DC inverter air to water heat pump all in one Series A
INSTALLATION AND OPERATING INSTRUCTIONS DC INVERTER SERIES INSTALLATION AND OPERATING INSTRUCTIONS AIR TO WATER INSTALLATION AND OPERATING INSTRUCTIONS MODELS: KS50-DC / KS70-DC / KS90-DC KS120-DC / KS150-DC - MONOBLOC SYSTEM SERIES A - HEATING & COOLING - AIR TO WATER HEAT PUMP WITH DC INVERTER…
-
WELCOME
Congratulations on your selection of our heat pump for your comfort conditioning requirements. Your home is fitted with a unique renewable heating technology, allowing you to benefit from lower running costs and a more even temperature throughout your home. An air source heat pump collects and…
-
Summary
1. Warning p4 2. Safety warnings p4 3. Principle of working p5 4. Checking before and after starting p5 5. Pump capacity diagrams p6 6. Installation outdoor unit p7 7. The step and diagram of collect refrigerant p8 8. Diagram for installation and connection p9 9. Pipe connection for floor heating…
-
1. Warnings
This manual is an integral part of the machine and must always be reachable in your technical room. This Heat pump is meant exclusively for heating or cooling. Any other non-conform and random use will be considered as dangerous and unsuitable. The assembly, the electric connection and the start up…
-
3. Principle of working
The operation of the heat pump is shown below. A heat pump works on the same principle as a fridge using a refrigerant fluid which boils at low temperature. Free energy is take from the air to boil the refrigerant in the evaporator coil, changing it from a liquid to a vapour. This low grade heat is…
-
5. Pump capacity diagrams
Wilo-Yonos PARA High Flow 25/10 6 / 41
-
6. Installation outdoor unit
6.1 Select the installation place of outdoor unit The outdoor unit should be installed on a solid wall and fastened securely. The following procedure must be observed before connecting the pipes or electric cables. 1) Decide which is the best position on the wall and leave enough space to be…
-
7. The step and diagram of collect refrigerant
If the machine needs to be disconnected and moved to another place or refrigerant charging, please recycle the gas back into the compressor according to the following steps before doing the disconnecting: 1.Turn to the menu: OPERATION---MAN TEST 2. Remove the cap of two valves with the spanner. 3.…
-
8. Diagram for installation and connection
Using for floor heating and water tank heating Wat er Ou tlet Water Inlet PCB 3-Way Valve Electrical He ater Wat er pu mp Water Tank Outside Unit Heat ex changer Inside Unit Floor Blowing AV closes AV1 Parti cle Fil te r AV2 Drai n Valve Indoor Outdoor Using for radiator and water tank heating Water…
-
10. Filling & venting the water circuit system
1. Check the heating medium system for leakage; 2. Please follow the fig.1 (on page 10) to connect the pipeline, the water filling pump and the service connections; the capacity of external filling pump must be at least 3 m3/h; 3. Before galvanize to heat pump, Three Way Valve was in "A" state (the…
-
11. Installation master plan
When the electric heater was breakdown, and it is need to be taken down to repair. You can take out the electric heater through L1 L2 L3 N this hole. WTT WTT connecting abov e 1 0 cm High Pressure Valve Water tank abo ve 50c a bo 15c ve m m The left-side must spacious if only 45 -50cm distance at…
-
12. Description of the display panel and menu
12.1 Control panel The control panel of DC inverter series features a graphic display with five control buttons. 12.2 Functions The control computer is operated via a menu system displayed on the control panel. There is a main menu and several sub-menus accessible from the main menu. The menus are…
-
12.3 Symbols
For you to know at a glance the actual operating mode of the heat pump, each of the following symbols will be shown in the lower part of the display depending on which part of the unit is working: Symbols description The heat pump is running. 95% Running speed percentage of compressor The auxiliary…
-
OPERATION
Running mode: Water tank heating, Room heating, Room heating 1, Room heating 2, Auto. HEATCRVE The setting of this submenu will affect the room temperature; CURVE is program that adjusts feed water temperature according outdoor ambient temperature, factory setting is ambient temperature 0℃ as feed…
-
ROOMHEAT 1
Room heating mode 1 heats the room only. In this mode the heat pump runs according to feed water temperature. You can set the feed water temperature directly. Adjustable from 20℃ to 65℃. Factory setting is 45℃. ROOMHEAT 2 Room heating mode 2: this mode only heats room. Heat pump runs according to…
-
Menu Text
Description Adjustable by CURVE The value entered shows the temperature of water to be distributed to radiators (feed water temperature) when outside air temperature is 0℃. User. See “adjustment CURVE value”. MIN Adjustment of value for lowest feed water temperature allowed. User. See “adjustment of…
-
RETURN: Display real return water temperature
PIPE: Display outdoor unit evaporator temperature for defrosting. OUT: Display real outdoor ambient temperature. CMPDIF TEMP: Compressor restart determined by the cooling of water tank. This setting is only for water tank heating. it is adjustable from 3℃ to 15℃. Factory setting is 5℃. CONSTANT…
-
Temperature difference between Temperature difference between The corresponding the feed water and the desired the feed water and the desired value water (℃) water(℃) The corresponding value -31 ~ -40 -40 1 ~ 10 10 -21 ~ -30 -30 11 ~ 20 20 -11 ~ -20 -20 21 ~ 30 30 -1 ~ -10 -10 31 ~ 40 40 DM = the…
-
The constant temperature function is only available in
Room heating, but not in water tank HEATING. Constant temperature function has two options: integral (DM) and constant room temperature. 1. The constant area diagram: T1-- room return water temperature, Ts-- room air setting temperature or feed water temperature. After compressor start running, when…
-
12.4.6 Sub-Menu TIME SETTING
How to enter the sub-menu TIME SETTING Choose TIME SETTING on the main menu INFORMATION by pressing Right button, TIME SETTING menu can be seen. TIMESETTING:use Up and Down buttons to select each item. DATE: To display year, month, day. DAY: To display the day of the week. TIME: To display or adjust…
-
12.4.7 Sub-Menu DEFROST
How to enter the sub-menu DEFROST Choose DEFROST on the main menu INFORMATION by pressing Right button, DEFROST menu can be seen. You can choose intelligent defrost or manual defrost. INTELLIGENT DEFROST Intelligent defrost. Once you choose this function defrosting is intelligent and automatic. When…
-
MANUAL.DEF
Manually defrost (adjustable defrost program) This function is semi-automatic. for example the operator can change the value of interval (the distance between defrosting) to be 40 minutes, and the START TEMP (the start temperature of defrosting) to be-4℃. If the defrosting time request and…
-
When in water tank heating, the electrical heater will function instead of the compressor
When in room heating mode the electrical heater will run depending on Integral. When in room heating 1 mode, the electrical heater will run depending on Integral. When in room heating 2 mode, the electrical heater automatically starts. EMERGENCY2 Is either ON or OFF, Factory setting is OFF. If you…
-
OUTADD.HEAT ON (OFF)
Factory setting is ON. To control outdoor unit electrical heater (bottom electrical heater evaporator heater). The heater will start when ambient temperature is lower than 0℃, and stop when ambient temperature is more than 2℃. When outdoor electrical heater is OFF, the outdoor heater can not start…
-
12.4.9 Sub-Menu OPERATING TIME
Sub-Menu RESET Reset to factory setting value. Menu Text Description Adjustable by HEAT PUMP Total operating hours of heat pump since installation. Operating time can not be reset to zero. Total operating hours of auxiliary heater (3KW/6KW/9KW) since installation. Operating time can not be reset to…
-
12.4.14 Adjustments made regularly
* Selection of operating mode. * Adjustment of desired room temperature by changing the room value. * Adjustment of heat curve. * Adjustment of maximum and minimum values for feed line temperature. * Heat Generation-General The indoor temperature should be adjusted by changing the heat curve. The…
-
find the cursor at the parameter CURVE
4. Open the selected parameter by pressing right button once. 5. Increase or reduce the pre-set value using up or down button, you will see from the diagram how the gradient of CURVE changes. 6. Press left button three times to return to main menu. 12.4.16 Adjustment of ROOM value (CURVE ROOM ) You…
-
SLOW START is determined by FEED (heat curve) again,
suppose the feed water temperature is 25℃. You may regulate the heat curve to set the water temperature to be a lower value such as 30℃, that is FEED 25 (30). When that happens the dm would decrease to -10 per minute. The time it takes to -60 becomes longer, meaning it takes that much longer for the…
-
If you wish to change a specific part of the heat curve
1. Open main menu INFORMATION by pressing right button once. You will find the cursor at sub-menu OPERATION. 2. Press down button to move the cursor to sub-menu HEAT CURVE. 3. Open the menu by pressing right button once. You will find the cursor at the parameter CURVE. 4. USING UP OR DOWN BUTTON…
-
factory setting is 70℃; if heat pump is using for floor heating, this setting is very important, because at the time the feed water temperature can not higher than 70℃, otherwise could be dangerous; the heat pump will stop as soon as actual feed water temperature more than MAX setting. If you wish…
-
14. Error codes
This table explains the error codes caused by a defective regulating component or by a security operation. You have to call your retailer. Alarm Explanation DISPLAY EEPROM EEPROM reading failure from display DISPLAY-TRANSITION COMMUNICATE The communications failure between display and main board…
-
5. Check the DC voltage between Positive pole and Negative pole if normal, the DC voltage should be
KS200-DC / 250-DC (triple phase): 540VDC , If it is not, you must change a new module: Positive pole Negative pole 6. Check the if DC voltage between A(first wire) and B(third wire) is normal, it should be 13.5V ~16.5V; if it is not, you must change a new module. A B 7. Check if some place has…
-
The cause of alarm ‘MODULE VOLTAGE OVER’ could be
1. Water flow was not enough; 2. One of the sensors got problem; 3. Ambient temperature was too high 4. Main board or power board (see pictures and name of PCB) has problem. How to do: 1. Check if the water flow was not enough; check if the water flow switch has problem, screw it out and check if…
-
1. Always ensure enough water flow; otherwise the flow switch can not open;
2. Check if the wire connection of high pressure switch was ok, or change a new one; The cause of alarm ‘WARM WATER TEMP.’ could be: 1. The connection of water tank temperature sensor was loose; 2. The water tank temperature sensor was broken; How to do: 1. Find the connection and make sure it is…
-
16. Sensors resistance table 1
-
Sensors resistance table 2
-
17. List of components
Indoor unit: + + 15 14 Room temperature sensor 17 37 / 41 3 Stainless steel plate heat exchanger 4 Water pump 5 Valve 1 6 Valve 2 7 Three way valve 8 Electrical heater rod 9 Electrical heater sleeve 10 Indoor electrical box 11 Connecting terminal 12 Relay for 3 way valve 13 2.5mm2 terminal 14 Drain…
-
Outdoor unit
NO. NAME NO. NAME NO. NAME 1 Top panel 10 Valve 2 19 White terminal 2 Outdoor fan and motor 11 Filter 20 Outdoor main PCB 3 Front grill 12 Electrical expansion valve 21 Relay for electrical heater 4 Bottom plate 13 Low pressure switch 22 Public terminal 5 Compressor 14 Four way valve 23 Fan motor…
-
18. Dimensions
-
WHITE
-
20 . Technical Characteristics