks designed to reduce the production time of conditioning and cooling systems. They can be equipped with all different kinds of water coolers. The…
-
Layout 1 - STANDARD
Layout 1 Features: Hydronic kit, chiller and system connected in series, hence the water flow is constant throughout the plant. NOTE: All HPT Fiorini standard kit kits are Layout Supply limit of HPT group 9 10 HPT GROUP 14 13 Legend 1. Storage tank 2. Y filter. Optional, supplied non-assembled 3.…
-
HPT hydronic system
Layout 2 - SPECIAL VERSION Layout 2 Features: Hydronic Kit and Chiller create the primary circuit, Hydronic Kit and Plant create the secondary circuit. Hence, the two circuits have independent flow rates. NOTE: Pump unit supplied only on one of the two circuits. 5 HYDRONIC KITS Supply limit of HPT…
-
HPT hydronic system
Layout 3 - SPECIAL VERSION Layout 3 features: Hydronic Kit and Chiller create the primary circuit, Hydronic Kit and the system create the independent secondary circuit. Then the two circuits have independent flow rates. NOTE: Pump assembly supplied on both circuits. Supply limit of HPT group HPT…
-
HPT: components
Horizontal HPT Vertical HPT HYDRONIC KITS Components 12 2 Components 1 Tank 1 Tank 2 Circulator 2 Circulator 3 Expansion vessel 3 Expansion vessel 4 On-off valve 4 On-off valve 5 Automatic ventilation system 5 Automatic ventilation system 6 Pressure relief valve 6 Pressure relief valve 7 Safety…
-
HPT: dimensions and connections
-
HPT-V 100-200
-
Prevalence and pressure
-
таблицы и схемы — в просмотре
-
HPT Layout 1 Codes
-
таблицы и схемы — в просмотре
-
vertical distribution
-
horizontal distribution
-
capacity of the expansion vessel
Max water content in the device and the dimensions of the expansion vessel On the first chart, the max water content in the hydraulic device which is compatible with the capacity of the expansion vessel (supplied with every HPT model) and with the start-up value of the safety valve (3 bar for all…
-
Preload of the expansion vessel
Legend H: height of the device in meters P: preload of the expansion vessel in bar If the result of the preload value is less than the standard value, no steps should be taken. This means that for every installation with a height below 12.25 m, the preload of the expansion vessel should be 1.5 bar.…
-
HPT accessories
1 Programmable timer for alternating pumps In the dual pump configuration, the timer can be used to handle alternating pump operation at specified time intervals. Without the timer, the alternating pump operation occurs at each startup of the group. Default alternation every 48 hours programmable. *…
-
HPT accessories
4 HYDRONIC KITS Filter (special version) Mesh filter, with 1000 micron holes, can be placed outside the unit to protect the pumps from any impurities in the equipment. see page: 133 8 Balancing valves (special version) Valve can be connected externally to balance the flow within the circuit. see…
-
HP 2.0
Hydronic system The HP 2.0 units are hydraulic stations meant to reduce the set-up time of the conditioning and cooling devices. They can be linked to any kind of water cooler. The HP unit has: Piping insulated with anti-condensate elastomer • piping insulated with anti-condensate elastomere •…
-
hydraulic chart
Features: Hydronic kit, chiller and plant connected in series, hence the water flow is constant throughout the plant. NOTE: All HPT Fiorini standard kit kits are designed according to the following chart. HYDRONIC KITS Supply limit of HP 2.0 group 12 HP 2.0 Group Legend 1. Circulator 2. Shut-off…
-
HP 2.0 hydronic system
components Components 108 1 Switchboard 2 Circulation pump (version with double pump, optional) 3 Removable bolted panel 4 Hinged panel 5 Shut-off valve 6 Water outlet 7 Water inlet 8 Pressure transmitter (only version with inverter) 9 Check valve (only version with double pump) 10 Ventilation grid…
-
таблицы и схемы — в просмотре
-
flow (m3/h)
-
1 pump
-
HP 2.0 hydronic systems: Capacity
of the circuit and the expansion vessel Max water content in the device and dimensions of the expansion vessel On chart 1 the max water volume in the hydraulic installation is indicated, compatible with the capacity of the expansion vessel and applicable to al HP 2.0 models. The safety valve also…
-
HP 2.0 preload of the expansion vessel
Legend H: height of the device in meters P: preload of the expansion vessel in bar Should the preload value be less than the standard value, no intervention has to be carried out. This means that an installation with a height of less than 12.25 meters has a preload of 1.5 bar. In this case the…
-
HP 2.0: accessories
1 Programmable timer for alternating pumps In the dual pump configuration, the timer can be used to handle alternating pump operation at specified time intervals. Without the timer, the alternating pump operation occurs at each startup of the group. Default alternation every 48 hours programmable. *…
-
7 4 HYDRONIC KITS Inverter (special version) Each pump can be operated by an inverter. The units equipped with inverters have a pressure sensor, 0-10 bar, which communicates with the inverter with 4-20 mA signal. All adjustment parameters are pre-loaded during the test run at the company. The user…
-
The VKB 2.0 units are buffer storage tanks with accessories (without circulation pump) designed in
order to significantly reduce the set-up time for the conditioning and cooling devices. With all hydraulic components which are indispensable for the correct functioning of the hydraulic circuit for the distribution of chilled water. The components can be coupled with all kind of water coolers. The…
-
VKB 2.0 Layout 1 STANDARD
Hydronic kit, chiller and plant connected in series, so constant water flow throughout the plant. Legend HYDRONIC KITS 1. Buffer unit, vkb 2.0 Series 2. Cooling unit/heat pump 3. Primary pump unit 4. Primary pump unit (redundant) 5. Filling unit Hydronic systems VKB 2.0 Layout 2 SPECIAL VERSION…
-
VKB 2.0 Description of the main components
• Storage tank The storage tank is made of varnished carbon steel plates and is insulated with closed cell elastomer . This type of insulation, guarantees an excellent resistance to condensate formation. • Fill up valve This valve refills the hydraulic circuit in the demand peak phase as well as…
-
Vessel
-
VKB 2.0 hydronic systems: Capacity
of the circuit and the expansion vessel Max water content in the device and dimensions of the expansion vessel On chart 1 the max water volume in the hydraulic installation is indicated, compatible with the capacity of the expansion vessel and applicable to all VKB 2.0 models. The safety valve also…
-
VKB 2.0 preload of the expansion vessel
P bar - H/10,2 + 0,3 H HI = 12,25 m H=0m P bar - 1,5 bar Legend H: height of the device in meters P: preload of the expansion vessel in bar Should the preload value be less than the standard value, no intervention has to be carried out. This means that an installation with a height of less than…
-
VKB 2.0 accessories
1 From threaded to flanged galvanized connections The codes and prices below are for single piece. Original connection 1”1/2 2” 2”1/2 3” 4” 2 Transformed connection uni-en pn 16 Code DN 40 838081200X DN 50 838081201X DN 50 838081202X DN 65 838081203X DN 65 838081204X DN 80 838081205X DN 80…
-
VKB 2.0 accessories
6 HYDRONIC KITS Filter (special version) Mesh filter, with 1000 micron holes, can be placed outside the unit to protect the pumps from any impurities in the equipment. see page: 133 6 Balancing valves (special version) Valve can be connected externally to balance the flow within the circuit. see…
-
таблицы и схемы — в просмотре
-
pag. 66
Hydronic Kit pag. 86 Accessories pag. 126 Cold Water Storage Tanks pag. 128 HPT pag. 132 HP 2.0 pag. 132 www.fiorini-industries.com VKB pag. 132 127 ACCESSORIES Cold Water Storage Tanks
-
Standard Accessories for Cold Water Storage Tanks
Galvanized Connections Adapters from threaded to flanged type Galvanized Connections Adapters from threaded to Victaulic type The codes and prices below are for single item. The adapter must be screwed onto the existing connection. The codes and prices below are for single item. The adapter must be…
-
Special versions for Cold Water Storage Tanks
Special versions change the conformation of the products and hence the sales code will be different depending on the customisation required. Fiorini is able to provide any tailored solution quickly, providing the customer with the support they need to guide them to the solution that best suits their…
-
Tank Layout
This page guides you in choosing the couplings geometry/position of a chilled water tank. When requesting a quote, please specify the chosen layout and any changes. STANDARD TL1 4 standard couplings TL5 2 special couplings right TL9 2 special couplings, top left and bottom front 130 TL2 4 special…
-
Standard Accessories for Hydronic kits
Accessories for HPT kit Code Description Price 838081000X DIFFERENTIAL PRESSURE SWITCH 838081104X TIMER OPTION 48H* 838080917X ANTIVIBRATING FEET FOR HPT 300/500L 838080936X ANTIVIBRATING FEET FOR HPT 750/1000L 838080938X ANTIVIBRATING FEET FOR HPT 1500/2500L * WARNING If the system operates 24…
-
Special versions for Hydronic kits
Special versions change the conformation of the products and hence the sales code will be different depending on the customisation required. Fiorini is able to provide any tailored solution quickly, providing the customer with the support they need to guide them to the solution that best suits their…
-
таблицы и схемы — в просмотре
-
Hot water systems
Contents Domestic Hot Water Storages FLEXY INOX pag. 140 DHW STORAGES FLEXY pag. 138 pag. 134 Indirect Water Heater pag. 142 Fast Heaters for DHW pag. 186 Fresh Water Stations for DHW pag. 200 Hot Water Storage Tanks pag. 238 Thermal Solar Systems pag. 252 Accessories and Insights pag. 272…
-
www.fiorini-industries.com
-
Hot water systems
A broad range of options which make it possible to efficiently produce Domestic Hot Water for both domestic and professional use and to manage water for technical use in heating systems. We have numerous series of products dedicated to the production and storage of hot water. Those products meet…
-
FLEXY
-
Inertial tanks for DHW
-
FLEXY INOX
The FLEXY INOX range consists of inertial tanks for domestic hot water made of stainless steel which is highly resistant against corrosion. The tanks are available in several capacities from 200 to 5000 litres. They are equipped with very powerful flexible insulation, externally covered in PVC and…
-
таблицы и схемы — в просмотре
-
www.fiorini-industries.com
-
Water heaters
Indice Domestic Hot Water Storages pag. 134 Fixed Exchangers Water Heaters pag. 144 SMART 2 pag. 148 SMART 2 SOLAR KIT pag. 152 SMART 1 HP pag. 156 SMART 2 HP pag. 160 SMART 1 INOX pag. 164 SMART 2 INOX pag. 168 INTERSPACE TANK pag. 172 WATER HEATERS SMART 1 pag. 144 Removable Exchangers Water…
-
Glass lined water heater with fixed internal
heat exchanger – SMART 1 The Smart 1 range consists of water heaters for the production of domestic hot water with a single fixed heat exchanger, available in several capacities, from 200 to 3000 litres. They are equipped with different type of insulation (see chart below), external PVC coating, a…
-
таблицы и схемы — в просмотре
-
for SMART 1 series
-
for SMART 1 series
Legend 1 Fiorini DHW storage tank 2 Magnesium anode 3 Gas water heater / additional source 4 Filling unit 5 Cold water bacteriostatic filter 6 DHW recirculation pump 7 Thermostatic DHW mixer 8 Safety group 9 Electrical resistor (optional) WATER HEATERS Pressure loss m.c.a./m2 Pressure loss fixed…
-
Glass lined water heater with two fixed
internal heat exchangers – SMART 2 The Smart 2 range consists of Water heaters for the production of domestic hot water with a double fixed heat exchanger, available in several capacities (from 200 up to 3000 litres). They are equipped with different type of insulation (see chart below), external…
-
таблицы и схемы — в просмотре
-
for SMART 2 series
-
for SMART 2 series
Legend 1 Fiorini DHW storage tank 2 Magnesium anode 3 Gas water heater / additional source 4 Solar thermal return group 5 Cold water bacteriostatic filter 6 DHW recirculation pump 7 Thermostatic DHW mixer 8 Fiorini solar panel 9 Safety group 10 Electrical resistor (optional) WATER HEATERS Pressure…
-
Glass lined water heater with a solar power
station – SMART 2 SOLAR KIT Water heater for the production of domestic hot water with a double fixed heat exchanger and a solar power station S2 SOLAR 30 - 25/6. The capacity is 300l. The water heater is equipped with very thick high-density rigid polyurethane insulation, external PVC coating, a…
-
таблицы и схемы — в просмотре
-
for SMART 2 SOLAR KIT series
DHW production TiACS = 10°C • • • • • • • Lower Exchanger Ta = 50°C TuACS = 45°C Ta = 60°C TuACS = 45°C Surface area Surface area Nominal flow kW (d) l/10 min. (e) l/10 min. (f) m2 m2 mc/h 1,1 1,4 Capacity Ti TuACS= 45°C TuACS = 60°C l °C l/h (a) kW (b) l/h (c) 1007 300 Upper Exchanger a continuous…
-
for SMART 2 SOLAR KIT series
Pressure loss m.c.a./m2 Pressure loss fixed heat exchanger The pressure loss in the chart is for a tube with a surface of 1 m2. To know the overall pressure loss, multiply the value with the exchange surface. WATER HEATERS Flow l/h S2 SOLAR 30 solar unit The S2 SOLAR 30 solar unit is the ideal…
-
Glass lined water heater with a fixed heat
exchanger for Heat pumps – SMART HP The HP range consists of water heaters for the production of domestic hot water with a double spiral singleheat exchanger with a large surface, to be connected with a heat pump. The heaters are available in several capacities, from 300 to 1000 l and are insulated…
-
таблицы и схемы — в просмотре
-
for SMART HP series
DHW production TiDHW = 10°C Surface area Nominal flow kW (b) l/10 min. (e) m2 mc/h 2236 91 691 3,8 4,0 2432 4,0 3390 138 1362 6,5 4,0 1227 80 3390 138 1628 6,5 4,0 Ti l °C l/h (a) 1000 • • • • Ta = 50°C TuDHW = 45°C Capacity 300 Exchanger TuDHW= 45°C a continuous DHW flow with TuDHW= 45°C b power of…
-
for SMART HP series
Pressure loss m.c.a./m2 Pressure loss fixed heat exchanger The pressure loss in the chart is for a tube with a surface of 1 m2. To know the overall pressure loss, multiply the value with the exchange surface. WATER HEATERS Flow l/h www.fiorini-industries.com 159
-
Glass lined water heater with fixed double heat
exchanger for Heat pumps – SMART HP 2 The HP 2 range consists of water heaters for the production of domestic hot water with a double fixed heat exchangers, one simple and one with double spiral with a large surface, to be coupled with a heat pump together with additional sources (solar, gas water…
-
таблицы и схемы — в просмотре
-
for SMART HP 2 series
DHW production TiACS = 10°C Ta = 50°C TuACS = 45°C Upper exchanger surface Lower exchanger surface Capacity Ti TuACS= 45°C l °C l/h (a) kW (b) l/10 min. (e) 50 553 22,5 435 80 1501 61,1 2334 Exchanger m2 m2 2,2 1 4,8 1,8 Nominal flow mc/h 1,0 2,6 1,5 4,1 • a continuous DHW flow with TuDHW= 45°C • e…
-
for SMART HP 2 series
Pressure loss m.c.a./m2 Pressure loss fixed heat exchanger The pressure loss in the chart is for a tube with a surface of 1 m2. To know the overall pressure loss, multiply the value with the exchange surface. WATER HEATERS Flow l/h www.fiorini-industries.com 163
-
exchanger - SMART INOX 1
The SMART INOX 1 range consists of water heaters for the production of sanitary hot water with a single fixed heat exchanger. They are available in several capacities, from 200 up to 3000 litres and have different insulation with respect to capacity (see chart below) and coated externally in PVC and…
-
таблицы и схемы — в просмотре
-
for SMART INOX 1 series
-
for SMART INOX 1 series
Legend 1 Fiorini DHW storage tank 2 Magnesium anode 3 Gas water heater / additional source 4 Filling unit 5 Cold water bacteriostatic filter 6 DHW recirculation pump 7 Thermostatic DHW mixer 8 Safety group 9 Electrical resistor (optional) WATER HEATERS Pressure loss fixed heat exchanger 2 A B 1,8…
-
exchanger - SMART INOX 2
The SMART INOX 2 range consists of water heaters for the production of domestic hot water with a double fixed heat exchanger. They are available in several capacities, from 200 up to 3000 litres and have different insulation with respect to capacity (see chart below) and coated externally in PVC and…
-
таблицы и схемы — в просмотре
-
for SMART INOX 2 series
-
for SMART INOX 2 series
Legend 1 Fiorini DHW storage tank 2 Magnesium anode 3 Gas water heater / additional source 4 Solar thermal return group 5 Cold water bacteriostatic filter 6 DHW recirculation pump 7 Thermostatic DHW mixer 8 Fiorini solar panel 9 Safety group 10 Electrical resistor (optional) WATER HEATERS Pressure…
-
Enamelled interspace tanks
The interspace tanks are intended for the production of domestic hot water. The heat exchange takes place through the outer mantle of the tank to which a cavity adheres, in which water from the boiler flows. The high exchange area ensures: • efficient operation, • high power exchanged, • uniform…
-
таблицы и схемы — в просмотре
-
Water heater
with tube heat exchanger – BOIL The BOIL range consists of water heaters with a tube heat exchanger for the production of domestic hot water. There are several capacities, from 200 up to 5000 litres. They are equipped, depending on the capacity, insulation (see chart below), an external cover in PVC…
-
таблицы и схемы — в просмотре
-
Water heater with tube heat exchanger
BOIL INOX The BOIL INOX range consists of water heaters with tube heat exchanger for the production of domestic hot water. They are available in several capacities, from 200 up to 5000 litres and equipped with different type of insulation (see chart below), external cover in PVC and a magnesium…
-
таблицы и схемы — в просмотре
-
for BOIL and BOIL INOX series
-
таблицы и схемы — в просмотре
-
Customized water heater with removable
exchanger The concept of the Boil custom range has been introduced to give the user the possibility of composing their own system for domestic how water production by coupling it with several types of storage tanks and exchangers. This enables the conception of flexible solutions for every type of…
-
Customized water heater with
removable exchanger The concept of the Boil custom range has been introduced to give the user the possibility of composing their own system for domestic how water production by coupling it with several types of storage tanks and exchangers. This enables the conception of flexible solutions for every…
-
Customized water heater with removable
-
Bundle tube heat exchanger
Water only Steam only Couplings legend D Drain N1 Exchanger inlet/outlet N2 Exchanger inlet/outlet T Vent 1 Gasket without cross-beam 2 Bundle tube heat exchangers 3 Gasket with cross-beam 4 Head Surf. m2 Power* kW Lt mm Øext mm Øhe mm N1 inch N2 inch Z1 mm Surface m2 Volume dp l mca 0,5 12,2 1" 1"…
-
Copper spiral coil
Compatibility chart for copper spiral coil and storage tank Surface m2 Capacity l 0,82 1,38 1,53 2,27 3,1 4,54 5,26 6,34 200 ✔ ✔ ✔ 300 ✔ ✔ ✔ 500 ✔ ✔ ✔ ✔ ✔ 800 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 1000 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 1500 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 2000 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 2500 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 3000 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 4000 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔…
-
Portata [lt/min]
-
www.fiorini-industries.com
-
Fast Heaters for DHW
Contents Domestic Hot Water Storages pag. 134 Indirect Water Heater pag. 142 Fast Heaters for DHW pag. 186 AFK pag. 188 AFW pag. 190 AFK-HD pag. 197 pag. 200 Hot Water Storage Tanks pag. 238 Thermal Solar Systems pag. 252 Accessories and Insights pag. 272 www.fiorini-industries.com 187 FAST HEATER…
-
Kit AFK
The AFK kit consists of a high efficiency inspectable plate heat exchange unit, fittings and circulation pump. The systems for the rapid production of domestic hot water combine an AFK Kit with an storage tank chosen freely within the FLEXY and BOIL ranges. The possibility of combining AFK kits with…
-
Kit AFK
FLEXY series pag. 138 FLEXY INOX series pag. 140 Size of the exchanger Power kW K042/09 35 14* Accessory 843090014X AFK insulation kit for heat exchanger and pipe fittings 822120028 SLC electronic control unit (see. pag. 274) Price FAST HEATER Kit AFK Code Continuous DHW production l/h dP Primary…
-
Kit AFW
The AFW kit consists of a high efficiency brazed plate heat exchange unit, fittings and circulation pump. The systems for the rapid production of domestic hot water combine an AFW Kit with an storage tank chosen freely within the FLEXY and BOIL ranges. The possibility of combining AFW kits with…
-
Kit AFW
Size of the exchanger WP4/14 Power kW 35* 14** FAST HEATER Kit AFW FLEXY series pag. 138 FLEXY INOX series pag. 140 AFW insulation kit Continuous DHW production l/h dP Primary kPa Couplings inch Min-max power of the pump W Tension V/Ph/Hz Min-max current A 859 18 1”1/4 3-140 230/1/50 0,04-1,1 WP4/20…
-
Technical information - DHW fast
production units – AFK and AFW series Dimensions The AFK and AFW DHW production station is different from regular water heaters because of the presence of a high efficiency plate heat exchanger. This feature ensures that the available power from the energy source is fully used even when the…
-
Performance with K042/09 plate heat exchanger
-
Performance with K042/21 plate heat exchanger
-
Performances with K042/33 plate heat exchanger
-
Fast selection charts for AFK and AFW
The two charts below can help you with the selection of the AFKX unit in some standard circumstances. Hotel rooms Storage tank capacity 200 l Exchanger model 300 l 500 l 750 l 1000 l 1500 l 2000 l K042/ 9 / WP4/14 * * K042/15 / WP4/20 * K042/21 / WP4/30 K042/25 / WP4/40 K042/33 / WP4/50 Consumption…
-
Heat exchanger group for domestic hot water
production – AFK-HD The AFK-HD system for the fast preparation of Domestic Hot Water can be coupled with storage tanks that are already installed in small, medium-sized and large settings. The available thermal exchange units can be coupled with all storage tank of the FLEXY, FLEXY INOX, BOIL and…
-
AFK-HD
Legend UTENZA ACS DOMESTIC HOT WATER AFK HD Stainless steel recirculation pump 2 Gasketed plate heat exchanger 3 Probe holder 4 Flow rate regulator 5 Safety valve 6 Drain valve 7 Electronic control panel (optional) 8 Output signal for primary circuit 4 SORGENTE TERMICA HEATING SOURCE Performances…
-
таблицы и схемы — в просмотре
-
www.fiorini-industries.com
-
Fresh Water Stations for DHW
Contents Domestic Hot Water Storages pag. 134 Indirect Water Heater pag. 142 Fast Heaters for DHW pag. 186 Fresh Water Stations for DHW pag. 200 AQUAMATIC pag. 202 SET 2.0 wall-mounted pag. 218 Mounted SET pag. 227 pag. 238 Thermal Solar Systems pag. 252 Accessories and Insights pag. 272…
-
Instantaneous DHW (Domestic Hot Water)
production unit with integrated storage tank Italian style, innovation and technology AQUAMATIC is an innovative product consisting of an inertial heat storage system coupled with an instantaneous hot water production unit. Everything is enclosed in a uniquely designed element, which combines style…
-
Installation schema and components
IDEA Legend IDEA Flex Galileus heat pump (outdoor unit) 2 IDEA Flex Galileus heat pump (indoor unit) 3 Fresh water station AQUAMATIC 4 Built-in inertial tank AQUAMATIC 5 Built-in three way diverter valve 6 Safety group 7 Fiorini solar panel 8 Solar station no pump 9 DHW recirculation pump Components…
-
Available Versions
The AQUAMATIC system is available with three different storage capacities and in three different versions. The versions differ in the presence of a second heat exchanger for additional sources and in the possibility of managing the additional heat source through an electronic pump and the specially…
-
Performance AQUAMATIC
Quantity of domestic water produced in l/m with different storage temperatures and different outlet temperatures 45 T out 40°C T out 42°C T out 45°C T out 48°C 40 35 DHW flow l/m Primary temperature °C For example, if Taccumulo =52°C And TDHW =45°C, the AQUAMATIC guarantees a flow of approximately…
-
Performance AQUAMATIC
Output in kW of the additional heat exchanger Output in kW of the additional heat exchanger in fucntion of the variation of the value ΔT between the temperature of the integrative source and the storage temperatore. Only for AQUAMATIC PLUS and AQUAMATIC SOLAR. AQUAMATIC 300serpentino coil 1,4 m2 1,4…
-
Dimensions Aquamatic
-
Dimensions AQUAMATIC Plus
-
Dimensions AQUAMATIC Solar
-
Installation chart AQUAMATIC
Legend 1 IDEA FLEX Galileus heat pump (outdoor unit) 2 IDEA FLEX Galileus heat pump (indoor unit) 3 Fresh water station AQUAMATIC 4 Diverter valve kit for stratification 5 Fiorini DHW recirculation kit 6 Heating system Installation chart AQUAMATIC Plus Example 1 (Heating fireplace / stove) Legend 1…
-
Installation chart AQUAMATIC Plus
Example 2 (Thermal solar) Legend 1 IDEA FLEX Galileus heat pump (outdoor unit) 2 IDEA FLEX Galileus heat pump (indoor unit) 3 Fresh water station AQUAMATIC 4 Diverter valve kit for stratification 5 Fiorini DHW recirculation kit 6 Heating system 7 Thermal solar return group 8 Fiorini solar panel 9…
-
Standard Accessories AQUAMATIC
Several kits with accessories that can be connected to the AQUAMATIC are available. Some of those can be supplied already assembled in our factory. Kit Electrical Resistor The kit with an electrical resistor (integrated) guarantees the a constant storage temperature, even in case of insufficient…
-
Kit External deviation valve for stratification
The kit with external deviation valve makes it possible to take the water for the return to the heat pump from the lower parts of the tanks instead of the middle in function of the temperature difference between the two zones in the tank. In this way the temperature of the water that returns to the…
-
Accessory – storage tank for installation
A tank that can be put onder the AQUAMATIC when you need an inertial flywheel dedicated exclusively to the heating installation of cool water installation. Reccommended in all case in which you have a heat pump as thermal source. Its installation makes it possible for the heat pump to operate at a…
-
Installation chart accessory
Accessory Storage with AQUAMATIC (1 source) Legend 1 IDEA FLEX Galileus heat pump (outdoor unit) 2 IDEA FLEX Galileus heat pump (indoor unit) 3 Fresh water station AQUAMATIC PLUS 4 AQUAMATIC built-instorage tank 5 Fiorini DHW recirculation kit 6 Heating/cooling system Accessory Storage with…
-
The recirculation kit makes it possible to check the pump of the domestic recirculation circuit (circulator not supplied). Possible settings: ✔ Programming the recirculation in time slots ✔ Programming the recirculation based on the temperature of the recirculation ring. ✔ Programming the…
-
Solar unit without pump for
AQUAMATIC SOLAR Solar unit with double tube to couple with the AQUAMATIC SOLAR when a pre-assembled solar station is needed that integrates and completes the functions already present in the AQUAMATIC SOLAR. The solar unit with double tube, completely assembled and tested, consists of: Return…
-
SET 2.0 wall-mounted fresh Water Stations
A plug and play system for transferring heat from the technical water storage tank with a programmable control unit and a circulator. The SET 2.0 unit ensures the DHW production with a limited formation of chalk and at a temperature chosen by the user. The heat exchange is carried out by the AISI…
-
Available versions
Fiorini offers two versions of the SET 2.0 fresh water station. The difference between the two is in the control unit: one version with a limited number of functions (SET 2.0 S) and another version with many functions and control settings (SET 2.0 L). Below the main features of the two units are…
-
SET 2.0 (S and L) thermal performance
-
SET 2.0 (S and L) thermal performance
70 SET 2.0 25 DHW circuit pressure loss (kPa) Flow of DHW to be distributed [l/min] 140 FRESH WATER STATION DHW circuit pressure loss (kPa) 120 SET 2.0 SET 2.0 Flow of DHW to be distributed [l/min] www.fiorini-industries.com 221
-
P1
211 90 P2 1" 105 1" Lt Wt Ht 1" 211 1" 90 A1 105 A2 SET 2.0 (S e L) technical information 25 35 Electrical supply (V/Ph/Hz) 40 230/1/50 Power of primary pump min/max (W) 2/52 Absorption of primary pump min/max (A) 0.04/0.52 Max power of the recirculation pump (can be managed from the control…
-
in combination with the water storage tank
Legend 1 SET fresh water station 2 Fiorini PFB water storage tank 3 Safety group 4 Solar panel 5 Thermal solar return 6 Additional heating source 7 DHW recirculation pump 8 Cold water bacteriostatic filter Equipment FRESH WATER STATION The SET 2.0 fresh water station is delivered in a cardboard box…
-
Kit to connect the SET in series
The kit to connect the SET in series is the option for all applications in which the need for Domestic hot water is very variable. In this way it is possible to connect max 8 fresh water stations and ensure a DHW production of min 2 l/m and max 800 l/min*. The electronic control units that are…
-
The recirculation kit offers multiple possibilities for the electronic control unit to control the pump of the sanitary recirculation circuit (circulator not supplied). Possible settings ✔ Programming the recirculation in time slots. The recirculation pump is activated only during the indicated time…
-
Kit with stratification valve for the storage tank
The kit makes it possible to direct the return from the fresh water station to the lower part instead of the mid part of the storage tank. Because of this, the stratification phenomenon in the storage tank is favoured and the efficiency of the entire heating system is maximized. Legend 1 SET fresh…
-
Mounted
DHW fresh water station A plug and play system for transferring heat from the technical water storage tank with a programmable control unit and a circulator. The SET unit ensures the DHW production with a limited formation of chalk and at a temperature chosen by the user. The heat exchange is…
-
Functions of the regulator
The SET fresh water station is equipped with a regulator that can execute the following functions: Efficient, electronic regulation of the velocity of the pump Graphical display Imposing the temperature of the DHW Imposing the max temperature of the DHW. This is a safety option which stops the unit…
-
Mounted SET 2.0 thermal performance
-
Mounted SET thermal performance
-
таблицы и схемы — в просмотре
-
Hydraulic performance SET
50 45 DHW circuitPerdita pressure di carico loss circuito (kPa) ACS (kPa) 40 SET -‐ SET -‐ -‐ Portata circuito ACS (l/min) Flow DHW circuit [l/m] 80 70 DHW circuit pressure lossA(kPa) Perdita di carico circuito CS (kPa) 60 SET -‐ SET -‐ 100 30 SET -‐ -‐ Portata circuito ACS (l/min) Flow DHW circuit…
-
Z3
Lt Wt Z4 Z2 Z1 Ht Model Lt mm Ht mm Wt mm Z1 mm Z2 mm Z3 mm Z4 mm SET 60 1004 SET 70 1004 1004 1004 SET 120 1004 SET 200 1220 1100 FRESH WATER STATION SET 80 SET 100 MOUNTED SET Technical information Electrical supply (V/Ph/Hz) 230/1/50 Power of primary pump max (W) Absorption of primary pump max…
-
In combination with the water storage tank
Legend 1 SET fresh water station 2 Fiorini PFB water storage tank 3 Safety group 4 Solat thermal 5 Solat thermal return 6 Heating from additional source 7 DHW recirculation pump 8 Cold water bacteriostatic filter Equipment The mounted SET fresh water station is delivered in a cardboard box with: ✔…
-
Kit to connect the SET in series
The kit to connect the SET in series is the option for all applications in which the need for domestic hot water is very variable, for example in sport centres, etc. In this way it is possible to connect max 8 fresh water stations and ensure a DHW production of min 5 l/m and max 3200 l/min*. The…
-
The recirculation kit makes it possible to opt for one of the multiple option offered by the electronic control station to control the pump of the sanitary recirculation circuit (circulator not supplied). Possible settings ✔ Programming the recirculation in time slots. The recirculation pump is…
-
Kit with stratification valve for the storage tank
The kit makes it possible to direct the return from the fresh water station to the lower part instead of the mid part of the storage tank. Because of this, the stratification phenomenon in the storage tank is favoured and the efficiency of the entire heating system is maximized. Legend 1 SET fresh…
-
таблицы и схемы — в просмотре
-
Water storage tanks
Contents Domestic Hot Water Storages pag. 134 Indirect Water Heater pag. 142 Fast Heaters for DHW pag. 186 Fresh Water Stations for DHW pag. 200 Hot Water Storage Tanks pag. 238 PUFFER pag. 240 COMBI PLUS pag. 246 pag. 252 Accessories and Insights pag. 272 www.fiorini-industries.com 239 THERMAL…
-
Hot Water storage tanks
The Puffer tanks are inertial tanks for heating installations which store non-domestic hot water. They are used in all devices powered by discontinuous power sources (e.g. solar panels, wood burners, boiler stoves, etc.) or wherever the volume of water stored in the device must be increased (e.g.…
-
Product code
-
Size PFA
-
Size PFB
-
Size PFC
-
List of components
1 PFC Fiorini Puffer 2 Safety unit 3 Heating by alternative source 4 solar thermal return unit 5 bacteriostatic cold water filter 6 Heating circuit 1 7 Heating circuit 2 8 Fiorini solar collectors 9 Heater or stove with open vessel 30 Fixed coil power Potenza[kW] [KW]per perm m22 Power 25 The chart…
-
Combi storage tank
The COMBI PLUS range consists of inertial tanks for installations which use discontinuous energy sources, such as solar power systems, biomass systems and wood burning systems. Thanks to the internal exchanger with a stainless steel corrugated tube with a large surface, the instantaneous DHW…
-
таблицы и схемы — в просмотре
-
COMBI PLUS A
-
COMBI PLUS B
-
COMBI PLUS C
-
List of components
1 PFC Fiorini Puffer 2 Safety unit 3 Heating by alternative source 4 solar thermal return unit 5 bacteriostatic cold water filter 6 Heating circuit 1 7 Heating circuit 2 8 Fiorini solar collectors 9 Heater or stove with open vessel 70 Instantaneous DHW production Produzione istantanea ACS [l/mon]…
-
таблицы и схемы — в просмотре
-
Solar Thermal Systems
Contents Domestic Hot Water Storages pag. 134 Indirect water heater pag. 142 Fast Heaters pag. 186 Fresh Water Stations for DHW pag. 200 Hot Water Storage Tanks pag. 238 Thermal Solar Systems pag. 252 COMBI SUN - Kit for DHW production and heating pag. 258 AQUA SUN - Kit for DHW production pag. 256…
-
Thermal Solar Kit for DHW production
HOT WATER AND SOLAR HEATING SYSTEM Solar energy is an inexhaustible source of energy that can be easily used both in hot water preparation and in the heating process. Solar energy helps protect the environment and ensures significant energy savings. OUR SOLUTIONS Fiorini has designed two product…
-
Thermal Solar Kit for DHW production
ADVANTAGES ❂❂ Saving money. The technology we use ensures high efficiency. Acqua Sun and Combi Sun solutions make your working environment or your household more energy-efficient which saves you money every day. The solar Thermal Kit is not expensive and can be written off. ❂❂ Value of the property.…
-
AQUA SUN Thermal Solar kit
for DHW production The Aqua Sun Kit is the easiest and most efficient way to produce hot water using solar power. There are two versions of the Aqua Sun systems which correspond to different daily needs (see ‘daily needs’ chart). 1 Principles 1. The sun heats the solar liquid in the solar collectors…
-
AQUA SUN Thermal Solar kit
for DHW production Series Code Price Energy label Composition Rif. 8 A+B+D Aqua Sun 1 838111114X Aqua Sun 1.1 838111115X CC 1 H2000+SMART2 200 C 1 H2500+SMART2 200 x2 x3 Number of persons* Solar collector 1xH2000 Kit for basic connections 1 piece 1 piece - - C Joint 4 Solar station for pumping and…
-
Thermal Solar power kit for DHW
production and heating – COMBI SUN The Combi Sun kit is the solution which makes it possible to heat domestic water and water for the heating system. There are three versions of the Combi Sun system which correspond to different daily needs and different compositions/surfaces. Principles 1. The sun…
-
Thermal Solar power kit for DHW
production and heating – COMBI SUN Series Code Price Energy label Composition Rif. 8 Combi Sun 4 838111120X Combi Sun 6 838111121X Combi Sun 8 838111122X D C 4 H2500+PFB800+SET25 D C 6 H2500+PFB1000+SET25 CD 8 H2500+PFB1500+SET40 small Residence* medium Solar collector 4xH2500 A+B+D Kit for basic…
-
H2000 - High efficiency flat plate
solar panels with aluminium tank H2000 high performance solar collector – 2 m2 with an aluminium frame for vertical and horizontal installation The new solar collector is made of profiles in high quality anticorrosive aluminium (Al Mg). Closing system with integrated perimeter gasket in vulcanized…
-
H2000 - High efficiency flat plate
solar panels with aluminium tank Assembly Technical information Gross surface (m²) 2,02 Exposed surface (m²) 1,84 Net surface (m²) 1,84 Capacity (l) 1,56 Flow Glass thickness Glass transmission coefficient Thickness of insulation Absorber high flow/low flow 3,2 mm 91% 40 mm piano covered in highly…
-
H2500 - High efficiency flat plate
solar panels with aluminium tank H2500 high performance solar collector – 2,5 m2 with an aluminium frame for vertical and horizontal installation The new solar collector is made of profiles in high quality anticorrosive aluminium (Al Mg). Closing system with integrated perimeter gasket in vulcanized…
-
H2500 - High efficiency flat plate
solar panels with aluminium tank Assembly Technical information Gross surface (m²) 2,51 Exposed surface (m²) 2,31 Net surface (m²) 2,31 Capacity (l) 1,95 Flow Glass thickness Glass transmission coefficient Thickness of insulation Absorber high flow/low flow 3,2 mm 91% 50 mm piano covered in highly…
-
Assembly and materials
Assembly and materials A broad range of installation solutions All models of the collector are available in several versions in terms of installation, fixing and materials. Depending on the functional characteristics and the type of roof (flat roof, pitched roof with tile, on sheet, etc.) it is…
-
Collector fixing systems
-
MTDC Solar regulator
The MTDC differential controller is an electronic regulator for solar power systems. It is equipped with a large LED screen which enables an efficient control of the solar power system. A very useful wizard will guide you during the start-up of the system. Step by step the wizard program will…
-
S1 SOLAR 1
Solar module The Solar module S1 SOLAR 1 is pre-assembled, tested and can be used for small solar installations. The unit consists of a single return circuit. The return circuit is equipped with: • Flow meter and flow regulator, together with fill and drain couplings • Solar circulation pump • Ball…
-
S2 SOLAR 30
Solar module The Solar module S2 SOLAR 30 is pre-assembled, tested and can be used in small and medium solar installations. It is equipped with a pre-wired regulator and temperature sensors. The unit consists of a RETURN and DELIVERY circuit. The delivery circuit comes with: • Ball valve with check…
-
S2 SOLAR 2
Solar module The two-pipe solar station consists of the following components: Return: • Flow regulator gauge 20-70 l/min • high efficiency synchronous solar circulator 0-10V command • ball valve with non-return valve 18 bar (the non-return • valve can be left out by turning the handle for 45…
-
Document to request further information
on solar thermal installations Address Client Type of residence (one family, condo) Name Name Street Street Postal code/city Postal code/city Telephone Telephone Fax Fax Requested installation Planned cost of the installation Budget € DHW (domestic hot water) Heating (room) Heating (swimming pool)…
-
Document to request further information
on solar thermal installations Installation of the solar panels Integrated in the roof Useful size of the roof m On the roof Useful height of the roof m On the façade (optional) Height of the installation m On tile Shadow yes no Other need of crane yes no orientation of the roof solar tubes (length…
-
таблицы и схемы — в просмотре
-
Accessories and Insights
Contents Domestic Hot Water Storages pag. 134 Indirect Water Heater pag. 142 Fast Heaters for DHW pag. 186 Fresh Water Stations for DHW pag. 200 Hot Water Storage Tanks pag. 238 Thermal Solar Systems pag. 252 Accessories and Insights pag. 272 for DHW storage pag. 274 storage special versions pag.…
-
Storage tanks loading controller SLC
The SLC unit is a modern electronic regulator for loads of large DHW storage tanks with a high temperature precision. They are equipped with a wide display and makes it possible to program the desired temperature in the inside of the tanks on three different peak times a day. It is possible to…
-
Magnesium anode
Capacity Description Code Magnesium anode 22x400 M8 without plug FLEXY, FLEXY INOX, BOIL , BOIL INOX, SMART INOX capacity 200÷300 l R22100003 Magnesium anode 33x500 M8 without plug "FLEXY, FLEXY INOX, BOIL , BOIL INOX, SMART INOX capacity 500÷5000 l 6000÷10000 l (N°2 pieces)” R22100004 Price Each…
-
Single-phase electrical heaters that can be integrated with
the boilers, copper heating elements, IP44 protection category, supplied with regulation thermostat (range 20-70 °C), safety thermostat (manual reset), electric cable and Schuko plug 10-16A/250V Code Price Connection GAS M Temperature safety thermostat °C Power Length L W mm 824100166 1200 365 1"1/2…
-
Special versions of DHW storages
Special executions change the conformation of the products and hence the sales code will be different depending on the special execution required. Fiorini is able to meet any out-of-the-box request quickly, providing the customer with the assistance they need to guide them to the solution that best…
-
Standard accessories for fast heaters
Insulation kit AFK for exchanger and fittings See pag 188 Insulation kit AFW for exchanger and fittings See pag 190 Code Description Price 843090014X Insulation kit for AFK Cod. SLC electronic control unit See pag 274 Code Description Price 822120028 SLC electronic control unit Accessorio Prezzo…
-
Expansion vessel
Drain valve Code Description 809040007 809040012 Price Code Description Permanent drain valve for solar power system DN20 811010061 Expansion vessel for solar power system 18 LT Permanent drain valve for solar power system DN25 811010062 Expansion vessel for solar power system 25 LT 10 811010094…
-
2-way motor-driven valve
Description Code DN25 2-way motor-driven valve, closed when not powered. 809020103 DN32 2-way motor-driven valve, closed when not powered. 809020104 Price ON/OFF motor-driven 2-way valve with red brass casing, internal elements made of brass and steel. Adjusted by electro-thermal device (manual…
-
Thermostatic Mixer tap for domestic water
Description Code Thermostatic Mixer tap for domestic water 3560°C-1” 809020151 Thermostatic Mixer tap for domestic water 3560°C-1” 1/4 809020152 Price Single burn-proof mixer tap with red brass casing for integration in hot water piping with a set of fittings. Independent adjustment and water…
-
Tank treatments
Bluetech Bluetech is an innovative treatment, which is obtained from thermosetting resins. It offers a lot of advantages in comparison to traditional treatments: • excellent resistance and stability under high temperature • excellent adhesion to the carbonized steel and high elasticity •…
-
User conditions
If you want to properly use the storage tanks and prevent malfunctions or damage, you should respect the following limitations: a) the storage tank has to be equipped with an efficient cathodic protection. b) The quality requirements for drinking and food-grade water has to be in accordance with…
-
Available protection equipment
Overpressure protection To prevent undesirable effects caused by overpressure, it is recommended to use protective devices, such as a safety valve. Since water is incompressible and it expands when heated, an adequate expansion system should be installed which can prevent a rupture in the water…
-
Regulation and precaution
Below the suggestions and information are described on how to properly manage and use the devices in accordance with the DM 37/08 law. Hot water storage Heat generators used for the production of hot water for hygienic and domestic use by various users in a residential environment have to have…
-
Guidelines for Legionella
prevention and control Environmental Conditions Long-term measures The conditions that favour the development and proliferation of Legionella bacteria are the following: • Water temperature between 25°C and 42°C • Aerobic environment • Presence of nutritive elements (slag, biofilm, iron ions, and…
-
heaters, as well as the distribution and recirculation
networks. ness seems moderately influenced by the pH levels and temperature of the water. › Filtration at point-of-use Micro-filtration allows to eliminate Legionella in the water in output at the point-of-use by employing a mechanical barrier (0.2 μm). It is a localized treatment system and easy to…
-
таблицы и схемы — в просмотре
-
Pressure tanks
Contents The P.E.D Directive pag. 292 H1 P.E.D Directive pag. 292 Classification chart for pressure vessels pag. 294 Classification chart pag. 294 Tanks pag. 296 HP - Pressurized Autoclaves pag. 298 AK - Compressed Air pag. 299 VE - Expansion vessels pag. 301 VO - Heat transfer oil pag. 302 AV…
-
таблицы и схемы — в просмотре
-
A broad range of pressurized tank, with CE mark, in accordance with the P.E.D. directive (Directive 2014/68/UE) The products are manufactured as prescribed by the P.E.D. directive, which applies to storage tanks that have to contain dangerous fluids or fluids under high pressure and/or temperatures.…
-
The PED directive (Directive 2014/68/UE) regulates the design, manufacturing and conformity valuation of pressure vessels and products submitted to a maximum allowable pressure “PS” over 0.5 bar. The CE directive aims to harmonize the nationals laws in the member states that relate to the valuation…
-
Category PED CE label Intervention by notified body Additional costs PS ≤ 0,5 Not applicable No No No Article 4 paragraph 3 Applicable No No No I Applicable Yes No Yes II Applicable Yes Project delivery without approval Inspection visit III Applicable Yes Inspection visit + project approval…
-
Tables for classification
-
таблицы и схемы — в просмотре
-
AC series Fiorini autoclaves are designed for lifting and distributing water under pressure. They are intended to form a lung of pressurized water which, if properly sized, serves to limit the number of start-ups of the pump. They are used to ensure perfect water distribution in the upper floors of…
-
16–64 bar - HP series The “HP” series consists of pressurized autoclaves, used in industrial installations to maintain constant pressure or to absorb water hammering. The HP gamma is different from the AC series because of the max operating pressure which is higher in the HP series. The models, with…
-
8, 11, 12 bar – AK series The AK pressurized air tanks are indispensable in systems that distribute compressed air. The tanks guarantee a constant flow, reduce the compressor start-ups and ensure a stable pressure in the entire distribution net to compensate consumption peaks (ex. Installations…
-
tanks, under high pressure – AP series The AP tanks for compressed air under high pressure are used in all compressed air distribution systems with elevated pressure. The AP series is different from the AK series because of the operating pressure which is superior in the AP series. The models, with…
-
pressurized water, 6, 8, 12 bar – VE series The VE expansion vessels are generally used in industrial installations in order to compensate for the volume variation of the heat transfer fluid caused by temperature variations. They have no membrane, which brings the heat transfer fluid in direct…
-
pressurized heat transfer oil – VO series The VO series are installed in industrial heaters with heat transfer oil in a closed circuit in order to compensate for the thermal expansion of the heat transfer fluid. The models, with CE label, are available in capacities from 300 up to 15.000 litres in…
-
12 bar 200ºC – AV series The AV steam accumulators are generally installed to support industrial steam generators (fast and with a forced circulation). The accumulator is the lung in applications in which the steam content of the heaters is low and not sufficient to manage the numerous transitions…
-
www.fiorini-industries.com
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.