Чиллеры AQL, AQH. Технический каталог 2007г.
Модели 20-35. Чиллеры AQL, AQH. Технический каталог 2007г.
Загружаем документ…
Текст каталога
-
u Air Cooled Water Chillers
AQL (Cooling Only Version) AQH (Heat Pump Version) Models 20 to 35 19.1 to 35.9 kW 20.5 to 38.6 kW Engineering Data Manual EDM AQ410-A.1GB Date : September 2007 Supersedes : None
-
Key Points
R410A refrigerant. Simpler refrigerant circuit layout. Units are suitable for low water temperature applications with leaving water temperature of -8 °C (min.). Great accessibility to internal components for service operations. ModBus interface. New display on external panel allowing the…
-
Specifications (continued)
Condenser fans Each unit has two axial fans with 610 mm of diameter. The fans are placed directly in front of the coil in order to increase air flow and heat transfer between air and refrigerant. They are fitted with protective grilles. The condenser fans have 2 speeds : 630 rpm for normal operating…
-
Refrigerant Flow Diagram - AQL R410A
2 A AT SH SL M BT OIL EQUAL. 1 H F L C 6 D E 5 Page 4 I 8 S components 1 Compressor tandem scroll type 2 Air cooled condenser 3 Filter drier 4 Sight glass 5 Thermostatic expansion valve 6 Plate heat exchanger 7 Pump 8 Drain valve 9 Water buffer tank 10 Water filter (supplied loose) 11 Automatic…
-
Refrigerant Flow Diagram - AQH R410A
3 2 AT A SH H D OFF BT M OIL EQUAL. 1 SL F L C 8 G E 7 N I 10 S 10 N FS components 1 Compressor tandem scroll type 2 4-way valve 3 Air cooled condenser 4 Biflow filter drier 5 Sight glass 6 Biflow thermostatic expansion valve 7 Liquid receiver 8 Plate heat exchanger 9 Pump 10 Drain valve 11 Water…
-
Operating Limits
20 Min. Max. °C -8 18 K 3 8 l/h 2050 5466 barg °C -10 50 l 48 AQL/AQH in cooling mode Water outlet temperature * Water ∆T Flow rate Max. operating pressure Water Air temperature Optimal water volume 25 30 Min. -8 3 2676 Max. 18 8 7135 -10 50 Min. -8 3 3318 Max. 18 8 8847 35 Min. Max. -8 3858 10287…
-
Correction factors
Fouling factors - Evaporator Fouling factor (m2.°C/kW) Cooling capacity factor Power input factor 0.044 1.000 1.000 0.088 0.987 0.995 0.176 0.964 0.985 0.352 0.915 0.962 Fouling factor (m2.°C/kW) Cooling capacity factor Power input factor 0.044 1.000 1.000 0.088 0.987 1.023 0.176 0.955 1.068 0.352…
-
Physical Data - AQL R410A
AQL sizes Cooling capacity kW Power input (compressor) kW 19.1 24.9 30.9 35.9 5.5 7.5 10.0 11.2 Total EER* 3.13 3.06 2.93 3.0 Energy class A B B B ESEER 5.00 4.94 4.37 4.08 IPLV 5.25 5.19 4.59 4.28 Number of refrigerant circuits Part load steps 0-50-100 0-50-100 0-50-100 0-50-100 Power supply %…
-
Physical Data - AQH R410A
AQH sizes Cooling capacity kW Power input (compressor) kW 19.1 24.9 30.9 35.9 5.5 7.5 10.0 11.2 Total EER* 3.13 3.06 2.93 3.01 Energy class A B B B 5.00 4.94 4.37 4.08 4.28 ESEER IPLV 5.25 5.19 4.59 Heating capacity kW 20.5 27.6 34.5 38.6 Power input (compressor) kW 5.44 7.94 9.74 11.38 3.39 3.21…
-
Electrical Data
Units* Sizes Max. power input Max. current input Start-up current kW A A 20 10.1 21.5 62 25 13.6 25.5 80 30 15.8 35.3 94 35 18.0 35.3 121 * Data given for unit with one pump. Data given for compressor at maximum conditions. Compressors Power input at max. conditions per compressor (kW) 4.3 4.3 6.1…
-
Performance Data - AQL R410A
25 AQL 20 AQL 25 AQL 30 AQL 35 20.1 4.5 21.3 4.6 22.4 4.6 23.6 4.7 24.8 4.8 26.1 4.9 27.4 5.0 27.9 5.1 26.2 6.0 27.8 6.2 29.3 6.2 30.8 6.4 32.4 6.5 34.1 6.6 35.7 6.8 36.4 6.8 32.5 8.1 34.4 8.3 36.3 8.4 38.2 8.6 40.2 8.7 42.3 8.9 44.3 9.1 45.2 9.2 37.8 9.0 40.0 9.2 42.2 9.3 44.4 9.5 46.7 9.7 49.2 9.9…
-
Performance Data - AQH R410A
Cooling mode 25 Ambient air temperature (°C) AQH LWT Cool. Input Cool. Input Cool. Input Cool. Input Cool. Input Cool. Input Cool. Input Cool. Input Cool. Input sizes (°C) cap. power* cap. power* cap. power* cap. power* cap. power* cap. power* cap. power* cap. power* cap. power* (kW) (kW) (kW) (kW)…
-
Pump and Plate Heat Exchanger Curves - AQL/AQH R410A
kPa 30-35 20-25 1700 2200 2700 3200 3700 4200 4 20-25 4700 5200 30-35 5700 6200 Water flow (l/h) 1 and 2 pump static head pressure curves. 3 and 4 plate heat exchanger water pressure drop curves. 850 30-35 Power input (W) 750 650 20-25 1700 2200 2700 3200 3700 4200 4700 5200 5700 6200 Water flow…
-
Dimensions - External Hydrokit for AQL/AQH R410A 20 to 35
Front view Side view 43 A C 186 390 B 92 Top view holes Ø9 62,5 1352 1477 33 62,5 A B C Water inlet Ø1 ½" gas male Water outlet Ø1 ½" gas male Tank fill Ø1/2" gas male Dimensions in mm. Page 15
-
Space requirements - AQL/AQH R410A 20-35
200 mm 200 mm 200 mm 400 mm 800 mm Your distributor : ACE Marketing S.A.S. CAC Export Department 42 cours Jean-Jaurès 17800 Pons - France Tel. : +33 (0)5 - Fax : +33 (0)5 www.airwell.com As part of our ongoing product improvement programme, our products are subject to change without prior notice.…