Ceiling / Dual Discharge
General Contents . ky Ceiling / Dual Discharge ky General Contents General Features different refrigerants the following factors should be applied: This product is designed for use in cold rooms, air locks, laboratories, meat-cutting facilities, packing rooms and so on. The shape is generally low…
-
Ceiling / Dual Discharge
General Contents Test and cleaning The coils are cleaned and dehydrated in order to remove any traces of oil. Each heat exchanger undergoes a pressure and leak test with dry air at 30 bar, before being supplied with a nitrogen pre-charge. Guarantee All our products are protected under warranty for…
-
ky Top ky Product description Applications These double air flux units are designed for use in cold rooms containing fresh goods with volumes ranging from 10-150m³. The units are designed for quick and easy maintenance with immediate access to key inspection areas. This series is available as an…
-
Capacity Capacity
-
ky Top Drawings ky Weight Model Top • TGL • TBL 530 TGL33 36 TGL34 41 TGL35 50 TGL36 58 TGL37 71 TGL38 83 TBL61 22 TGL35 TBL62 25 TBL65 TBL63 34 TBL64 38 TBL65 47 TGL37 TBL66 54 TBL67 TBL67 67 TBL68 77 TBL61 130 1" GAS 740 1030 268 TGL33 TBL63 TGL32 TGL31 TGL31 12 Kg 1240 1780 2550 We reserve the…
-
ky Top ky Options Fan Motor Different fan motors suitable for different installations 6-pole, 230V/1 Ph 4-pole, 400V/3 Ph Model: ALL APPLICATIONS All Models Local safety switch wired See Electrical Data Page. Model: ALL APPLICATIONS All Models Reheating coil Use: Re heating coil for Dual Discharge…
-
ky Top ky Electrical Data Junction box for motors TGL/TBL series Function Junction box complete with screw-on cover, cable glands and terminal strip. General data Material: Plastic IP Protection Class: Min IP55 Colour: Grey RAL7035 Insulation class: II Ambient Temp.: -25°C Max +50°C Weight: 0,5 kg…
-
Junction box for "E" defrost TGL/TBL series Function Junction box complete with screw-on cover, cable glands and terminal strip. General data Material: Plastic IP Protection Class: Min IP55 Colour: Grey RAL7035 Insulation class: II Ambient Temp.: -25°C Max +50°C Weight: 0,5 kg N F INCOMING SUPPLY…
-
ky Top ky Electric Heater ALL SERIES Function The elements are designed to operate in a refrigeration field with high moisture rate. Special care is taken in selecting the power supply, cables and insulation materials. General data ELECTRICAL DEFROST Model ELECTRICAL ELEMENT DRAIN LINE COIL…
-
ky Top Code description ky Series Room Temperature Fin Spacing TGL Fruit and vegetables (from 0 to 10° C) 4,5 mm TBL Frozen food (from -18 to -25° C) 7 mm TGL TGL Green Line TBL Blue Line E S 31 A S 1) Application E Direct Expansion Evaporator W Brine Unit Cooler 2) Noise Level S 4-pole fan motor L…
-
ky BFG/BFB ky Product description Applications The double air flux series, designed for use in cold rooms for fresh and frozen goods ranging in volume from 100 to 800m3. The units are designed for quick and easy maintenance with immediate access to key inspection areas. This series is available as…
-
Capacity Capac[SC2] ity [SC3]
-
ky TFG ky Product description Applications Double air flux series, designed for use in working and packing areas, where low noise levels and low air velocity are required. Typical room volumes from 50 to 500m³. The units are designed for quick and easy maintenance with immediate access to key…
-
Capac- Capacity [SC2] ity [SC3]
-
ky BFG/BFB,TFG Options ky Terminal Box See Electrical Data Page. Model: ALL APPLICATIONS All Models Fan Motor Different fan motors suitable for different installations 6-pole, 230V/1 Ph 4-pole, 400V/3 Ph Model: ALL APPLICATIONS All Models 6-pole, 400V/3 Ph Local safety switch wired See Electrical…
-
Cabinet made entirely of stainless steel
Casework component in stainless steel AISI 304. Application Use: More information on corrosion prevention can be found in the Miscellaneous section. Model: ALL APPLICATIONS All Models Drip tray isolated Construction: Sandwich manufactured with two aluminium shells and 12mm polyethylene insulation in…
-
ky BFG/BFB,TFG ky Electrical Data Junction box for motors FG/BFB,TFG series Function Junction box complete with screw-on cover, cable glands and terminal strip. General data Material: Plastic IP Protection Class: Min IP55 Colour: Grey RAL7035 Insulation class: II Ambient Temp.: -25°C Max +50°C…
-
ky BFG/BFB,TFG ky Electric Heater ALL SERIES Function The elements are designed to operate in a refrigeration field with high moisture rate. Special care is taken in selecting the power supply, cables and insulation materials. General data N° heater P(W) ELECTRICAL ELEMENT DRAIN LINE (Optional) P(W)…
-
ky BFG/BFB,TFG ky Code description Series Room Temperature Fin Spacing G Fruit and vegetables (from 0 to 10° C) 4 mm B Frozen food (from -18 to -25° C) 7 mm BFG BFG E S 40 3 B Green Line BFB Blue Line TFG Green Line 1) Application E Direct Expansion Evaporator W Brine Unit Cooler A Ammonia Pump…
-
ky BigTop ky Product description Applications Double air flux series, designed for use in cold rooms housing fresh and frozen goods, ranging in volume from 300 to 2000m³. Unit designed for quick and simple maintenance with easy access to key inspection areas. This series is available as an…
-
Capac- Capacity [SC2] ity [SC3]
-
ky BigTop ky Options Terminal Box See Electrical Data Page. Model: ALL APPLICATIONS All Models Fan Motor Different fan motors suitable for different installations 6-pole, 230V/1 Ph 4-pole, 400V/3 Ph Model: ALL APPLICATIONS All Models 6-pole, 400V/3 Ph Local safety switch wired See Electrical Data…
-
Double drip tray isolated
Construction: Sandwich manufactured with two aluminium shells and 12mm polyethylene insulation in between. Features: The insulation prevents water from condensing on the bottom of the drip-tray and reduces the Model: ALL APPLICATIONS All Models transfer of the defrost heat into the cold room. It can…
-
ky BigTop ky Electrical Data . Junction box for motors ITR/ITB series Function Metallic junction box complete with cable glands and terminal strip. General data Protection class IP55 Operating temperature: min -25°C max +50°C Internal dimensions (HxWxD): 250x200x105mm Wall mounting type N° 5 brass…
-
Electric wiring diagram
-
Junction box for "E" defrost ITR/ITB series Function Junction box complete with screw-on cover, cable glands and terminal strip. General data Protection class IP56 Operating temperature: min -25°C max +50°C Internal dimensions (HxWxD): 80x120x50mm Fixing holes (HxW): 42x82mm max. 8mm max. diameter…
-
Electric wiring diagram
-
ky Big Top ky Electric Heater ALL SERIES Function The elements are designed to operate in a refrigeration field with high moisture rate. Special care is taken in selecting the power supply, cables and insulation materials. General data ELECTRICAL DEFROST Model DRIP TRAY COIL ITRE562B5 ITRE562C5…
-
ky BigTop ky Code description Series Room Temperature R Fruit, vegetables and meat (from 0 to 10°C) 5 mm B Frozen food (from -18 to -25° C) 7 mm Fin Spacing ITR ITR Red Line ITB Blue Line E S 56 3 B 5 E 1) Application E Direct Expansion Evaporator W Brine Unit Cooler A Ammonia Pump 2) Noise Level S…
-
Blast Freezers
General Content . ky Blast Freezers ky General Content General Features Air circulation Most of our Blast Freezers are available in the following versions: • Direct expansion Freon evaporator • Pump ammonia evaporator Freezing method Blast freezing (convection). The fans blow the air through the…
-
Blast Freezers
General Content Guide value for external pressure • Alfa Blast 150 Pa: This unit can be used for shock cooling processes where the goods (typically meat) have to be cooled quickly but not too deeply. To ensure that the air can reach the product on all sides, fans with an external pressure drop are…
-
ky AlfaBlast ky Product description Applications AlfaBlast is a unit cooler with horizontal airflow. It is ideal for shock-freeze applications in confined spaces, and offers efficient capacity to industries such as meat, poultry, fish, baked goods, dairy, ice cream, ready-meals, and in all sectors…
-
Capacity
-
таблицы и схемы — в просмотре
-
Capacity
-
Ø 630 mm
-
ky AlfaBlast ky Options Terminal Box See Electrical Data Page. Model: ALL APPLICATIONS All Models Fan Motor Special fans 150 Pa • 500 mm • 630 mm Model: ALL APPLICATIONS All Models Local safety switch wired See Electrical Data Page. Model: ALL APPLICATIONS All Models Coil Treatment / Material…
-
Insulated drip tray
Construction: Sandwich manufactured with two aluminium shells and 12mm of polyethylene insulation in between. Features: The insulation prevents water condensing on the bottom side of the drip-tray and reduces the Model: ALL APPLICATIONS All Models transfer of the defrost heat into the cold room. It…
-
ky AlfaBlast ky Electrical Data . Connection box for electric fan motor Function Junction box complete with screw-on cover, cable glands and terminal strip. General data Material: sheet of steel IP Protection Class: Min IP55 Colour: Grey RAL 7032 Insulation Class: I Ambient Temp.: min. -25°C, max.…
-
Connection box for electric defrost Function Junction box complete with screw-on cover, cable glands and terminal strip. General data Material: sheet of steel IP Protection Class: Min IP55 Colour: Grey RAL 7032 Insulation Class: I Ambient Temp.: min. -25°C, max. +50°C Weight: approx. 4Kg Dimensions…
-
CONNECTION DIAGRAM
-
ky AlfaBlast ky Electric Heater ALL SERIES Function The elements are designed to operate in a refrigeration field with high moisture rate. Special care is taken in selecting the power supply, cables and insulation materials. General data Model Drip Tray Coil N° heater P(W) N° heater P(W) ABE501A 10…
-
Drip Tray
-
ky AlfaBlast Code description ky 1 Code No. AB 150 2 E 3 S A 7 E 1) Fan type 150 Fan motor 150pa Standard pressure 2) Application E Direct Expansion ev. A Ammonia pump ev. 3) Noise level S Standard noise level L Low noise level, only for Standard pressure 4) Fan diameter 50 500 mm 63 630 mm 5) Two…
-
General Alfa Select Air Legend
Description 1 D D fan cabling (three phase) BSFT Basic Switch Board + Speed Control Temp. + Signal BI Y Y fan cabling (three phase) Basic Switch Board + Frequency Converter (Inverter) D/Y D/Y fan cabling (three phase), single speed fan motor BSI Basic Switch Board + Frequency Converter (Inverter) +…
-
ky Centrifugal Units ky General Content General Features Relative humidity T Most of our unit coolers are available in the following versions: The cold room hygrometric conditions are defined by the room temperature and the working T. At positive cold room temperatures T has an influence on the…
-
Guarantee
All our products are protected under warranty for 18 months from the shipping date. In the unlikely event of a defect occurring within the warranty period, please return the equipment or faulty part free of charge to us, where we will decide whether to repair or replace the goods . Unfortunately, We…
-
ky ISC Product description ky Applications Series with centrifugal fans, designed for sock applications and mainly in working and packing rooms above 0°C, where it is necessary to have low air velocity and uniform hygrometric conditions. Cold room capacities ranging from 150 to 1500m3. The units are…
-
Capacity
-
ky ISC ky Options Non-standard static pressure Available external static pressure: 50, 100, 200 Pa Model: ALL APPLICATIONS All Models Coil Treatment / Material Pre-coated fins: Epoxy-coated, pre-painted aluminium fins. Model: Cataphoresis treatment: An electrolytic process is achieved by submerging…
-
ky ISC ky Electric Heater ALL SERIES Function The elements are designed to operate in a refrigeration field with high moisture rate. Special care is taken in selecting the power supply, cables and insulation materials. General data ELECTRICAL DEFROST Model ELECTRICAL ELEMENT COIL DRAIN LINE N°…
-
ky ISC ky Code description Code No. ISC Series Product Room Temperature Fin Spacing ISC Daily Product from 12 to 0°C 4,2 mm S E 1) 1, 2 fans 2) Progressive Number 3) Coil size 4) Application S Direct expansion evaporation P Brine unit cooler A Ammonia pump ev. 5) Defrost A Air defrost E Electric…
-
AlfaBlue Condensers
General Contents . ky AlfaBlue Condensers ky General Contents General Features All products are designed to satisfy both commercial and industrial refrigeration, air conditioning, and retail refrigeration. All axial condensers are available in the following versions: • Vertical installation (V) •…
-
AlfaBlue Condensers
General Contents Sound Data The sound pressure level is based on the calculation (according to EN 13487) of the sound pressure level on the surface of a cuboid area which is at a 10 metre distance and is parallel to the reference envelope of the sound source. (Standard sound pressure level; annex C…
-
ky BCM - Single Fan Row ky Product description Application The Alfa Laval Condenser can be used in refrigeration and air conditioning equipment Standard design Coil The innovative heat exchanger gives excellent heat transfer with minimised refrigerant charge, thanks to the new fin corrugations…
-
Fans
Four different fan diameters are available for the BCM: 630, 800, 910, 1000 mm. Diameter 630, 800, 910, 1000 mm with three-phase motor 400V-50Hz, for 630 (L, Q, R) also single-phase 230V-50Hz. The motors come with external rotors, protection class IP 54 according to DIN 40050. This Axial Condenser…
-
Airflow [m3/h]
-
Air flow [m<super>3</super>/h]
-
Airflow [m3/h]
-
таблицы и схемы — в просмотре
-
Airflow [m3/h]
-
ky BNM NH3 - Single Fan Row ky Product description Application The Alfa Laval condenser with stainless steel tubes was specifically designed for refrigeration plants where ammonia refrigerant is used. The condensers are designed for outdoor operation. Standard design Coil The innovative heat…
-
Fans
Four different fan diameters are available for the BCM: 630, 800, 910, 1000 mm. Diameter 630, 800, 910, 1000 mm with three-phase motor 400V-50Hz, for 630 (L, Q, R) also single-phase 230V-50Hz. The motors come with external rotors, protection class IP 54 according to DIN 40050. This Axial Condenser…
-
Airflow [m3/h]
-
таблицы и схемы — в просмотре
-
Airflow [m3/h]
-
таблицы и схемы — в просмотре
-
Airflow [m3/h]
-
Weight
-
HORIZONTAL POSITION
-
Weight [Kg]
-
Switchboard and cabling
Function Model: Switchboard for supply and control of fan motors. All Models A switchboard can supply up to 8 individual motors or 8 paired motors (i.e. max. of 16 motors). Switchboard and cabling are supplied as standard for vertical installation of the unit. If you have different needs, please…
-
Multi-circuits
All models are suitable for multi-circuits, enabling more than one refrigeration system to operate with a Model: single condenser. All Models Sub-cooling circuit Sub-cooling is achieved by the use of an integrated sub-cooling section which harnesses approximately Model: 10% of the coil surface. This…
-
ky BCM/BNM - Single Fan Row ky Electrical Data Safety Switch Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic Case Cabinet Colour: Grey (Yellow-Red Knob) Protection Class…
-
Safety Switch EMC Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic case with internal copper-painted Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min IP65…
-
Terminal Box Function Connection box for electric fan motor General data Material: Plastic IP Protection Class: Min RAL 7035 Colour: Grey RAL 7035 Insulation Class: II Ambient Temp.: min. -40°C, max. +80°C Weight: Approx. 0.5Kg. Dimensions 162
-
Switch Board (Control Panel) Function Basic Version for Horizontal Installation General data Cabinet Material: Sheet steel 15/10mm zinc-coated Internal Plate: Sheet steel 20/10mm zinc-coated Protection Class: IP 55 Cabinet Colour: RAL 7035, light grey polyester paint Cabinet Doors: Opening angle…
-
Electric wiring diagram
Q1 1 3 K1 K2 K3 K4 K5 K6 (2) NOTE : (1) (2) (3) (4) EXTERNAL SHORT CIRCUIT PROTECTION MAX FUSE REMOVE JUMPERS WHEN SPEED CONTROLLER IS ORDERED NOT MOUNTED WHEN FAN SPEED CONTROLLER IS ORDERED SCHIELDED CABLE TO BE USED ONLY WHEN EMC CABLING OPTION IS REQUESTED X2 X2 X1 (1) NOTE : (1) REMOVE JUMPER…
-
Switch Board (Control Panel) Function Basic Version for Vertical Installation General data Cabinet Material: Sheet steel 15/10mm zinc-coated Internal Plate: Sheet steel 20/10mm zinc-coated Protection Class: IP 55 Cabinet Colour: RAL 7035, light grey polyester paint Cabinet Doors: Opening angle 110°…
-
Electric wiring diagram
Q1 1 3 K1 K2 K3 K4 K5 K6 (2) NOTE : (1) (2) (3) (4) EXTERNAL SHORT CIRCUIT PROTECTION MAX FUSE REMOVE JUMPERS WHEN SPEED CONTROLLER IS ORDERED NOT MOUNTED WHEN FAN SPEED CONTROLLER IS ORDERED SCHIELDED CABLE TO BE USED ONLY WHEN EMC CABLING OPTION IS REQUESTED X2 X2 X1 (1) NOTE : (1) REMOVE JUMPER…
-
Current Distribution Function Current distributors are available as optional accessories. Numerous fans can be connected. In combination with Fcontrol frequency inverters, we can deliver the current distribution with both main switch and bypass function. Features: The current distributor is equipped…
-
Frequency Converter (Inverter) Function Frequency inverter (incl. sine filter) for 3~ motors. Universal controller for refrigeration and air conditioning line input 3~ 208-480V, housing IP54, internal display. • Speed controller with manual adjustment of output voltage at the unit or via external…
-
Dimensions
-
ky BCM/BNM - Single Fan Row ky Code description Code No. BCM/BNM S 63 2 A 1) Type of noise level (number of dB(A) to reduce compared with "base" version) Turbo noise level Standard noise level Low noise level Quiet noise level Residential noise level T S* L* Q* R* - base -10 -18 -29 Fan diameter Ø…
-
ky BCD - Double Fan Row ky Product description Application The Alfa Laval Condenser can be used in refrigeration and air conditioning equipment Standard design Coil The innovative heat exchanger gives excellent heat transfer with minimised refrigerant charge, thanks to the new fin corrugations…
-
• Fan speed control
• Energy saving • Noise reduction when air temperature is below the design temperature. • Variable and efficient speed control according to the heat rejected • Better performance control • Special fans: • 480/3ph-60Hz IP54: High adaptability on every market. • IP 55: Highly durable fan to be used in…
-
Airflow [m3/h]
-
Airflow [m 3/h]
-
Airflow [m3/h]
-
ky BND NH3 - Double Fan Row ky Product description Application The Alfa Laval condenser with stainless steel tubes was specifically designed for refrigeration plants where ammonia refrigerant is used. The condensers are designed for outdoor operation. Standard design Coil An innovative heat…
-
• Fan speed control
• Energy saving • Noise reduction when air temperature is below the design temperature. • Variable and efficient speed control according to the heat rejected • Better performance control • Special fans: • 480/3ph-60Hz IP54: High adaptability on every market. • IP 55: Highly durable fan to be used in…
-
Airflow [m 3/h]
-
Airflow [m3/h]
-
таблицы и схемы — в просмотре
-
VERTICAL POSITION
-
ø20
-
ky BCD/BND - Double Fan Row ky Options Motor fans (a) Fan motor 400 V/3ph - 60Hz, IP54: Q/R for Ø 800/910/1000 and also S/L for Ø 800/910 Model: (b) Fan motor 460 V/3ph - 60Hz, IP54: Q/R for Ø 800/910/1000 and also S/L for Ø 800/910 Ø 800 (a,b) Ø 910(a,b) Ø1000 (a,b) Local safety switch wired See…
-
Switchboard and cabling
Function Model: Switchboard for supply and control of fan motors. All Models A switchboard can supply up to 8 individual motors or 8 paired motors (i.e. max. of 16 motors). Switchboard and cabling are supplied as standard for vertical installation of the unit. If you have different needs, please…
-
Multi-circuits
All models are suitable for multi-circuits, enabling more than one refrigeration system to operate with a Model: single condenser. All Models Sub-cooling circuit Sub-cooling is achieved by the use of an integrated sub-cooling section which harnesses approximately Model: 10% of the coil surface. This…
-
ky BCD/BND - Double Fan Row ky Electrical Data Safety Switch Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic Case Cabinet Colour: Grey (Yellow-Red Knob) Protection Class…
-
Safety Switch EMC Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic case with internal copper-painted Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min IP65…
-
Terminal Box Function Connection box for electric fan motor General data Material: Plastic IP Protection Class: Min RAL 7035 Colour: Grey RAL 7035 Insulation Class: II Ambient Temp.: min. -40°C, max. +80°C Weight: Approx. 0.5Kg. Dimensions 190
-
Switch Board (Control Panel) Function Basic Version for Horizontal Installation General data Cabinet Material: Sheet steel 15/10mm zinc-coated Internal Plate: Sheet steel 20/10mm zinc-coated Protection Class: IP 55 Cabinet Colour: RAL 7035, light grey polyester paint Cabinet Doors: Opening angle…
-
Electric wiring diagram
Q1 1 3 K1 K2 K3 K4 K5 K6 (2) NOTE : (1) (2) (3) (4) EXTERNAL SHORT CIRCUIT PROTECTION MAX FUSE REMOVE JUMPERS WHEN SPEED CONTROLLER IS ORDERED NOT MOUNTED WHEN FAN SPEED CONTROLLER IS ORDERED SCHIELDED CABLE TO BE USED ONLY WHEN EMC CABLING OPTION IS REQUESTED X2 X2 X1 (1) NOTE : (1) REMOVE JUMPER…
-
Switch Board (Control Panel) Function Basic Version for Vertical Installation General data Cabinet Material: Sheet steel 15/10mm zinc-coated Internal Plate: Sheet steel 20/10mm zinc-coated Protection Class: IP 55 Cabinet Colour: RAL 7035, light grey polyester paint Cabinet Doors: Opening angle 110°…
-
Electric wiring diagram
Q1 1 3 K1 K2 K3 K4 K5 K6 (2) NOTE : (1) (2) (3) (4) EXTERNAL SHORT CIRCUIT PROTECTION MAX FUSE REMOVE JUMPERS WHEN SPEED CONTROLLER IS ORDERED NOT MOUNTED WHEN FAN SPEED CONTROLLER IS ORDERED SCHIELDED CABLE TO BE USED ONLY WHEN EMC CABLING OPTION IS REQUESTED X2 X2 X1 (1) NOTE : (1) REMOVE JUMPER…
-
Current Distribution Function Current distributors are available as optional accessories. Numerous fans can be connected. In combination with Fcontrol frequency inverters, we can deliver the current distribution with both main switch and bypass function. Features: The current distributor is equipped…
-
Frequency Converter (Inverter) Function Frequency inverter (incl. sine filter) for 3~ motors. Universal controller for refrigeration and air conditioning line input 3~ 208-480V, housing IP54, internal display. • Speed controller with manual adjustment of output voltage at the unit or via external…
-
Dimensions
-
ky BCD/BND - Double Fan Row ky Code description Code No. BCD/BND S 80 2 A 1) Type of noise level (number of dB(A) to reduce compared with "base" version) Turbo noise level Standard noise level Low noise level Quiet noise level Residential noise level T S* L* Q* R* Fan diameter Ø 800mm - base -7 -16…
-
AlfaGreen Condensers
General Contents . ky AlfaGreen Condensers ky General Contents General Features All products are designed to satisfy both commercial and industrial refrigeration, air conditioning, and retail refrigeration. All axial condensers are available in the following versions: • Vertical installation (V) •…
-
AlfaGreen Condensers
General Contents Sound Data The sound pressure level is based on the calculation (according to EN 13487) of the sound pressure level on the surface of a cuboid area which is at a 10 metre distance and is parallel to the reference envelope of the sound source. (Standard sound pressure level; annex C…
-
ky AC - Single Fan Row ky Product description Application The Alfa Laval Condenser can be used in refrigeration and air conditioning equipment. Standard design Coil This innovative heat exchanger gives excellent heat transfer with minimal refrigerant costs, thanks to the new fin corrugation…
-
Capacity
-
таблицы и схемы — в просмотре
-
Airflow [m3/h]
-
таблицы и схемы — в просмотре
-
Ø 400
Ø 500 207
-
D
-
ky AC - Single Fan Row ky Options Motor fans (a) Fan motor 400 V/3ph - 60Hz, IP54: S/L for Ø 400, also Q for Ø 500; S/L/Q/R for Ø 630/800/910 Model: (b) Fan motor 460 V/3ph - 60Hz, IP54: S/L for Ø 400, also Q for Ø 500; S/L/Q/R for Ø 630/800/910 Ø 400(a,b,c) (c) Fan motor 230V/1ph - 50/60Hz, IP54…
-
Switchboard Options
R anti-condensate resistor 230Vac (operating temperature -25 ÷ +35°C) Model: C cooling fan 230Vac (operating temperature -10 ÷ +50°C) All Models F cooling fan + anti-condensate resistor Fan Speed Control Speed controller in plastic covering box, IP55, complies with EMC regulations. The FSC checks…
-
Feet
-
ky AC - Single Fan Row ky Electrical Data Safety Switch Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic Case Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min…
-
ky AC - Single Fan Row ky Code description Code No. AC 1 S A 1) Type of noise level (number of dB(A) to reduce compared with "base" version) Standard noise Low noise level level Fan Ø 400 mm Fan Ø 500 mm Fan Ø 630 mm Fan Ø 800/910 mm 2) Fan diameter Ø Quiet noise level Residential noise level S* std…
-
ky Alfa V- ACV ky General Contents General Features All products are designed to satisfy both commercial and industrial refrigeration, air conditioning, and retail refrigeration. All axial condensers are available in the following versions: • Vertical airflow direction • Most common refrigerant HFC…
-
Sound Data
The sound pressure level is based on the calculation (according to EN 13487) of the sound pressure level on the surface of a cuboid area which is at a 10 metre distance and is parallel to the reference envelope of the sound source. (Standard sound pressure level; annex C EN 13487) Sound pressure…
-
ky Alfa V- ACV ky Product description Application The Alfa Laval Condenser can be used in refrigeration and air conditioning equipment. Standard design Coil Optimized “V-type” design provides large capacity within a compact size. An innovative heat exchanger that gives excellent heat transfer with…
-
• • • Product description Corrosion / Shock / Condensation / UV-resistant Wide range of solutions IP66 for casing, IP56 for switchboard 100% recyclable • Fan step control • Energy saving • Cheapest method of controlling performance • Fan speed control • Energy saving • Noise reduction when air…
-
Capacity
-
таблицы и схемы — в просмотре
-
Capacity
-
ky Alfa V- ACV ky Options Motor fans (a) Fan motor 400 V/3ph - 60Hz, IP54: S/L/Q/R for Ø 800/910 Model: (b) Fan motor 460 V/3ph - 60Hz, IP54: S/L/Q/R for Ø 800/910 Ø 800 (a,b) Ø 910(a,b) Local safety switch wired See Electrical Data Page. Model: All Models Terminal Box See Electrical Data Page.…
-
Switchboard Options
R anti-condensate resistor 230Vac (operating temperature -25 ÷ +35°C) Model: C cooling fan 230Vac (operating temperature -10 ÷ +50°C) All Models F cooling fan + anti-condensate resistor Switchboard with Fan Speed control Switchboard and cabling, including an electronic fan speed controller…
-
Vibration Dampers
-
ky Alfa V- ACV ky Electrical Data Safety Switch Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic Case Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min IP65…
-
Terminal Box Function Connection box for electric fan motor General data Material: Plastic IP Protection Class: Min RAL 7035 Colour: Grey RAL 7035 Insulation Class: II Ambient Temp.: min. -40°C, max. +80°C Weight: Approx. 0.5Kg. Dimensions 227
-
Current Distribution Function Current distributors are available as optional accessories. Numerous fans can be connected. In combination with Fcontrol frequency inverters, we can deliver the current distribution with both main switch and bypass function. Features: The current distributor is equipped…
-
Frequency Converter (Inverter) Function Frequency inverter (incl. sine filter) for 3~ motors. Universal controller for refrigeration and air conditioning line input 3~ 208-480V, housing IP54, internal display. • Speed controller with manual adjustment of output voltage at the unit or via external…
-
Dimensions
-
ky Alfa V- ACV ky Code description Code No. ACV S 80 2 A 1) Type of noise level (number of dB(A) to reduce compared with "base" version) Standard noise level Fan Ø 800/910/1000 mm Low noise level Quiet noise level Residential noise level S* L* Q* R* std -7 -17 -20 2) Fan diameter Ø 80 800 mm 90 910…
-
ky Centrifugal Units ky General Content General Features The Alfa Laval centrifugal condenser range is suitable for use in all refrigeration and air conditioning applications. All units can be built for either horizontal or vertical discharge, with vertical coils and single bank modules from 1 to 4…
-
Sound Data
The sound pressure level is based on the calculation (according to EN 13487) of the sound pressure level on the surface of a cuboid area which is at a 10 metre distance and is parallel to the reference envelope of the sound source. (Standard sound pressure level; annex C EN 13487) Sound pressure…
-
ky CRC/CRI ky Product description Application The Alfa Laval Condenser can be used in refrigeration and air conditioning equipment. Standard design Coil The heat exchanger provides excellent heat transfer with minimal refrigerant charge as a result of the new fin corrugation developed by Alfa Laval…
-
Capacity
-
Dimensions (mm)
-
ky CRC/CRI Options ky Local safety switch wired Local safety switch and cabling for each electric fan motor. Plastic covering box, IP65, nominal current 16A – 3 phases, insulated voltage 600V. Material / Colour: Polycarbonate grey (yellow-red handle) Mechanical duration: 20,000 operations. Operating…
-
ky CRC/CRI ky Electrical Data Safety switch Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic Case Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min IP65 Ambient…
-
ky CRC/CRI ky Code description Code No. CRC V 17 CE 50 Pa 1) Airflow V Vertical Flow H Horizontal Flow 2) Range of capacity (from 17 to 92kW) 3) Type of fan: Centrifugal Radial 4) Static pressure. (Please specify when placing the order) 50 Pa Standard Pressure 100 Pa No Standard Pressure 150 Pa No…
-
AlfaBlue Dry Coolers
General Content . ky AlfaBlue Dry Coolers ky General Content General Features Energy Efficiency Class A dry cooler is a forced convection air-cooled fluid cooler, designed for outdoor installation. Air is forced over a finned coil which contains the working fluid such as water or a water and glycol…
-
AlfaBlue Dry Coolers
General Content Sound Data The sound pressure level is based on the calculation (according to EN 13487) of the sound pressure level on the surface of a cuboid area which is at a 10 metre distance and is parallel to the reference envelope of the sound source. (Standard sound pressure level; annex C…
-
ky BDM - Single Fan Row ky Product description Application Alfa Laval Dry Coolers can be used in refrigeration, air conditioning equipment and in industrial cooling (cooling of water or other different fluids, food, power, process and general industry). Standard design Coil This innovative heat…
-
Fans
On the BDM, four different fan diameters are available: 630, 800, 910, 1000 mm. Diameter 630, 800, 910, 1000 mm with three-phase motor 400V-50Hz, for 630 (L, Q, R) also single-phase 230V-50Hz. The motors come with external rotors, protection class IP 54 according to DIN 40050, while integrated…
-
Pressure Drop
-
таблицы и схемы — в просмотре
-
Pressure Drop
-
таблицы и схемы — в просмотре
-
Serie
-
VERTICAL POSITION
-
ky BDM - Single Fan Row ky Options Motor fans (a) Fan motor 400 V/3ph - 60Hz, IP54: Q/R for Ø 630/800/910/1000 and also S/L for Ø 630/800/910 Model: (b) Fan motor 460 V/3ph - 60Hz, IP54: Q/R for Ø 630/800/910/1000 and also S/L for Ø 630/800/910 Ø 630(a,b,c) (c) Fan motor 230V/1ph - 50/60Hz, IP54…
-
Switchboard and cabling
Function Switchboard for supply and control of fan motors. A switchboard can supply up to 8 individual motors or 8 paired motors (i.e. max. of 16 motors). Model: BDM All Models Switchboard and cabling are supplied as standard for vertical installation of the unit. If you have different needs, please…
-
Non-standard fin spacing
The standard fin spacing is 2.1mm. Model: Alternative: 2.5mm and 3.2mm All Models Flanges AISI Model: All Models Feet H Horizontal Position (500 and 850mm) Model: A Feet adjustable from 350-950cm All Models V Vertical Position Vibration Dampers Model: BDM Type H mm A mm B mm C mm D mm Weight Kg…
-
ky BDM - Single Fan Row ky Electrical Data Safety Switch Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3PCabinet Material: Plastic Case Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min…
-
Safety Switch EMC Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic case with internal copper-painted Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min IP65…
-
Terminal Box Function Connection box for electric fan motor General data Material: Plastic IP Protection Class: Min RAL 7035 Colour: Grey RAL 7035 Insulation Class: II Ambient Temp.: min. -40°C, max. +80°C Weight: Approx. 0.5Kg. Dimensions 258
-
Switch Board (Control Panel) Function Basic Version for Horizontal Installation General data Cabinet Material: Sheet steel 15/10mm zinc-coated Internal Plate: Sheet steel 20/10mm zinc-coated Protection Class: IP 55 Cabinet Colour: RAL 7035, light grey polyester paint Cabinet Doors: Opening angle…
-
Electric wiring diagram
Q1 1 3 K1 K2 K3 K4 K5 K6 (2) NOTE : (1) (2) (3) (4) EXTERNAL SHORT CIRCUIT PROTECTION MAX FUSE REMOVE JUMPERS WHEN SPEED CONTROLLER IS ORDERED NOT MOUNTED WHEN FAN SPEED CONTROLLER IS ORDERED SCHIELDED CABLE TO BE USED ONLY WHEN EMC CABLING OPTION IS REQUESTED X2 X2 X1 (1) NOTE : (1) REMOVE JUMPER…
-
Switch Board (Control Panel) Function Basic Version for Vertical Installation General data Cabinet Material: Sheet steel 15/10mm zinc-coated Internal Plate: Sheet steel 20/10mm zinc-coated Protection Class: IP 55 Cabinet Colour: RAL 7035, light grey polyester paint Cabinet Doors: Opening angle 110°…
-
Electric wiring diagram
Q1 1 3 K1 K2 K3 K4 K5 K6 (2) NOTE : (1) (2) (3) (4) EXTERNAL SHORT CIRCUIT PROTECTION MAX FUSE REMOVE JUMPERS WHEN SPEED CONTROLLER IS ORDERED NOT MOUNTED WHEN FAN SPEED CONTROLLER IS ORDERED SCHIELDED CABLE TO BE USED ONLY WHEN EMC CABLING OPTION IS REQUESTED X2 X2 X1 (1) NOTE : (1) REMOVE JUMPER…
-
Current Distribution Function Current distributors are available as optional accessories. Numerous fans can be connected. In combination with Fcontrol frequency inverters, we can deliver the current distribution with both main switch and bypass function. Features: The current distributor is equipped…
-
Frequency Converter (Inverter) Function Frequency inverter (incl. sine filter) for 3~ motors. Universal controller for refrigeration and air conditioning line input 3~ 208-480V, housing IP54, internal display. • Speed controller with manual adjustment of output voltage at the unit or via external…
-
Dimensions
-
ky BDM - Single Fan Row ky Code description Code No. BDM S 63 2 A 1) Type of noise level (number of dB(A) to reduce compared with "base" version) Residential noise level Turbo noise level Standard noise level Low noise level Quiet noise level T S* L* Q* R* - base -10 -18 -29 Fan diameter Ø 800mm…
-
ky BDD/BDD6 - Double Fan Row ky Product description Application The Alfa Laval dry coolers can be used in refrigeration, air conditioning equipment and in Industrial Cooling (cooling of water or other different fluids), Power, Process and General Industry. Standard design Coil Innovative heat…
-
• Fan speed control
• Energy saving • Noise reduction when the air temperature is below the design temperature. • Variable and efficient speed control according to the heat rejected • Better performance control • Special fans • 480/3ph-60Hz IP54: High adaptability for every market • IP 55: High protection fan for use…
-
Airflow [m 3/h]
-
таблицы и схемы — в просмотре
-
Airflow [m 3/h]
-
таблицы и схемы — в просмотре
-
Airflow [m 3/h]
-
таблицы и схемы — в просмотре
-
VERTICAL POSITION
-
ky BDD/BDD6 - Double Fan Row ky Options Motor fans (a) Fan motor 400 V/3ph - 60Hz, IP54: Q/R for Ø 800/910/1000, S/L only for Ø 800/910 Model: (b) Fan motor 460 V/3ph - 60Hz, IP54: Q/R for Ø 800/910/1000, S/L only for Ø 800/910 Ø 800 (a,b) Ø 910(a,b) Ø1000 (a,b) Local safety switch wired See…
-
Switchboard and cabling
Function Model: Switchboard for supply and control of fan motors. All Models A switchboard can supply up to 8 individual motors or 8 paired motors (i.e. max. of 16 motors). Switchboard and cabling are supplied as standard for vertical installation of the unit. If you have different needs, please…
-
Non-standard fin spacing
The standard fin spacing is 2.1mm. Model: Alternative: 2.5mm and 3.2mm All Models Spray water Consisting of a pipe system with several fitted spraying nozzles that nebulise water in the air suction of Model: the coil. Spray water comes mounted on delivery. All Models Feet V Vertical Position Model…
-
ky BDD/BDD6 - Double Fan Row ky Electrical Data Safety Switch Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic Case Cabinet Colour: Grey (Yellow-Red Knob) Protection Class…
-
Safety Switch EMC Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic case with internal copper-painted Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min IP65…
-
Terminal Box Function Connection box for electric fan motor General data Material: Plastic IP Protection Class: Min RAL 7035 Colour: Grey RAL 7035 Insulation Class: II Ambient Temp.: min. -40°C, max. +80°C Weight: Approx. 0.5Kg. Dimensions 282
-
Switch Board (Control Panel) Function Basic Version for Horizontal Installation General data Cabinet Material: Sheet steel 15/10mm zinc-coated Internal Plate: Sheet steel 20/10mm zinc-coated Protection Class: IP 55 Cabinet Colour: RAL 7035, light grey polyester paint Cabinet Doors: Opening angle…
-
Electric wiring diagram
Q1 1 3 K1 K2 K3 K4 K5 K6 (2) NOTE : (1) (2) (3) (4) EXTERNAL SHORT CIRCUIT PROTECTION MAX FUSE REMOVE JUMPERS WHEN SPEED CONTROLLER IS ORDERED NOT MOUNTED WHEN FAN SPEED CONTROLLER IS ORDERED SCHIELDED CABLE TO BE USED ONLY WHEN EMC CABLING OPTION IS REQUESTED X2 X2 X1 (1) NOTE : (1) REMOVE JUMPER…
-
Switch Board (Control Panel) Function Basic Version for Vertical Installation General data Cabinet Material: Sheet steel 15/10mm zinc-coated Internal Plate: Sheet steel 20/10mm zinc-coated Protection Class: IP 55 Cabinet Colour: RAL 7035, light grey polyester paint Cabinet Doors: Opening angle 110°…
-
Electric wiring diagram
Q1 1 3 K1 K2 K3 K4 K5 K6 (2) NOTE : (1) (2) (3) (4) EXTERNAL SHORT CIRCUIT PROTECTION MAX FUSE REMOVE JUMPERS WHEN SPEED CONTROLLER IS ORDERED NOT MOUNTED WHEN FAN SPEED CONTROLLER IS ORDERED SCHIELDED CABLE TO BE USED ONLY WHEN EMC CABLING OPTION IS REQUESTED X2 X2 X1 (1) NOTE : (1) REMOVE JUMPER…
-
Current Distribution Function Current distributors are available as optional accessories. Numerous fans can be connected. In combination with Fcontrol frequency inverters, we can deliver the current distribution with both main switch and bypass function. Features: The current distributor is equipped…
-
Frequency Converter (Inverter) Function Frequency inverter (incl. sine filter) for 3~ motors. Universal controller for refrigeration and air conditioning line input 3~ 208-480V, housing IP54, internal display. • Speed controller with manual adjustment of output voltage at the unit or via external…
-
Dimensions
-
ky BDD/BDD6 - Double Fan Row ky Code description Code No. BDD or BDD6 S 80 2 A 1) Type of noise level (number of dB(A) to reduce compared with "base" version) Turbo noise level Standard noise level Low noise level Quiet noise level Residential noise level T S* L* Q* R* Fan diameter Ø 800mm - base -7…
-
AlfaGreen Dry Coolers
General Content . ky AlfaGreen Dry Coolers ky General Content General Features Tube Protection A dry cooler is a forced convection air-cooled fluid cooler, designed for outdoor installation. Air is forced over the finned coil which contains the working fluid such as a water and glycol mix. When…
-
AlfaGreen Dry Coolers
General Content Sound Data The sound pressure level is based on the calculation (according to EN 13487) of the sound pressure level on the surface of a cuboid area which is at a 10 metre distance and is parallel to the reference envelope of the sound source. (Standard sound pressure level; annex C…
-
ky DC - Single Fan Row Product description ky Application Refrigeration of liquids for: • industrial refrigeration; • food, power; • process & general industry; • air conditioning. Standard design Coil The heat exchanger gives heat transfer with minimal fluid volume, as a result of new fin…
-
Capacity
-
Ø 500
-
ky DC - Single Fan Row ky Options Motor fans (a) Fan motor 400 V/3ph - 60Hz, IP54: S/Q/R Model: (b) Fan motor 460 V/3ph - 60Hz, IP54: S/Q/R All Models (c) Fan motor 230V/1ph - 50/60Hz, IP54: S/L/Q Local safety switch wired Local safety switch and cabling for each electric fan motor. Plastic covering…
-
Feet
-
ky DC - Single Fan Row ky Electrical Data Safety Switch Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic Case Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min…
-
ky DC - Single Fan Row ky Code description Code No. DC S 50 2 A 1) Type of noise level (number of dB(A) to reduce compared with "base" version) Standard noise Low noise level level Fan Ø 500 mm Quiet noise level Residential noise level S* L* Q* R* std -9 -19 - 2) Fan diameter Ø 50 500 mm 3) Number…
-
ky Alfa V- VDD/VDD6 ky General Contents General Features Energy Efficiency Class A dry cooler is a forced convection air-cooled fluid cooler, designed for outdoor installation. Air is forced over the finned coil which contains the working fluid such as a water and glycol mix. When determining the…
-
Sound Data
The sound pressure level is based on the calculation (according to EN 13487) of the sound pressure level on the surface of a cuboid area which is at a 10 metre distance and is parallel to the reference envelope of the sound source. (Standard sound pressure level; annex C EN 13487) Sound pressure…
-
ky Alfa V- VDD/VDD6 ky Product description Application Refrigeration and air conditioning applications: • water cooling • free cooling Standard design Coil Optimized “V-type” design provides large capacity within a compact size. This innovative heat exchanger design gives excellent heat transfer…
-
• Switch on/off
• Local safety switch wired to isolate the fan. An EMC switch is also available • Terminal box • All fans are wired for easy connection to the electrical supply • Design for frequency converter • Units can run under frequency control (when air temperature falls below the designated level, it…
-
Airflow
-
таблицы и схемы — в просмотре
-
Capacity
-
таблицы и схемы — в просмотре
-
Capacity
-
таблицы и схемы — в просмотре
-
Capacity
-
таблицы и схемы — в просмотре
-
Capacity
-
таблицы и схемы — в просмотре
-
ky Alfa V- VDD/VDD6 ky Options Motor fans (a) Fan motor 400 V/3ph - 60Hz, IP54: S/L/Q/R for Ø 800/910 Model: (b) Fan motor 460 V/3ph - 60Hz, IP54: S/L/Q/R for Ø 800/910 Ø 800 (a,b) Ø 910(a,b) Local safety switch wired See Electrical Data Page. Model: All Models Terminal Box See Electrical Data Page.…
-
Switchboard Options
R anti-condensate resistor 230Vac (operating temperature -25 ÷ +35°C) Model: C cooling fan 230Vac (operating temperature -10 ÷ +50°C) All Models F cooling fan + anti-condensate resistor Switchboard with Fan Speed control Switchboard and cabling, including an electronic fan motor speed controller…
-
ky Alfa V- VDD/VDD6 ky Electrical Data Safety Switch Function Local safety switch and cabling for each electric fan motor. General data Power Supply: • 400VAC, 50/60Hz • Max fuse 16A Number of poles: 3P Cabinet Material: Plastic Case Cabinet Colour: Grey (Yellow-Red Knob) Protection Class: Min IP65…
-
Terminal Box Function Connection box for electric fan motor General data Material: Plastic IP Protection Class: Min RAL 7035 Colour: Grey RAL 7035 Insulation Class: II Ambient Temp.: min. -40°C, max. +80°C Weight: Approx. 0.5Kg. Dimensions 320
-
Current Distribution Function Current distributors are available as optional accessories. Numerous fans can be connected. In combination with Fcontrol frequency inverters, we can deliver the current distribution with both main switch and bypass function. Features: The current distributor is equipped…
-
Frequency Converter (Inverter) Function Frequency inverter (incl. sine filter) for 3~ motors. Universal controller for refrigeration and air conditioning line input 3~ 208-480V, housing IP54, internal display. • Speed controller with manual adjustment of output voltage at the unit or via external…
-
Dimensions
-
ky Alfa V- VDD/VDD6 ky Code description Code No. VDD or VDD6 S 80 2 A 1) Type of noise level (number of dB(A) to reduce compared with "base" version) Standard noise level Fan Ø 800/910/1000 mm Low noise level Quiet noise level Residential noise level S* L* Q* R* std -7 -17 -20 2) Fan diameter Ø 80…
-
ky Treatment ky Corrosion prevention for Air Coolers . • Corrosion prevention for Air Coolers • Indoor & outdoor applications • Material optimisation 325
-
Legend Component Tubes Fins COIL Overall materials or treatments Internal drip tray Casing Visible sheets External drip tray Impeller Fan Motor Material Cu SS Al Alprv Cu Al+Cat Al+T Al StZn Cat StZn+T SS Al SS Al Alprv StZn SS Al Alprv SS Al Al coated Fibreglass IP54 IP55 Description Copper…
-
Indoor installation
APPLICATION Fish Dairy Pasta Fruit Tubes Fins Normal use Pre-cooling rooms for half carcasses Cu Al Cu Al / Alprv Al / StZn Al Al / Alprv Al / Alprv Processing rooms Cu Al / Alprv Al / StZn Al Al / Alprv / SS SS Al / Alprv / SS SS Al / Alprv / SS SS Al / Alprv SS Al / Alprv / SS SS Al / Alprv / SS…
-
Outdoor installation
APPLICATION Condensers Coil Tubes Fins Fans Casing Overall materials Visible sheet or treatments Feet Impeller Motor Normal use Cu Al StZn StZn Painted StZn Painted Al IP54 Industrial environment (e.g. a polluted suburban area) Cu Alprv StZn StZn Painted StZn Painted Al IP54 Note Additional regular…
-
ky Evaporative Cooling Device ky For AlfaBlue Dual and Alfa V General The device consists of a pipe system with several fitted spraying nozzles that nebulise water in the air suction of the coil. The spray water solution is used to increase the cooling capacity of the units, by humidification of air…
-
The efficiency of the spray water device influenced by
• Relative humidity • Ambient temperature • Fan motor airflow • Wind When the correlation between relative humidity and water absorption degree of efficiency is non-linear. For example, if relative humidity is 90%, the air is almost saturated; using the spray water device will indicate any abnormal…
-
V-type standard noise and V-type low noise
MODEL Series VDD VDD6 ACV VDD VDD6 ACV VDD VDD6 ACV VDD VDD6 ACV VDD VDD6 ACV VDD VDD6 ACV VDD VDD6 ACV Length mm Number of nozzles Double Row Standard noise and Double Row Low noise Total water flow inlet (l/min) Electrical wiring. D Y Noise level Ø mm S/L 802/902 2620 4 5.2 2.4 S/L 803/903 3930 6…
-
Below is a psychometric chart
-
Water quality
NOZZLE MAINTENANCE With this kit only use water with the following characteristics: The nozzles need regular maintenance in order to maintain their efficiency and prevent damage. We suggest making a first check after 5 hours of running before making future checks every 100 hours. pH: 6÷7 Hardness: 8…
-
ky AlfaStreamer ky AlfaStreamer Abstract To describe the characteristics of a streamer used in air coolers. The streamer, a plug and play optional, provides the cooler with a higher air throw but without disadvantages like increased power consumption or noise levels. The Alfa Laval units tested show…
-
This equation can be modified to
p=#RT where # = m / V or better: with: p = absolute pressure (N/m2, lb/ft2) T = absolute temperature (°K, °R) xv= mole fraction of water vapour Ma= molar mass of dry air Mv= molar mass of water (18.015*10-3 Kg*mol-1) Z= compressibility factor R = individual gas constant (J/Kg.°K, ft.lb/slugs.°R) In…
-
with
!t0 = the temperature difference between the air stream and the ambient air v0 = velocity at the diffuser/valve outlet [m/s] K = the diffuser coefficient Aeff = the diffuser or valve’s effective outlet area [m2] Fans (key component) Every fan must overcome the resistance occurring when taking the…
-
Air velocity
The air throw, defined by CECOMAF- standard GT6-001 and ENV 328 as the distance between the fan and the point on the rotation axis where the outflow velocity reaches a limit of 0.25m/s, is used as the main criterion. However, it must be considered that in industrial application the velocity limit…
-
If the air velocity along the room is not enough to assure an optimal cold air distribution, the air stream will deflect and start looping. To avoid this effect you can: • increase the number of cooling units. • increase the rotational speed of the motor. • use long textile socks. All the proposed…
-
Plotted In red is the velocity of air of a standard unit, reached at different distances. As was expected, the velocity decreases with increased distance from the fan due to the mixing processes in the exhaust stream with other air in the room. It’s important to emphasise that the fan’s performance…
-
Graph 2 plots the results of unit INRW503K60W(B). Note that the limit velocity as ENV 328 rule (0.25m/s) is reached at 24 m without streamers. With streamers it is possible to increase the air throw to 11m; with the streamer the limit velocity was reached at 35m. When the limit velocity is…
-
Graph 3
Benefit of Streamers • Concentration of the outflow stream in axial direction. • Uniform and high efficient cooling of large rooms. • No energy losses • No fan efficiency performance disruption. • No noise • Easy installation 341
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.